Revise the BV-1. Technical specifications as follows:

Remove Pace Insert Pace 3/4 8-1 3/4 8-1 3/4 8-2 3/4 8-2 i

3/4 8-3 3/4 8-3 3/4 8-4 3/4 8-4 3/4 8-4a B3/4'8-2 B3/4 8-2

?

I t

891024030C 891016 hDR ADOCK 05000334 FDC i ;

t s

3/4.8 ELECTRICAL POWER SYSTEMS 3/4.8.1 A.C.

SOURCES OPERATING LIMITING CONDITION FOR OPERATION 3.C.1.1 As a minimum, the following A.C.

electrical power sources shall be OPERABLE:

a.

Two physically independent circuits betwec7 the offsite transmission net. cork and the onsite Class 1E distribution system, and l

b.

Two separato ar.d independent diesel generators each with:

l 1.

Separate day and engine-mounted fuel tanks containing-a minimum of 900 gallons of fuel, 2.

A separate fuel storage system containing a minimum of 17,500 gallons of fuel, and 3.

A separate fuel transfer pump.

APPLICABILITY:

MODES 1,2,3 and 4.

ACTION:

a.

With either an offsite circuit or diesel generator (1) of l

the above required A.C.

electrical power sources inoperable, demonstrate the OPERABILITY of the remaining A.C.

sources by performing Surveillance Requirements 4.8.1.1.1.a and 4.8.1.1.2.a.5 within one hour and at least once per 8 hours9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br /> thereafter; restore at least two offsite circuits and two diesel generators to OPERABLE status within 72 hours8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br /> or be in COLD SHUTDOWN within the next 36 hours4.166667e-4 days <br />0.01 hours <br />5.952381e-5 weeks <br />1.3698e-5 months <br />.

b.

With one offsite circuit and one diesel generator (1) of I

the above required A.C.

electrical power sources inoperable, demonstrate the OPERABILITY of the remaining A.C.

sources by performing Surveillance Requirements 4.8.1.1.1.a and 4.8.1.1.2.a.5 within one hour and at least once per 8

hours thereafter; restore at least one of the inoperable sources to OPERABLE status within 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> or be in COLD SHUTDOWN within the next 36 hours4.166667e-4 days <br />0.01 hours <br />5.952381e-5 weeks <br />1.3698e-5 months <br />.

Restore at least two offsite circuits and two diesel generators to OPERABLE status within 72 hours8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br /> from the time of initial loss or be in COLD SHUTDOWN within the next 36 hours4.166667e-4 days <br />0.01 hours <br />5.952381e-5 weeks <br />1.3698e-5 months <br />.

BEAVER VALLEY - UNIT 1 3/4 8-1 PROPOSED

\\

i

)

r

'e ELECTRICAL POWER SYSTEMS j

ACTION (Continued) i c.

With two of the above required offsite A.C.

circuits inoperable, demonstrate the OPERA'JILITY of two diesel generators by performing Sur'.eillance Requirensnt I

4.8.1.1.2.a.5 within one hour and at least once per 8 hours9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br /> thereafter, unless the diesel generators are already 1

operating; restore at least one of the inoperable offsite sources to OPERABLE status within 24 hocrs or be in at least I

HOT-STANDBY within the next 4 hours4.62963e-5 days <br />0.00111 hours <br />6.613757e-6 weeks <br />1.522e-6 months <br />.

With only one offsite j

source

restored, restore at least two offsite circuits to OPERABLE status within 72 hours8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br /> from time of initial loss or be in COLD SHUTDOWN within the next 36 hours4.166667e-4 days <br />0.01 hours <br />5.952381e-5 weeks <br />1.3698e-5 months <br />.

d.

With two of the above required diesel generators (1) {

inoperable, demonstrate the OPERABILITY of two offsite A.C.

circuits by performing Surveillance Requirement 4.8.1.1.1.a within one hour and at least once per 8 hours9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br /> thereafter; restore at least one of the inoperable diesel generators to OPERABLE status within 2 hours2.314815e-5 days <br />5.555556e-4 hours <br />3.306878e-6 weeks <br />7.61e-7 months <br /> or be in COLD SHUTDOWN within the next 36 hours4.166667e-4 days <br />0.01 hours <br />5.952381e-5 weeks <br />1.3698e-5 months <br />.

