Text

s O'-

O TABLE 2.2-1 (Continued) e C

Q REACTOR TRIP SYSTEM INSTRUMENTATION TRIP SETPOINTS m

4 9

FUNCTIONAL UNIT TRIP SETPOINT ALLOWABLE VALUES f

13. Steam. Generator Water 2,12% of narrow range instrument 111%of narrow range instrument g

Level--Low-Low span-each steam generator span-each steam generator

[

14. Steam'/Feedwater Flow

< 40% of full steam flow at

< 42.5% of full steam flow at 5

Mismatch and Low Steam BTED THERMAL POWER coincident RATED THERMAL POWER coincid,ent H

Generator Water Level with steam generator water level with steam generator water level

> 25% of narrow range instru-

> 24% of narrow range instru-

~

ment span--each steam generator ment span--each steam gensrator

15. Undervol tage-Reactor

> 2750 voits-each bus

> 2725 volts-each bus g

Coolant Pumps tn E

16. Underfrequency-Reactor

> 57.5 Hz - each bus

> 57.4 Hz - each bus E

y Coolant Pumps 8

~

g

17. Turbine Trip A.

Auto stop oil Pressure 45 psig

+ 5 psig g

B.

Turbine Stop Valve

> 1% open

> 1% open

18. Safety Injection Input Not Applicable Not Applicable from ESF
19. Reactor Coolant Pump Not Applicable Not Applicable Breaker Position Trip i

i e