SOUTH CAROLINA ELECTRIC a GAS COMPANY POST OFFICE 80x 764 COLUMBIA. SOUTH CAROLINA 29218
[
T. C. NicMots, J R.
Vict Potstormt A80 Gaove Cascv?vyt February 4, 1981 NucLEAm O.cnams L
Mr. Harold R. Denton, Director Office of Nuclear Reactor Regulation U. S. Nuclear Regulatory Commission Washington, D. C.
20555 I
Subject:
Virgil C. Summer Nuclear Station Docket No. 50/395 t
Unexpected Lifting of Pressurizer Safety Valve
Dear Mr. Denton:
This report is submitted in accordance with the requirements of
'NUREG 0737, Item IIK.3, Table C.3 Item 3.
It reflects all events con--
cerning the fa11ure of or challenges to safety / relief valves which occurred at the Virgil C. Summer Nuclear Station through December, 1980.
i Following is a synopsis of our single such event.
I On September 7, 1980, pressurizer safety valve 8010B unexpectedly
[
lifted during the performance of Preoperational Test RC-3, " Pressurizer Pressure and Level Control Functional Test".
This procedure calls for f
Reactor Coolant System (RCS) pressure to be manually increased to verify control functions, alarms, etc.
As RCS pressure was increased, the sub-I ject valve lifted at 2380 psig which is below the proper lift pressure of-2485 psig.
The valve will be reset as a part of the preoperational test program.
There were no failures of valve components or associated systems.
The cause of this event has been determined to be improper setpoint set-ting and is therefore classified as a " challenge.to" pressurizer safety i
valve 8010B.
If further information is needed concerning this matter, please contact me.
a to Very truly yours, p
Ir W
m
?l
[;-[
T. C. Nichols, Jr.
I
. t _a s.
e, s
ARK:TCN;bsg k
I cc: Page Two-l
~
q'
.t; 8102100 k 3
e,
-.~.
E('
b
~
i:
Mr. E.trold R. Denton Page Two e
cc: Messrs. V.C. Summer G.H. Fischer T.C. Nichols, Jr.
E.H. Crews,'Jr.
O.W. Dixon, Jr.
W.A. Williams, Jr.
O.S.'Bradham D.A. Nauman R.B. Clary
-A.R.
Koon A.A. Smith J.B. Knotts, Jr.
J.L. Skolds l
B.A. Bursey NPCF/Whitaker File J
i s
a i
4 I.
l 4
i-i f
4 1,
l g
g 83-9 ge-
'(+--er-viy
'r-W w 'g gr='=ug.
,9ev.=
-+w4--y 7ge4 g-1
-4 +-w/ Sp
-9
.'iWa*
g-p g-ge m
g g
yy y Mf4-er-Fr + - r Tys
+
t-
'tY
e
-