ML19339C243

From kanterella
Jump to navigation Jump to search
Forwards IE Info Notice 80-39, Malfunction of Solenoid Valves Mfg by Valcor Engineering Corp. No Written Response Is Required
ML19339C243
Person / Time
Site: Beaver Valley
Issue date: 10/31/1980
From: Grier B
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION I)
To: Woolever E
DUQUESNE LIGHT CO.
References
NUDOCS 8011170893
Download: ML19339C243 (1)


Text

GAJpo f[.....,Jt,,

UNITED STATES

//

y cgg NUCLEAR REGULATORY COMMISSION l

REGION I 631 PARK AVENUE

' +, '

g MING,OF PRUSSIA, PENNSYLVANIA 19406 October 31, 1980 4

Doc'ket No. 50-412 j

Duquesne Light Company

~

~

v.: -

ATTN:

Mr. E. J. Woolever E.

Vice President fi 435 Sixth Avenue M

~ ~ O, Pittsburgh, Pennsylvania 15219 E

y 35 Gentlemen:

The enclosed IE Informa. on Notice No. 80-39, " Malfunctions of Solenoid Valves Manufactured by Valcor dngineering Corporation," is forwarded to you for infomation.

No written response is required.

If you desire additional information regarding this matter, please contact this office.

Sincerely, Bo e H. Grier Director

Enclosures:

1.

IE Information Notice No. 80-39 2.

List of Recently Issued IE Information Notices CONTACT:

D. L. Caphton (21S-337-5265) cc w/encis:

R. J. Washabaugh, Quality Assurance Manager 80 11 y esti

[f3 i

SSINS No.:

6835 Accessien N2.:

8008220245 IN 80-39 UNITED STATES NUCLEAR REGULATORY COMMISSION OFFICE OF INSPECTION AND ENFORCEMt.NT

~

WASHINGTON, D. C. 20555 Octcher 31, 1980 IE INFORMATION N3TICE NO. 80-39: MALFUNCTION OF SOLENOID VALVES MANUFACTURED BY VALCOR ENGINEERING CORPORATION PURPOSE:

The intent of this Information Notice is to alert holders of construction permits and operating licenses for nuclear power plants of a potentially generic problem involving the malfunctioning of certain solenoid valves manu-factured by the Valcor Engineering Corporation (Valcor).

The solenoid valves so involved are designated as Valcor Valve Model No. V52600-554-1.

Valcor has informed us that these valves have only been supplied to the McGuire facility; however, since these valves were substituted for solenoid valves of another manufacturer that did not meet the requirements of IE Bulletin.No. 79-01 and its amendments, licensees and holders of construction permits should take into account the problem identified in this Information Notice prior tc making any sinflar substitution.

BACKGECUND:

By TWX dated June 27, 1980, Valcor submitted a preliminary 10 CFR Part 21 Report addressin0 the malfunctioning of Valcor solenoid valves at the McGuire facility.

The malfunctioning valves have been identified as Valcor Valve Model No. 52600-554-1 This TWX was subsequently followed by a letter dated July 3, 1980, transmitting a more detailed Part 21 Report entitled," Quality Assurance Report", a copy of which is attached hereto as Enclosure No. 1.

In brief, the malfunction appears to be an intermittent type wherein the valve fails to cycle from OPEN to CLOSE to OPEN immediately after a sustained period of operation in the energi::ed (OPEN) mode.

Although the wives are rated for

" continuous operation", Valcor contends that the valves were not designed to meet the operating conditions requiring the immediate cycling from QPEN to CLOSE to OPEN after a sustained period of continuous energi::ation.

A major source of the problem, therefore, may be a misunderstanding of the term

' continuous operation".

By letter dated July 14, 1980 to Duke Power Company, Valcor transmitted its recommendations in this matter entitled, " Outline -

Suggested Modification Procedures", a copy of which is attached hereto as Enclosure No. 2.

Enclosures:

j DUPLICAT.3 DOCUMENT l

Entire document previously entered into system under:

ANO h cM h

[

No. of pages:

.