ML19326C101

From kanterella
Jump to navigation Jump to search
Forwards ROs 50-313/76-12,50-313/76-13 & 50-313/76-14
Date released: 12/06/2019 Download: ML19326C101


RO 50-313/76-14:on 760628:svc Water Valve CV-3812 Failed to Open on Command During Surveillance Test.Caused by Apparent Binding Between Stem & Bushing.Stem & Bushing Will Be Replaced
ML19326C108
Person / Time
Site: Arkansas Nuclear Entergy icon.png
Issue date: 07/16/1976
From: Cook R
ARKANSAS POWER & LIGHT CO.
To:
References
Download: ML19326C108 (4)
RO 50-313/76-13:on 760624,leak Found in Feedwater Line to Steam Generator A.Visual Insp Indicates Cause Due to Electrolysis or Corrosion Between Pipe & Concrete Floor Rebar.Defective Pipe Replaced & Floor Penetration Enlarged
ML19326C104
Person / Time
Site: Arkansas Nuclear Entergy icon.png
Issue date: 07/16/1976
From: Mardis D
ARKANSAS POWER & LIGHT CO.
To:
References
Download: ML19326C104 (4)
RO 50-313/76-12:on 760622,socket Weld Leak Discovered in Primary Makeup Pump P36C Suction Relief Line.Cause Not Determined.Leak Isolated at Pump Suction & Discharge.New Piping Section & Elbow Installed
ML19326C103
Person / Time
Site: Arkansas Nuclear Entergy icon.png
Issue date: 07/16/1976
From: Cook R
ARKANSAS POWER & LIGHT CO.
To:
References
Download: ML19326C103 (4)
Forwards ROs 50-313/76-12,50-313/76-13 & 50-313/76-14
ML19326C100
Person / Time
Site: Arkansas Nuclear Entergy icon.png
Issue date: 07/16/1976
From: Phillips J
ARKANSAS POWER & LIGHT CO.
To: HOWARD E M
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION IV)
References
Download: ML19326C100 (1)