Restore at least two diesel generators to OPERABLE status within 72 hours8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br /> from time of initial loss or be in COLD SHUTDOWN within the next'36 hours4.166667e-4 days <br />0.01 hours <br />5.952381e-5 weeks <br />1.3698e-5 months <br />.

SURVEILLANCE REQUIREMENTS 4.8.1.1.1 Two physically independent circuits between the offsite transmission network and the onsite Class 1E distribution system 4

shall be:

a.

' Determine OPERABLE at least once por 7 days by verifying correct breaker alignments, indicated power availability, and I

b.

Demonstrated OPERABIE at least once per 18 months by transferring (manually and automatically) unit power supply from the unit circuit to the system circuit.

L 4.8.1.1.2 Each diesel generator shall be demonstrited OPERABLE:

At least once per 31 days on a STACGERED TEST BASIS by:

a.

1.

Verifying the fuel level in the day and engine-mounted fuel tank, L

2.

Verifying the fuel level in the fuel storage tank, (1)

Fuel oil contained in the storage tanks not meeting the properties in accordance with 8.1.1.2.d.2 or 8.1.1.2.e shall be brought within the specified limits within 7 days.

l BEAVER VALLEY - UNIT 1 3/4 8-2 l

PROPOSED

~.

1 fELECTRICAL POWER SYSTEMS SURVP.ILLANCE REQUIREMENTS (Continued) 3 3.

Deleted l

s 4.

Verifying the fuel transfer pump can be started and

' transfers fuel from the storage system to the day and engine-mounted tank, 5.

Verifying the diesel starts from ambient condition, 6.

Verifying the generator is synchronized, loaded to 21425 kw, and operates for 2 60 minutec, and 7.

Verifying the diesel generator is aligned to provide standby power to the associated emergency busses.

b.

At least once per 18 months during shutdown by:

c 1.

Subjecting the diesel to an inspection in accordance I

with procedures prepared in conjunction with its manufacturer's recommendations for this class of standby service, i

2.

Verifying the generator capability to reject a load of 2450 kw without tripping, 3.

Simulating a loss of offsite power in conjunction with a safety injection signal, and:

a)

Verifying de-energization of the emergency busses l

and load shedding from the emergency busses.

b)

Verifying the diesel starts from ambient condition on the auto-start signal, energizes the emergency 1

busses with permanently connected loads, energizes j

the auto-connected emergency loads through the load sequencer and operatea for 2 5 minutes while

(

L its generator is loaded with the emergency loads.

4.

Verifying that on a

loss of power to the emergency

busses, all diesel generator
trips, except engine overspeed, generator differential and overcurrent, are autcmatically disabled.

BEAVER VALIEY - UNIT 1 3/4 8-3 PROPOSED

Q

~'

p, de r

i:

is l

li 7

ELECTRICAL POWER SYSTEMS SURVEILLANCE REQUIREMENTS '(Continued) r 5.

Verifying the diesel generator operates for 2

60 minutes while loaded to 2 2750 kw.

6.

Verifying that the auto-connected loads to each diesel generator do not exceed the 2000 hour0.0231 days <br />0.556 hours <br />0.00331 weeks <br />7.61e-4 months <br /> rating of 2850 kw.

7.

Verifying thet the automatic load sequence timer is OPERABLE with each load sequenco time within 1 10% of its required value.

c.

Check forLand remove accumulated water:

1.

From the day tank, at least once per 31 days and after

[

each operation of the diesel where the period of operation was greater than 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br />, and 2.

From the fuel oil storage tank, at least once per 92 days.

e d.

By sampling (1) new fuel oil in accordance with ASTM D4057-81 prior.to addition to the storage tanks and:

L i

1.

By verifying in accordance with the tests specified in ASTM D975-81 prior 'to addition to the storage tanks that the sample has:

i a)

An API Gravity of within 0.3 degroes~at 60'F or a l

specific gravity of within 0.0016 at 60/60*F, when l

compared to the supplier's certificate or an L

absolute specific gravity at 60/60*F of greater than or equal to 0.83 but less than or equal to o

0.89 or an API gravity at 60'F of greater than or equal to 27 degrees but less than or equal to 39

degrees, b)

A kinematic viscosity at 40*C of greater than or equal to 1.9 centistokes, but loss than or equal to 4.1 centistokes, if gravity was not determined by comparison with the supplier's certification, r

c)

A flash point equal to or greater than 125'F, and d)

A clear and

'right appearance with proper color when tested in accordance with ASTM D4176-82.

