APPENDIX A NOTICE OF VIOL!. TION

-.=

Tennessee Valley Authority License No. DPR-33 Browns Ferry Nuclear Plant Based on the NRC inspection June I to June 30, 1980, certain of your activities were apparently not conducted in full compliance with NRC requirements as indi-cated below. These items have been categorized as described in correspondence to you dated December 31, 1974.

As required by 10 CFR 50 Appendix B and implemented by Tennessee Valley Authority Nuclear - Operational Quality Assurance Manual Section 2.1 Part II, upon completion of maintenance on any item of the CSSC list and before release for service, appropriate testing shall be performed to verify operatior.a1 acceptability.

Contrary to the above, on June 23, 1980, the control valve #2 pressure sensor, which sends a signal to the Reactor Protection System to indicate turbine control valve fast closure, had maintenance performed on it and was returned to service without testing of the Reactor Protection System to verify proper operation of the repaired pressure switch.

This is an infraction and applicable to Unit 1.