Confirms Technical Guidance Provided in 770208 Telcon Re Validity of Licensee Action to Conform W/Requirements for Electrical Cables in Vertical Raceways.Revised Cable/Conduit Installation Spec Acceptable
ML19329B147
Person / Time
Site: Davis Besse 
Issue date: 02/28/1977
From: Seyfrit K
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE)
To: Heishman R
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION III)
Shared Package
ML19329B143 List:
References
NUDOCS 8001300721
Download: ML19329B147 (2)


Text

.

~

[bl3 n-c:a-as v.

U G.

FES 281977 Docket No. 50-346 j

.c v

I MEMORANDlM FOR:

R. F. Heishman. Chief, Reactor Construction and

- r

~

~ =' Engineering Support Branch,'RIII, i

FROM:

K. V. Seyfrit. Chief, Reactor Technical Assistance Branch,IE~

j

SUBJECT:

DAVIS BESSE UNIT NO.1 - SUPPORT OF CONTROL AND

- ' INSTRUMENT CABLES ROUTED IN VERTICALLY INSTALLED

~;

f CONDUIT (AITS F30248Hl)

'~d s

j This. memorandum confi ms the technical guidance provided to D. W. Hayes l

of your office during the telecon with me on February 8,1977.

Region III through AITS F30248H1 requested headquarters assistance in the O

asta<c= ant of the validity of the action taken by this licensee to con-form to the requirements specified in Section 300-19 of the 1971 National Electric Code (NEC) regarding electrical cables installed in vertical

~

raceways. At this facility, the licensee is casuritted to use the NEC for Class IE cable design and installation.

During a special~ electrical-inspection the NRC inspector noted that instrumentation and control cables routed in vertical conduit risers did not-===maan to the~ criteria specified in Section 300-19 of the NEC.

Section 300-19 requires that "... a cable support shall be provided at -

or near the top of the vertical raceway, plus a-support'for och interval _

df spacing as. specified in Table 300-19(a)."

~

lE71censee's corrective action-was ~t6. revise their Cable / Conduit Instal-1&Uos Specification No. 7749-E-14. This document provides installation

.. procedures for conduit, raceways, cables, and cable supports in vertical

~

conduit risers. - Details of the specific changes made to Specification 7749-E-14 are presented. in the enclosed letter from the Licensee to RIII g j

. dated November 24,1976, Serial No. 160.

p #37 a

RTAB has reviewed this matter and has concluded 'that the revisions p

are appropriate and do not conflict with the intent of NEC Section

  1. J3 300-19.

Furtherinore, we believe the revised cable installation design is acceptable for support of instrumentation / control cables installed in vertical conduit as described in your memorandici and further described in the Licensee's letter dated Nobember-24,1976 to Mr. Keppler.

~

o,,,cGQNTACT:

V. D. Thomas 8.0.0..).3 0 0 7.A.I

.iu=mm.

me. gem

.e

\\

~

?. -

~.

V.

M R. F. Heishman 2 ~

FEB281977 In our opinion.- the licensee's requirement which calls for a cable restraint on either instrumentation or control cables which are over 20 feet in length in the vertical and terminated at the upper and exceeds the requirements,of Section 300-19 of the NEC.

In this application, the cable-restraint is primarily for the purpose of l

termination protection and not related to conductor tension strain.

On the basis of our review and discussions' held wit $ Bechtel. Gaithersburg on this issue, we consider the matter closed and plan no further action i

- on it unless requested.

c

~

l

~

.~

~

i

.y

' K. V. Seyfrit, Chief Reactor Technical Assistance Branch

,v Office of Inspection and Enforcement

Enclosure:

O

~

Ltr., Lowell E. Roe, TECO to James G. Kappler,.RIII, dd.

j 1

11/24/76

~

~

~

~

.,a

~

i

=

i O-

~

~ RIP:1086/F30248H1 or.c=;

RTA: RIP E...

RTA; RIP.:I l

VDThomas:sgh.. KVSeyfr.1 2/0)f77.;

2D$/77...

an.s

....;