APPENDIX A NOTICE OF VIOLATION Florida Power Corporation Docket No. 50-302 Crystal River 3 License No. OPR-72 As a result of the inspection conducted on February 10, 1981, and in accordance with the Interim Enforcement Policy, 45 FR 63754 (October 7,1980), the following violation was identified.

10 CFR 71.5(b) requires that "the licensee comply with the applicable

~

requirements of.. 49 CFR Parts 170 - 189." 49 CFR 173.393(j)(3) requires that radiation levels shall not exceed ten millirem per hour at any point two meters (six feet) from the vertical planes projected. by the outer lateral surface of the car or vehicle.

Contrary to the above, on February 10, 1981, one shipment of radioactive waste (AS 24614) was delivered to the Chem-Nuclear Services, Inc., Barnwell,

'~

~

South Carolina burial site with radiation levels of 16 mR/hr at two meters from the vertical plane projected by the outer lateral surfaces of the vehicle.

This is a Severity Level III Violation (Supplement V.C.2).

Pursuant to the provisions of 10 CFR 2,.201, you 'are het eby required to submit to this. office within twenty-five days of the date of this NoLice, a written statement or explanation in reply, including:

(1) admission or denial of the alleged violation; (2) the reasons for the violation if admitted;' (3) the corrective steps which have been taken and the results achie'ved; (4) corrective t

steps which will be taken to avoid further violations; and (5) the date when full compliance will be achieved. Under the authority of Section 182 of the Atomic Energy Act of 1954, as amended, this response shall be submitted under oath or affirmation.

Date:

8106230 N

-. -