BEAVER VALLEY - UNIT 1 3/4 3-4 i

PROPOSED

F r

' bLE'C5HICAL POWER SYSTEMS SURVEILLANCE REQUIREMENTS (Continued) 2)

By verifying within 31 days of obtaining the sample that the other properties specified in Table 1 of ASTM D975-81 are met when tested in accordance with ASTM D975-81 except that the analysis for sulfur may be

~i performed in accordance with ASTM D1552-79 or ASTM.

D2622-82.

+

e)

At least once every 31 days by obtaining a sample of fuel oil from the storage tanks and day tanks in accordance with ASTM D2276-78, and verifying that total particulate contamination is less than 10 mg/ liter when checked in accordance with ASTM D2276-78, Method A.

BEAVER VALLEY - UNIT 1 3/4 8-4a l

PROPOSED

o ELECTRIC POWER SYSTEMS BASES A.C.

SOURCES.

D.C.

SOURCES AND ONSITE POWER DISTRIBUTION SYSTEMS (Continued)

Operation with a

battery cell's parameter outside the normal limit but within the allowable value specified in Table 3.8-1 is permitted for up to 7

days.

during this 7 day period:

(1) the allowable values for electrolyte level ensures no physical damage

~ lates with an adequate electron transfer capability; (2) to the p

the allowable value for the average specific gravity of all the

cells, not more than.020 below the manufacturer's recommended full charge specific
gravity, ensures that the decrease in rating will be less than the safety margin provided in sizing; (3) the L

allowable value for an individual cell's specific gravity, ensures

~

that an individual cell's specific gravity will not be more than t

.040 below the manufacturer's full charge specific gravity and that the overall capability of the battery will be mainte!.ned within an acceptable limit; and (4) the allowable value for an individual l

cell's float

voltage, greater than 2.07
volts, ensures the l

battery's capability to perform its design function.

I Note (1) provides clarification of specification 3.8.1.1 action requirements when the diesel generators are inoperable as a result of surveillance requirements 4.2.1.1.2.d.2 and 4.8.1.1.2.e l

in accordance with Regulatory Guide 1.137 Revision 1 Regulatory Position C.2.a.

BEAVER VALLEY - UNIT 1 B3/4 8-2 PROPOSED

f-

~

K

  • .n 37 6,(

ATTACHME'NT A-2 h';.

Revise the BV-2 Technical Specifications as follows:

Remove Paces Insert Paces s

3/4 8-1 3/4 8-1 i

3/4 8-2 3/4 8-2 3/4 6-3 3/4 8-3 3/4 8-4 3/4 8-4 3/4 8-5 3/4 8-5 B3/4 8-2 B3/4 8-2 1

h r

b l

l i

s 1 ?

(

I:

1 L

7

3/h.8ELECTRICALPOWERSYSTEMS 1

3/4.8.1 A.C.' SOURCES OPERATING, LIMITING CONDITION FOR OPERATION 3.8.1.1 As a minimum, the following A.C. electrical power sources shall be OPERABLE:

Two physically independent circuits between the offsite transmission a.

network and the onsite Class IE distribution system, and b.

Two separate and independent diesel generators each with:

1.

Separate day tank containing a minimum of 350 gallons of fuel,.

2.

A separate fuel storage system containing a minimum of 53,225 gallons of fuel, 3.

A separate fuel transfer punip, 4.

Lubricating oil storage containing a minimum total volume of 504 gallons of lubricating oil, and 5.

Capability to transfer lubricating oil from storage to the diesel generator unit.

APPLICABILITY: MODES 1, 2, 3 and 4.

ACTION:

With either an offsite circuit or diesel generatohof the above re-I a.

quired A.C. electric'al power sources inoperable, demonstrate the OPERABILITY of the remaining A.C. sources by perfoming Surveillance Requirements 4.8.1.1.1.a and 4.8.1.1.2.a.5 within one hour and at least once per 8 hours9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br /> thereafter; restore at least two offsite cir-cuits and two diesel generators to OPERABLE status within 72 hours8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br /> or m

be in COLD SHUTDOWN within the next 36 hours4.166667e-4 days <br />0.01 hours <br />5.952381e-5 weeks <br />1.3698e-5 months <br />.

