.O APPENDIX A NOTICE OF VIOLATION Georgia Power Company License Nos. DPR-57 Hatch

& NPF-5 Based on the NRC inspection September 16-19, 1980, certain of your activities were apparently not conducted in full compliance with NRC requirements as indi-cated below.

These items have been categorized as described in correspondence to you dated December 31, 1974.

A.

As required by Technical Specification Section 6.5.2.8.i, an independent fire protection and loss prevention inspection and audit shall be performed annually utilizing either qualified offsite licensee personnel or an outside fire protection firm.

Contrary to the above, an independent fire protection and loss prevention inspection and audit has not been performed since August 15, 1979.

This is an infraction.

B.

As required by Technical Specification Section 3.13.6, all penetration fire barriers protecting safety related areas shall be functional at all times.

Contrary to the above, the fire door between the Unit 1 Radwaste Building and the Ucit 1 East Cableway was blocked in the open position on September 17, 1980, by hs se to welding cylinders and the rolling fire door for diesel gen-erator Room 1A was obstructed from closing on September 19, 1980 due to equipment stoced in the door opening. A fire watch or equivalent monitoring were not provictd for these nonfunctional fire barrier penetrations.

This is an infrac' ion and applies only to Unit 1.