/03L-0:on 801025,temp Indicator TI-2412B Associated W/Loop a Failed Low.Caused by Leads from Recorder Connected Upstream of Isolation Amplifier.Procedure Changed to Connect Recorder Leads to Isolated Points of Circuit
ML19343A961
Person / Time
Site: North Anna 
Issue date: 11/19/1980
From: Cartwright W
VIRGINIA POWER (VIRGINIA ELECTRIC & POWER CO.)
To:
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION II)
Shared Package
ML19343A958 List:
References
LER-80-080-03L-01, LER-80-80-3L-1, NUDOCS 8011240352
Download: ML19343A961 (2)


LER-1980-080, /03L-0:on 801025,temp Indicator TI-2412B Associated W/Loop a Failed Low.Caused by Leads from Recorder Connected Upstream of Isolation Amplifier.Procedure Changed to Connect Recorder Leads to Isolated Points of Circuit
Event date:
Report date:
3391980080R03 - NRC Website

text

..

[ ')

U.S. NUCT'" 'EGULATORY COMMISSION

\\

LICENSEE EVENT REPORT CONTROL BLOCK / / / / / / / (1)

(PLEASE PRINT OR TYPE ALL REQUIRED INFORMATION)

/0/1/

/V/A/N/A/S/2/ (2)

/0/0/-/0/0/0/0/0/-/0/0/ (3)

/4/1/1/1/1 (4)

/ / / (5)

LICENSEE CODE LICENSE NUMBER LICENSE TYPE CAT

///

P [L/ (6)

/0/5/0/0/0/3/3/9/

(7)

/1/0/2/5/8/0/

(8) /3/3/1/9/a/o/ (9)

UR DOCKET NUMBER EVENT DATE REPORT DATE EVENT DESCRIPTION AND PROBABLE CONSEQUENCES (10)

/0/2/

/

On October 25, 1980 while operating in Mode 1 at 100% power, the temperature

/

/0/3/

/

indicator (TI-2412B) associated w.th the overpower AT setpoint for Loop A

/

/0/4/

/

failed low.

Since the affected channel was placed in the trip condition within/

/0/5/

/

one hour, as required by T.S. 3.3.1.1, the health and safety of the public

/

/0/6/

/

were not affected. The event is reportable pursuant to T.S. 6.9.1.9.c.

/

/0/7/

/

/

/0/8/

/

/

SYSTEM

CAUSE

CAUSE COMP.

VALVE CODE CODE SUBCODE COMPONENT CODE SUBCODE SUBCODE

/0/9/

/I/A/ (11) /D/ (12) /Z/ (13) /I/N/S/T/R/U/ (14)

/I/ (15)

/Z/ (16)

SEQUENTIAL OCCURRENCE REPORT REVISION LER/R0 EVENT YEAR REPORT NO.

CODE TYPE NO.

(17) REPORT NUMBER

/8/0/

/-/ /0/8/0/

/\\/

/0/3/

/L/

[-/

[0/

ACTION FUTURE EFFECT SHUTDOWN ATTACHMENT NPRD-4 PRIME COMP.

COMP 0hTNT TAKEN ACTION ON PLANT METHOD HOURS SUBMITTED FORM SUB. SUPPLIER MANUFACTLHER [G/ (18) /Z/ (19) /Z/ (20) [Z/ (21) /0/0/0/0/ (22) [Y/ (23) [N/ (24) [N/ (25) /W/1/2/0/ (26)

CAUSE DESCRIPTION AND CORRECTIVE ACTIONS (27)

/1/0/

/

The temperature indicator failed low when leads from a recorder were connected /

/1/1/

/

upstream of an isolation amplifier. The recorder was usc 1 to monitor the

/

/1/2/

/

overpower AT setpoint during a load swing test.

The corrective action was to /

/1/3/

/

change the procedure so as to connect the recorder leads to isolated points of /

/1/4/

/

of the appropriate circuit.

/

FACILITY METHOD OF STATUS

% POWER OTHER STATUS DISCOVERY DISCOVERY DESCRIPTION (32)

/(

[A/ (31)

/ OPERATOR OBSERVATION /

'1/5/

[B/ (28)

/1/0/0/ (29) /

NA ACTIVITY CONTENT RELEASED OF RELEASE AMOUNT OF ACTIVITY (35)

LOCATION OF RELEASE (36)

/1/6/

/Z/ (33)

/Z/ (34) /

NA

/

/

NA

/

PERSONNEL EXPOSURES NUMBER TYPE DESCRIPTION (39)

/1/7/ /0/0/0/ (37) [Z[ (38) /

NA

/

PERSONNEL INJURIES NUMBER DESCRIPTION (41)

/1/8/ /0/0/0/ (40) /

NA

/

LOSS OF OR DAMAGE TO FACILITY ( )

TYPE

DESCRIPTION

/1/9/

LZ/ (42) /

NA

/

PUBLICITY ISSUED DESCRIPTION (45)

NRC USE ONLY

/2/0/

/NL (44) /

NA

/////////////

NAML OF PREPARER W. R. CARTWRIGHT PHONE (703) E94-5151

@h

4%

i

. Virginia Electric and Power Company North Anna Power Station, Unit #2 Attachment: Page 1 of I Docket'No. 50-339 Report No. LER 80-080/03L-0

Description of Event

On October 25, 1980 while operating in Mode I at-100% power, the temperature indicator (TI-2412B) associated with the overpower AT setpoint for Loop A failed low.

The applicable Technical Specification is 3.3.1.1,

- and the event is reportable pursuant to T.S. 6.9.1.9.c.

Probable Consequences of Occurrence Since the affected channel was placed in the trip condition within one hour, as required by T.S. 3.3.1.1, the health and safety of the public were not affected.

1

Cause of Event

The temperature setpoint failed low when leads from a recorder were connected to unisolated points of the circuit. The corrective action was to change the procedure of the load swing test so that the recorder i

leads are connected to isolated points of the circuit.

Immediate Corrective Action

The immediate action was to place the overpower AT channel in the trip condition. The channel was checked to verify it was not affected by the recorder leads.

Scheduled Corrective Action

~There are no scheduled corrective actions.

Actions Taken to Prevent Recurrence A change was made in the procedure of the load swing test such that leads from the. recorder are connected ~at isolated points of the appropriate circuits.

Generic Implications 4

There are no generic implications.