Withoneoffsitecircuitandonedieselgeneratuhoftheabovere-b.

l quired A.C. electrical power sources inoperable, demonstrate the OPERABILITY of the remaining A.C. sources by performing Surveillance Requirements 4.8.1.1.1.a and 4.8.1.1.2.a.5 within one hour and at least once per 8 hours9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br /> thereafter; restore at least one of the in-operable sources to OPERABLE status within 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> or be in COLD SHUTDOWN within the next 36 hours4.166667e-4 days <br />0.01 hours <br />5.952381e-5 weeks <br />1.3698e-5 months <br />.

Restore at least two offsite circuits and two diesel generators to OPERABLE status within 72 hours8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br /> from the time of initial loss or be in COLD SHUTDOWN within the next 36 hours4.166667e-4 days <br />0.01 hours <br />5.952381e-5 weeks <br />1.3698e-5 months <br />.

BEAVER VALLEY - UNIT 2 3/4 8-1 f0SW 0

ELECTRICAL POWER SYSTEMS i

1 l

LIMITING CONDITION FOR OPERATION (Continued)

O' With two of the above required offsite A.C. circuits inoperable,-

c.

-demonstrate the OPERABILITY of two diesel generators by performing Surveillance Requirements 4.8.1.1.2.a.5 within one hour and at least once per 8 hours9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br /> thereafter, unless the diesel generators are already operating; restore at least one of the inoperable offsite sources to OPERABLE status within 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> or be in at least HOT STAND 8Y within the next 4 hours4.62963e-5 days <br />0.00111 hours <br />6.613757e-6 weeks <br />1.522e-6 months <br />. With only one offsite source restored, restore at least twc offsite circuits to OPERABLE status within 72 hours8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br /> from time of initial loss or be in COLD SHUTDOWN within the next 36 hours4.166667e-4 days <br />0.01 hours <br />5.952381e-5 weeks <br />1.3698e-5 months <br />.

Withtwo-oftheaboverequireddieselgeneratorsinoperab1hdemon-l-

d.

strate the OPERABILITY of two offsite A.C. circuits by performing Surveillance Requirement 4.8.1.1.1.a within one hour and at least L

once per 8 hours9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br /> thereafter; restore at least one of the inoperable f

diesel generators to OPERABLE status within 2 hours2.314815e-5 days <br />5.555556e-4 hours <br />3.306878e-6 weeks <br />7.61e-7 months <br /> or be in COLD SHUTDOWN within the next 36 hours4.166667e-4 days <br />0.01 hours <br />5.952381e-5 weeks <br />1.3698e-5 months <br />.

Restore at least two diesel gen-erators to OPERABLE status within 72 hours8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br /> from time of initial loss or be in COLD SHUTDOWN within the next 36 hours4.166667e-4 days <br />0.01 hours <br />5.952381e-5 weeks <br />1.3698e-5 months <br />.

SURVEILLANCE REQUIREMENTS r

4.8.1.1.1.

Two physically independent circuits between the offsite trans-mission network and the onsite Class 1E distribution system shall be:

1 l

a.

Determine OPERABLE at leart once per 7 days by verifying correct breaker alignment, indicated power availability, and b.

Demonstrated OPERABLE at least once per 18 months by transferring (manually and autorratically) unit power supply from the unit circuit to the system circuit.

4.8.1.1.2 Each diesel generator shall be demonstrated OPERABLE:

At least once per 33 days on a STAGGERED TEST BASIS by:

a.

1.

Verifying the fuel level in the day tank, 2.

Verifying the fuel level in the fuel storage tank, (I) Fuel oil cohded i., de sk e h /cs not ~ee h de y

y p

er tie s is a c c or/a -e e a d '/l T. /, /. 2,c/. a o r f' y, p, e s de/

y 9 4f w,$d 2% spec lhd/ I, mas waL' 7 days, l

BEAVER VALLEY - UNIT 2 3/4 8-2 llE0 f0.5 Eh

-n-

,._.-..n,-

an.

v

. ELE.CTRICAL POWER SYSTEMS i

4 a'

cSURVEILLANCE REOUIREMENTS (Con 110 ped) hl.bt'e r ; $. y i ng.....

....r.,.,.ic;cl--f u.-1 f rcm the fuel :tereg-3.

-tenk is within the accepicbh limit 3 3pecified in Tet,ie 1 cf

--A';iM 0070 hin checked for viecesity, water and sedi cat,-

4.

Verifying the fuel transfer pump can be started and transfers fuel from the storage system to the day tank, P

5.

Verifying the diesel starts from ambient condition, 6.

. Verifying the generator is synchronized, loaded to > 4,238 kw, and operates for at least 60 minutes, 7.

