Forwards LERs 81-012/03L-0,81-015/03L-0,81-016/03L-0 & 81-017/03L-0
Date released: 01/17/2020 Download: ML20003H971


LER 81-017/03L-0:on 810405,while Performing FNP-1STP-28.2, LOSP Bif Sequencer Failed to Meet Time Requirements for Picking Up Step 6.Caused by Agastat Timer Setpoint for LOSP Bif Sequencer Drifting Below Setpoint.Timer Adjusted
ML20003H987
Person / Time
Site: Farley 
Issue date: 05/04/1981
From:
ALABAMA POWER CO.
To:
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION II)
References
Download: ML20003H987 (1)
LER 81-016/03L-0:on 810405,during Channel Check Surveillance test,overtemp-delta Temp Instrumentation Loop Associated w/TI412C Declared Inoperable When Trip Setpoint Failed to Meet Tolerance Requirements.Caused by Defective Nll Card
ML20003H984
Person / Time
Site: Farley 
Issue date: 05/04/1981
From: Hairston W
ALABAMA POWER CO.
To:
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION II)
References
Download: ML20003H984 (1)
LER 81-015/03L-0:on 810404,during Channel Check Surveillance Test,Feedwater Flow Loop FT-486 Failed to Meet Tolerance Requirements & Declared Inoperable.Caused by Plug Assembly for Root Valve for Transmitter FT-486 Not Opening
ML20003H976
Person / Time
Site: Farley 
Issue date: 05/04/1981
From: Hairston W
ALABAMA POWER CO.
To:
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION II)
References
Download: ML20003H976 (2)
LER 81-012/03L-0:on 810402,during Testing of Containment 1A Spray Pump,Containment Spray Sys Snubber CS2-Rl31 Declared Inoperable Upon Discovery of Hydraulic Fluid Leakage.Caused by Cracked Reservoir.Reservoir Replaced
ML20003H973
Person / Time
Site: Farley 
Issue date: 05/04/1981
From: Hairston W
ALABAMA POWER CO.
To:
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION II)
References
Download: ML20003H973 (1)
Forwards LERs 81-012/03L-0,81-015/03L-0,81-016/03L-0 & 81-017/03L-0
ML20003H970
Person / Time
Site: Farley 
Issue date: 05/04/1981
From: Clayton F
ALABAMA POWER CO.
To:
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION II)
References
Download: ML20003H970 (1)