O INDEX LIMITING CONDITIONS FOR OPERATION AND SURVEILLANCE REQUIREMENTS SECTION Page 3/4.7.2 STEAM GENERATOR PRESSURE / TEMPERATURE LIMITATION.......
3/4 7-12 3/4*.7.3 COMPONENT COOLING WATER SYSTEM.......................
3/4 7-13 3/4.7.4 SERVICE WATER SYSTEM.................................
3/4 7-15 3/4.7.5 ULTIMATE HEAT SINK...................................
3/4 7-17 3/4.7.6 CONTROL ROOM EMERGENCY VENTILATION SYSTEM............
3/4 7-18 3/4.7.7 SEALED SOURCE CONTAMINATION..........................
3/7 7-21 3/4.7.8 FIRE SUPPRESSION SYSTEMS Fi re Suppressi on Water System........................ 3/4 7-23 S p r i nk l e r Sy s tems.................................... 3/4 7-27 Fi re Ho s e S ta ti on s................................... 3/4 7-29 3/4.7.9 PENETRATION FIRE BARRIERS............................
3/4 7-31 3/4.7.10 HYDRAULIC SNUBBERS...................................
3/4 7-32 3/4.7.11 CONTROL BUILDING MODIFICATION CONNECTION BOLTS.......
3/4 7-37 3/4.8 ELECTRICAL POWER SYSTEMS 3/4.8.1 A.C. SOURCES 0 p e ra ti n g............................................ 3/4 8-1 Shutdown.............................................
3/4 8-5 3/4.8.2 ONSITE POWER DISTRIBUTION SYSTEMS A.C. Di stribution - Operating........................ 3/4 8-6 A.C. Di stribu tion - Shutdown......................... 3/4 8-7 0.C. Di stribution - Operating........................ 3/4 8-8 D.C. Di stribu ti on - Shutdown......................... 3/4 8-10 3/4.8.3 UNDERVOLTAGE PROTECTION 4.16 kV Emergency Bus Undervoltage Protection........ 3/4 8-11 TROJAN-UNIT 1 yII co\\\\ toit;L
ELECTRICAL POWER SYSTEM f
3/4.8.3 UNDERVOLTAGE PROTECTION 4.16 kV EMERGENCY BUS UNDERVOLTAGE PROTECTION LIMITING CONDITION FOR OPERATION 3.8.3.1 The 4.16 kV Emergency Bus Undervoltage Protection instrumen-tation shown in Table 3.8-1 shall be OPERABLE with their trip set-points set consistent with the values shown in the Trip Setpoint col-umn of Table 3.8-2.
i APPLICABILITY: As shown in Table 3.8-1.
ACTION:
4 With a 4.16 kV Emergency Bus Undervoltage Protection instru-a.
mentation channel trip setpoint exceeding the value shown in Table 3.8-2, declare the channel inoperable and apply the applicable ACTION requirement of Table 3.8-1 until the channel is restored to OPERABLE status with the trip setpoint adjusted consistent with the Trip Setpoint value.
b.
With a 4.16 kV Emergency Bus Undervoltage Protection instrumen-tation channel inoperable, take the ACTION shown in Table 3.8-1.
SURVEILLANCE REQUIREMENTS 4.8.3.1 Each 4.16 kV Emergency Bus Undervoltage Protection instrumen-tation chan el shall be demonstrated OPERABLE by the performance of the CHANNEL CALIBRATION and CHANNEL FUNCTIONAL TEST operations during the modes and at the frequencies shown in Table 4.8-1.
f l '
l TROJAN-UNIT I 3/4 8-11
r
- l TABLE 3.8-1 4.16 kV EMERGENCY BUS UNDERVOLTAGE PROTECTION INSTRUMENTATION g
MINIMUM g
TOTAL NO.
CHANNELS CHANNELS APPLICABLE 3
FUNCTIONAL UNIT OF CHANNELS TO TRIP OPERABLE MODES ACTION
?
E a.
4.16 kV Emergency Bus Q
Undervoltage (Loss of
. Voltage) 4/ Bus 2/ Bus 3/ Bus 1, 2, 3*
1 l
b.
~
4.16 kV Emergency Bus Undervoltage (Degraded Voltage) 4/ Bus 2/ Bus 3/ Bus 1, 2.-3*
1 r
i s"
[
T i
C c
1 f
1
l e.
i e
TABLE 3.8-1 (Continued)
TABLE NOTATION
ACTION STATEMENTS ACTION 1 - With the nt.mber of OPERABLE channels one less than the Total Number of Channels, operation may proceed provided both of the following conditions are satisfied:
j a.
The inoperable channel is placed in the tripped j
condition within one hour.
i b.
The Minimum Channels OPERABLE requirement is met; however, one additional channel may be bypassed for up to 2 hours2.314815e-5 days <br />5.555556e-4 hours <br />3.306878e-6 weeks <br />7.61e-7 months <br /> for surveillance testing per Specification 4.8.3
}
i-I L
TROJAN-UNIT 1 3/4 8-13 l
i m.
_,.,_,..y.
?
TABLE 3.8-2 4.16 kV EMERGENCY Pi!S UNDERVOLTAGE PROTECTION INSTRUMENTATION TRIP SETPOINTS 51 -
8 FUNCTIONAL UNIT TRIP SETPOINT ALLOWABLE VALUES g
E a.
4.16 kV Emergency Bus 2560 volts with a 2560 1 210 volts with a
-a Undervoltage (Loss of 1.1 second time delay 1.1 1 0.1 second time delay Voltage) b.
4.16 kV Emergency Bus 3850 volts with a 3850 + 80 volts with a Undervoltage (Degraded 55 second time delay 55 i T second time delay Voltage) a f
1
_ _ =.
t t
4 TABLE 4.8-1 4.16 kV EMERGENCY BUS UNDERVOLTAGE PROTECTION INSTRUMENTATION g
SURVEILLANCE REQUIREMENTS o
S CHANNEL MODES IN WHICH f
CHANNEL FUNCTIONAL SURVEILLANCE E
FUNCTIONAL UNIT CALIBRATION TEST REQUIRED a.
4.16 kV Emergency Bus R
M 1,2,3 Undervoltage (Loss of Voltage) b.
4.16 kV Emergency Bus R
M 1,2,3 Undervoltage (Degraded Voltage)
L; 4
9 e
e
.