Verifying the diesel generator is aligned to provide standby.

power to the associated emergency busses, and 8.'

Verifying the lubricating oil inventory in storage.

i b.

At least once per 18 nonths* during shutdown by:

i 1.

Subjecting the diesel to an inspection in accordance with pro-cedures prepared in conjunction with its manufacturer's recom-mendations for this class of standby service, 2.

Verifying the generator capability to reject a load of > 825 kw without tripping, 3.

Simulating a loss of offsite power in conjunction with a safety injectionsignal,and:

a)

Verifying de-energization of the emergency busses and load shedding from the emergency busses.

b)

Verifying the diesel starts from ambient condition on the auto-start signal, energizes the emergency busses with per-manently connected loads, energizes the auto-connected emergency loads through the-load sequencer and operates for

> 5 minutes while its generator is loaded with the emertjency Toads.

4.

Verifying that on a loss of power to the emergency busses, all diesel generatop trips, except engine overspeed, backup phase

'ault detection, generator differential current, and generator overexcitation are automatically disabled.

"The specified 18-month surveillance interval during the first fuel cycle may gbe extended to coincide with completion of the first refueling outage.

This item (backup phase fault detection) is to be implemented no later than startup from the second refueling outage.

8EAVER VALLEY - UNIT 2 3/4 8-3 fhfC5 D

I h

h ELECTRICAL POWER SYSTEMS SURVEILLANCE RE0VIREMENTS (Continued) 5.

Verifying the diesel generstor c.arates for at least 60 minutes while loaded to'> 4,238 kw.

6.

Verifying that the auto-connected loads.to each diesel generator do not exceed the 2000 hour0.0231 days <br />0.556 hours <br />0.00331 weeks <br />7.61e-4 months <br /> rating of 4,535 kw.

7.

Verifying that the automatic load sequence timer is OPERABLE with each load ' sequence time within 110% of its required value, c.

Check for and remove accumulated water:

1.

From the day tank, at least once per 31 days and after each operation of the' diesel where the period of operation was, greater than 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br />, and

^

2.

From the fuel oil storage tank, at least once per 92 days.

At least once per 92 days and' from new fuel oil prior to its ad tion to the storage tanks by verifying that a sample obtained n

ccordance with ASTM D270-1975 meets the following minimum quire-4m ts and'is tested within the specified time limits:

ZMEAT l t

1.

A soon as a sample is taken (or prior to adding w fuel to the torage tank) verify in accordance with the ests specified in A5 0975-1977 that the sample has:

1 a)

A wat and sediment content of less an or equal to 0.05 h

volume rcent; i

b)

.4 kinematic scosity at 40'C o greater than or, equal to 1.9 centistoke but less tha or equal to 4.1 centistokes; L

I c)

An API Gravity of

  • hin 0 degrees of 60 F, or a specific gravity of withia 0.0 6 t 60/60'F when compared to the supplier's certificate an absolute specific gravity at 60/60*F of greater t n or qual to 0.83 but less than or 4

L equal to 0.89, or API Gra ty of greater than er equal to 27 degrees bu ess than or qual to 39 degrees; and 2.

Within one week af r obtaining the samp

, verify an impurity level of less th 2 milligrams of insolub. s per 100 milliliter is met when te ed in accordance with ASTM D 74-1970.

The analysis on e sample may be performed after addition of new fuel o 3.

Within o weeks of obtaining the sample, verify that he other prope ies specified in Table 1 of ASTM 0975-1977 and Re latory l

Gui 1.137 Position 2,a are met (when tested in accordanc with A

D975-1977).

An analysis for sulfur shall be performed n accordance with ASTM D129, ASTM 01552-1979 or ASTM 02622-19 u

l BEAVER VALLEY - UNIT 2 3/4 8-4

{

NOI)CSEh l

l.

