ML19340E090
| ML19340E090 | |
| Person / Time | |
|---|---|
| Site: | Bailly |
| Issue date: | 11/10/1980 |
| From: | James Keppler NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION III) |
| To: | Shorb E NORTHERN INDIANA PUBLIC SERVICE CO. |
| References | |
| NUDOCS 8101060362 | |
| Download: ML19340E090 (2) | |
Text
.
bil Kf C
<f
'o UNITED STATES 8 "., s.,
1 NUCLEAR REGULATORY COMMISSION E
REGION 111
[
799 ROOSEVELT ROAD o
% '...
- e" GLEN ELLYN. l' LiNolS 60137 November 10, 1980 Those on Attached Address Listing:
This IE Information Notice No. 80-41 is provided as an early notification of a possibly significant matter.
It is expected that recipients will review the information for possible applicability to their facilities. No specific action or response is requested at this time.
If further NRC evaluations so indicate, an IE Circular or Bulletin will be issued to recommend or request specific licensee actions.
If you have questions regarding this matter, please contact the this office.
Sincerelv, N'
Y James G. Keppler /
Director
Enclosure:
IE Information Notice No. 80-41 cc w/ encl:
Mr. D. W. Kane, Sargent & Lundy Mr. Gary N. Wright, Chief Division of Nuclear Safety 4
Reproduction Unit NRC 20b 8101000 M b Q
RIIT's CORPORATE ADDRESSES FOR OPERATING LICENSEES AND CONSTRUCTION PERMIT HOLDERS (BWR's and PUR's)
Docket No. 50-331 Iowa Electric Light and Power Company ATTN:
Mr. Duane Arnold s
President 23 IE Towers P. O. Box 351 53 Cedar Rapids, IA 52406
- b'
- . R cc w/ enc 1
- {}
D. Miteck, Chief c_ a Engineer ca
~$i Central Files O
S ra Director, NRR/DPM Director, NRR/ DOR AE0D Resident Inspector, RIII PDR Local PDR NSIC TIC Docket No. 50-367 Northern Indiana Public Service Company ATTN:
Mr. Eugene M. Shorb Senior Vice President 5265 Hohman Avenue Hammond, IN 46325 cc w/ enc 1:
Central Files Director, NRR/DPM Director, NRR/ DOR PDR Local PDR W
Mr. Dean Hansell, Offite of
)
Assistant Attorney General i
SSINS No.:
6835 1
Accession No.:
8008220260 UNITED STATES IN 80-41 NUCLEAR REGULATORY COMMISSION OFFICE OF INSPECTION AND ENFORCEMENT WASHINGTON, D.C.
20555 November 10, 1980 IE Information Notice No. 80-41:
FAILURE OF SWING CHECK VALVE IN THE DECAY HEAT REMOVAL SYSTEM AT DAVIS-BESSE UNIT N0. 1 Description of Circumstances:
On October 9, 1980 the resident inspector at the Davis-Besse facility was informed that the licensee had performed leak rate tests and identified exces-sive leakage through Decay Heat Removal System check valve CF-30.
Valve CF-30 is the inboard one of two in-series check valves that is used to isolate the reactor coolant system from the low pressure decay heat removal system.
On further investigation the licensee found that the valve disc and arm had separated from the valve body and was lodged just under the valve cover plate.
The two 2 5/8 x 5/8 inch bolts and locking mechanism for the bolts that holas the arm to the valve body were missing and have not been located.
The CF-30 valve is a 14-inch swing check valve manufactured by Velan Valve Corporation.
The cause of the failure has not been identified.
l The test that was in progress when the failure was identified was being con-ducted in response to a letter from Darrell G. Eisenhut, Office of Nuclear Reactor Regulations to all Light Water Reactor Licensees, LWR Primary Coolant System Pressure Isolation Valves, February 23, 1980.
This IE Information Notice is provided as an early notification of a possibly
(
significant matter that is still under review by the NRC staff.
It is expected that recipients will review the information for possible applicability to their facilities.
No specific action or response is requested at this time.
If NRC evaluations so indicate, further licensee actions may be requested or required.
No written response to this IE Information Notice is required.