From: Fitzpatrick E
GENERAL PUBLIC UTILITIES CORP.
To:
NRC OFFICE OF INFORMATION RESOURCES MANAGEMENT (IRM)
Shared Package
ML19354E845 List:
References
NUDOCS 9002020030
Download: ML19354E844 (2)


Text

_ _.

. t i

OPU Nuoleer Corporation f Nuclear  :===388 Forked River,New Jersey 08731-0388 j

5 609 971 4000 i Writer'sDirect Dial Number:

l January 19,'1990 l

5 Document Control Desk  !

U.S. Nuclear Regulatory Commission  ;

Washington, D.C. 20555 +

f centlemen  !

i Subjects Oyster Creek Nuclear Generating Station (OCNGS) _;

Docket No. 50-219 Technical Specification change Request (TSCR) No. 179 i GPUN submitted Technical Specification Change Request-(TSCR) No. 179 by letter dated  ;

June 30, 1989 to add limiting conditions of operation and surveillance requirements j for the high range radioactive noble gas effluent monitors. Along with this TSCR, a minor adminirtrative change was made to the legend and footnotes for Table 4.13-1.

At the request of the NRC Project Manager, CPUN has revised and is resubmitting the [

appropriate pages of TSCR No. 179 to identify this minor change.

GPUN has determined that the above change is a purely administrative change as  :

described in the Federal Register (48 FR 14869,Section I.c.2.e(i)) and therefore'is  !

not considered to involve a significant hasard as described in 10CFR50.92. l l

If there are any questions regarding this matter, please call Michael Heller, I Licensing Engineer at (609)971-4680. l Very truly yours, 9002020030 900119 ]

FDR ADOCK 0500 g9 E. E. Fitspatrick j P Vice President & Director oyster Creek EEF/MHzjc l TSCR0773A(16) cc: Mr. William T. Russell, Administrator Mayor Debra Madensky q Region I 818 West Lacey Road j U.S. Nuclear Regulatory Commission Forked River, NJ 08731 j 475 Allendale Road -]

King of Prussia, PA 19406 'Mr. Kent Tosch j NJ Bureau of Nuclear Engineering i NRC Resident Inspector Dept. of Environmental Protection j Oyster Creek Nuclear Generating Station CN 415 -1 Trenton, NJ 08625 l Mr.'Alex Dromerick U.S. Nuclear Regulatory Commission Washington, D.C. 20555 O[lW l I1 .l l , GPU Nuclear Corporation as a subsidiary of the General Pubhc Utihties Corporation j

'i i

1 OYSTER CREEK NUCLEAR GENERATING STATION  :

PROVISIONAL OPERATING LICENSE NO. DPR-16  !

DOCKET NO. 50-219 TECHNICAL SPECIFICATION CHANGE REQUEST NO. 179 l

)

i Applicant hereby requests the Commission to change Appendix A to the above captioned license as indicated below. pursuant to 10CFR50.91, an analysis  ;

concerning the determination of no significant hazards considerations is also 1 presented: i

1. Sections to be chanced 3.13, 3.15, 4.13, 4.15, and 6.9.3.
2. Extent of Chance  ;

Add specifications for the high range radioactive noble gas effluent monitors which are installed to comply with NUREG 0737, Item II.F.1.1, and l clarify that existing Technical Specifications address low range radioactive noble gas effluent monitors. In addition, reformat the legend l for Table 4.13-1 for better readability and delete the footnote for Table 4.13-1 which states "This surveillance will commence at the first cold shutdown after July 1, 1985".

3. Chances Recuested As indicated in the attached revised Technical Specification pages 3.13-3, 3.13-4, 4.13-1, 6-18, and Tableb 3.13.1, 3.15.2, 4.13.1 and 4.15.2.
4. Discussion NUREG 0737, Item II.F.1.1 requires the capability to detect and measure l concentrations of noble gas fission products in plant gaseous effluents during and following an accident. Monitors must be provided for every potential accident release path and must be capable of monitoring the full range of effluents from normal "As low as is Reasonably Achievable"

( ALARA) concentrations to the maximum concentrations expected during a design baris accident.

Two Radioactive Gaseous Effluent Monitoring Systems.(RAGEMS) are installed at Oyster Creek to perform this function; one to monitor releases at the main stack (RAGEMS I) and one to monitor the turbine building vents (RAGEMS II). RAGEMS I has two low range monitors and one high range monitor. RAGEMS II has one low range monitor and one high range monitor.

l GPUN is proposing to add limiting conditions of operation (LCOs) and surveillance requirements for the high range monitors. The existing ,

Technical Specifications (TSs) for Oyster Creek contain LCOs and [

surveillance requirements for the low range monitors. TSs for the low range monitors were incorporated as part of the Radiological Effluent Technical Specifications (RETS) to ensure compliance with the ALARA guidelines in 10CFR50, Appendix 1. ,

i