L

=

5

'l i

)

e i

a-L INSERT'1 do By sampling (1) new fuel oil in accordance with ASTM D4057-81 prior to addition to the storage tanks and:

1)

By verifying in accordance with the tests specified in

' ASTM D975-81 prior to addition to the storage tanks that the sample hast a)

An API Gravity of within 0.3 degrees at 60 F or a specific gravity of within 0.0016 at 60/60 F, when i

compared to the supplier's certificate or an absolute I

specific gravity at 60/60 F of greater than or equal to 0.83 but less than or equal to 0.89 or an API gravity at 60 F of great 2r than or equal to 27 degrees but less than or equal to 39 degrees, b)

A kinematic viscosity at 40 C of greater than or equal to 1.9 centistokes, but less than or equal to 4.1 centistokes, if gravity was not determined by comparisen with the supplier's certification, c)

A flash point equal to or greater than 125 F, and d)

A clear and bright appearance with proper color when tested in accordance with ASTM D4176-82.

f 2)

By verifying within 31 days of obtaining the sample that the other properties specified in Table 1 of ASTM D975-81 are met when tested in accordance with ASTM D975-81 except L

that the analysis for sulfur may be performed in accordance with ASTM D1552-79 or ASTM D2622-82.

0; At least once every 31 days by obtaining a sample of fuer oil from the storage tanks and day tanks in accordance with ASTM D2276-78, and verifying that total particulate contamination is less than 10 mg/ liter when checked in accordance with ASTM D2276-78, Method A.

l l

1 l

I l

TLEtTR"iCAL POWER SYSTEMS I

. 4 L

SURVEILLANCE REOUIREMENTS (Continued) j?pf At least once per 10 years or after any modifications which l

could affect diesel generator interdependence by starting ** both diesel generators simultaneously, during shutdown, and verifying that both diesel generators accelerate to at least 514 rpm in less than or equal to 10 seconds.

/'.

At least once per 10 years by:

l 1)

Draining each main fuel oil storage tank, removing the accumu-lated sediment, and cleaning the tank using a sodium hypochlorite l'

solution or other appropriate cleaning solution, and 2)

Performing a pressure test, of those portions of the diesel fuel oil system designed to Section III, subsection ND of the ASME Code, at a test pressure equal to 110% of_the system design pressure.

i a

l 1

1 i

1

\\

l l

l l

i l

i

    • This test s5all be conducted in accordance with the manufacturer's recommen-dations regarding engine prelube and warmup procedures, and as applicable regarding loading recommendations.

i BEAVER VALLEY - UNIT 2 3/4 8-5

/WWoJEh

}

~

3/4.8 ELECTRICAL POWER SYSTEMS BASES q

3/4.8.1, 3/4.8.2 A.C. SOURCES AND ONSITE POWER DISTRIBUTION (Continued)

Table 3.8-1 specifies the normal limits for each designated pilot cell and each connected cell for electrolyte level,. float voltage and specific gravity.

The limits for the designated pilot cells float voltage and specific gravity, greater than 2.13 volts and 0.015 below the manufacturer's full charge specific gravity or a battery charger current that had stabilized at a low value, is characteristic of a charged cell with adequate capacity.

The nomal limits for each connected cell for float voltage and specific gravity, greater than 2.13 volts and not more than 0.020 below the manufacturer's full charge specificgravitywithanaveragespecificgravityofalltheconnectedcells not more than 0.010 below the manufacturer s full charge specific gravity, ensures the OPERABILITY and capability of the battery.

Operation with a battery cell's parameter outside the normal limit but" within the allowable value specified in Table 3.8-1 is permitted for up to 7 days. During this 7 day period:

(1) the allowable values for electrolyte level ensures no physical damage to the plates with an adequate electron transfer capability; (2) the allowable value for the average specific gravity of all the cells, not more than 0.020 below the manufacturer's recommended full charge specific gravity, ensures that the decrease in rating will be less than the safety margin provided in sizing; 3) the allowable value for an individual cell's specific gravity, ensures that an individual cell's specific gravity will not be more than 0.042 below the manufacturer's full charge specific gravity and that the overall capability of the battery will be maintained within an acceptable limit; and 4) the allowable value for an individual cell's float voltage, greater than 2.07 volts, ensures the battery's capability to perform its design function.

/Joyha Q) p rWides cla v*Ift ha bit of sfe c ' b ' a he',. I,8', /, /

t ac % y u W ents wk s/h dkel 9 e., m k s an I

inspwa ble recu H sf sa " eI//" ~ e- "p 'umb as a t/. 7. J. /, 2. a',.2 ad V 2'. ), /, 2, e A accor a once win l

Aep alohty SwWe /,/.1 ? A c A s lan / dey u /o}ey AsMr C, ?.a,

l l

l 1

l l

BEAVER VALLEY - UNIT 2 B 3/4 8-2 Nd/0SEb l

I A'PFACHMENT B Safety Analysis Beaver Valley Power Station i

Proposed Technical Specification Change BV-1 Change No. 171 BV-2 Chanae No. 32 Description of Amendment Request:

The proposed amendment would modify the diesel generator surveillance requirements to reflect the j

McGuire Technical Specifications (TS) and Draft Revision 5 of the 9tandard Technical Specifications (STS) recommended by the NRC for sampling and analysis of diesel generator fuel oil.

j specification 3.8.1.1 has been revised by adding note (1) to clarify the Action requirements when the diesel generators are inoperable as a

result of surveillance requirements 4. 8.1.1. 2.d. 2 or 4. 8.1.1. 2. e.

These surveillance requirements verify the quality of the fuel oil in the storage tanks on a

periodic basis and in accordance with Regulatory Guide 1.137 Regulatory Position C.2.a, the fuel oil may be l

replaced in a

short period of time (about a week) when the fuel oil i

does not meet the specification requirements.

The intent of the surveillance requirements is to ensure the fuel oil satisfies the quality specifications, therefore, note (1) has been written to allow up to 7

days to correct the out of specification condition whether this involves replacing the fuel oil or another suitsble method.

Surveillance requirement 4.8.1.1.2.a.3 has been deleted for both units.

The fuel oil sample verification requirements will be satisfied by surveillance requirements 4.8.1.1.2.c, d and e.

BV-1 surveillance requirement 4.8.1.1.2.c has been added to require temoval of accumulated water (1) from the day tank at least once per 31 days and after each operation of the diesel where the diesel has i

operated for 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br /> or more, and (2) from the fuel oil storage tank, at least once per 92 days.

This surv3111ance requirement is consistent with the BV-2 requirement, however, it differs from the McGuire requirement in that the McGuire TS required removal of accumulated water from the storage tank once per 31 d'ys.

The BV-2 TS requires romoval of accumulated water once per 92 days.

This quarterly surveillance is consistent with a clarification in Draft Revision 5

of the Standard Technical Specifications (STS) which provides for a frequency of once per 92 days (or once per 31 days (if the groundwater table is equal to or higher than the bottom of the I

fuel oil storage tanks)).

This also reflects the guidance provided in Regulatory Guide 1.137

" Fuel-Oil Systems For Standby Diesel Generators,"

Regulatory Position C.2.d which states " Accumulated condensate should be removed from storage tanks on a quarterly basis or on a

monthly basis when it is suspected or known that the groundwater table is equal to or higher than the bottom of buried storage tanks."

The groundwater table averages 30 feet below the surface as described in BV-1 UFSAR Section 2.3.2 and Figure 2.3-3; and BV-2 UFSAR Section 2.4.13 and Figure 2.4-17, therefore, the quarterly surveillance is applicable.

e

%tttchment B (C intinued)

{

Surveillance r quirement 4.8.1.1.2.d has been added to the BV-1 TS to l

reflect the Mc oire and STS requirements for sampling and testing new i

fuel oil.

7 is surveillance requirement has also been incorporated in the BV-2

.S to replace surveillance requirement 4.8.1.1.2.d and effectively updates the ASTM standards referenced to later versions.

Surveillance requirement 4.8.1.1.2.e has been added to both units TS to require sampling the fuel oil in the storage tanks and day tanks at least every 31 days and verifying the total particulate contamination is less than 10 mg/ liter.

This will be performed in accordance with ASTM D2276-78 Method A which provides a more accurate test method for indicatioa of fuel oil impurity than the method currently specified in the BV-2 requirements.

BV-2 surveillance requirements 4.8.1.1.2.e and f have been re-numbered to reflect the addition of surveillance requirement 4.8.1.1.2.e.

These changes do not affect the BV-1 UFSAR Section 8.5 Emergency Power System and 9.14 Fuel Oil Systems or BV-2 UFSAR Section 9.5.4 t

Emergency Diesel Generator Fuel Oil Storage and Transfer System and Section 1.8 Conformance to NRC Regulatory Guides.

These fuel oil sampling and testing requirements have been approved for use at other plants and provide updated versions of the current BV-2 requirements.

The proposed changes incorporate additional requirements for BV-1 and update the BV-2 requirements to ensure adequate fuel oil quality is available for diesel generator operation i

and will not affect the accident analysis or reduce the safety of the plant.

l

[- -.

I ATTACHMENT C No Significant Hazard Evaluation Beaver Valley Power Station Proposed Te.,hnical Specification Change BV-1 Change No. 171 BV-2 Change No. 32 Basis for proposed no significant hacards consideration determination:

The Commission has provided standards for determining whether a

significant hazards consideration exists in accordance with 10 CFR 50.92(c).

A proposed amendment to an operating license for a

facility involves no significant hazards consideration if operation of the facility in accordance with the proposed amendment would not (1) involve a significant increase in the probability or consequences of an accident previously evaluated, (2) create the possibility of a new or different kind of accident from any accident previously evaluated, or (3) involve a significant reduction in a margin of safety.

The proposed changes do not involve a

significant hazard consideration because:

1.

The diesel generator fuel oil surveillance requirements have been revised to reflect Draft Revision 5 of the Stundard Technical Specifications (STS) and the McGuire Technical Specifications (TS).

Specification 3.8.1.1 has been revised by adding note (1) to clarify the Action requirements when the diesel generators are inoperable as a result of surveillance requirements 4.8.1.1.2.d.2 or 4.8.1.1.2.e.

These surveillance requirements verify the quality of the fuel oil in the storage tanks on a periodic basis and in accordance with Regulatory Guido 1.137 Regulatory Position C.2.a, the fuel oil may be replaced in a short period of time (about a

week) when the fuel oil does not meet the specification requirements.

The intent of the surveillance requirements is to ensure the fuol oil satisfies the quality specifications, therefore, note (1) has been written to allow up to 7 days to correct the out of specification condition whether this involves replacing the fuel oil or another suitable method.

Surveillance requirement 4.8.1.1.2.a.3 has been deleted for both units.

These fuel oil sample verification requirements will be satisfied by surveillance requirements 4.8.1.1.2.c, d

and e.

BV-1 surveillance requirement 4.8.1.1.2.c has been added to require removal of accumulated water (1) from the day tank at lesst once por 31 days and after each operation of the diesel where the diesel has operated for 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br /> or more, and (2) from the fuel oil storage tank, at least once per 92 days.

This is consistent with the DV-2 r equirement,- Draft Revision 5 of the STS and Regulatory Guide 1.137 " Fuel Oil Systems For Standby Diesel Generators."

Surveillance requirement 4.8.1.1.2.d has been added to the BV-1 TS to reflect the McGuire requirements for sampling and testing new fuel oil.

This surveillance requirement has also been incorporated in the BV-2 TS to replace surveillance requirement 4.8.1.1.2.d and effectively updates the ASTM standards referenced to later versions.

f a

h

(

'Att:chnient C (Continu:d) j

(

\\

Surveillance requirement 4.8.1.1.2.e has been added to both units l

TS to require sampling the fuel oil in the storage tanks and day tanks at least every 31 days and verifying the total particulate l

contamination is less than 10 mg/ liter.

This will be performed i

in accordance with ASTM D2276-78 method A which provides a more i

accurate test method for indication of fuel oil impurity than the method currently specified in the BV-2 requirements.

BV-2 surveillance requirements 4.8.1.1.2.e and f have been re-numbered to reflect the addition of surveillance requirement 4.8.1.1.2.e.

These changes do not affect the BV-1 UFSAR Section 8.5 Emergency Power System and 9.14 Fuel Oil Systems or BV-2 UFSAR Section l

9.5.4 Emergency Diesel Generator Fuel Oil Storage and Transfer System and Section 1.8 Conformance to NRC Regulatory Guides.

These fuel oil sampling and testing requirements have been approved for use at other plants and provide updated versions of i

the current BV-2 requirements.

The proposed changes incorporate additional requirements for BV-1 and update the BV-2 requirements to ensure adequate fuel oil quality is available for diesel generator operation, thercfore, the probability or consequences of an accident previously evaluated will not be increased.

2.

The proposed changes incorporate additional requirements for BV-1 and update the BV-2 fuel oil sampling and quality verification requirements.

These changen are consistent with Draft Revision 5 of the STS and the McGuire TS which provide an acceptable basis i

for adequate fuel oil surveillance.

Therefore, the proposed i

changes will not create the possibility of a new or different i

kind of accident from any accident previously evaluated.

3.

These changes are consistent with the accepted criteria for

sampling, testing and verification of diesel generator fuel oil quality.

The proposed changes will not affect any of the plant setpoints or margins to the accident analysis limits.

Therefore, the proposed changes will not involve a significant reduction in l

the margin of safety of the plant.

Therefore, based on the above considerations, this amendment does not involve a significant hazard.