Category:CONTRACTED REPORT - RTA
MONTHYEARML20101Q3431992-06-30030 June 1992 Metallurgical Evaluation of Weld Overlaid Pipe Sections from Brunswick Unit 2 Nuclear Power Station ML20065C9611990-08-24024 August 1990 Rev 2 to Technical Evaluation Rept Brunswick Steam Electric Plant Units 1 & 2 Station Blackout Evaluation, Final Rept ML20011D9151989-11-30030 November 1989 Review of the Brunswick Steam Electric Plant Probabilistic Risk Assessment ML20071P7151989-11-30030 November 1989 Rev 1 to Brunswick Steam Electric Plant Unit 2 Risk-Based Insp Guide, Final Version ML20005E9971989-11-30030 November 1989 Technical Evaluation Rept Pump & Valve Inservice Testing Program,Brunswick Steam Electric Plant,Units 1 & 2. ML19325C1451989-07-10010 July 1989 Technical Evaluation Rept for Dcrdr at CP&L Brunswick Steam Electric Plant,Units 1 & 2. ML19325C1471989-07-0707 July 1989 Post-Implementation Audit Rept for CP&L Brunswick Steam Electric Plant Units 1 & 2 SPDS 890515-18. ML20070Q5251989-01-31031 January 1989 Nuclear Power Plant Sys Sourcebook,Brunswick 1 & 2 ML20246P9671988-01-31031 January 1988 Technical Evaluation Rept on Second 10-yr Interval Inservice Insp Program Plan,Brunswick Steam Electric Plant Unit 1 ML20246B7221988-01-31031 January 1988 Technical Evaluation Rept on First 10-Yr Interval Inservice Insp Relief Requests:Cp&L,Brunswick Steam Electric Plant, Units 1 & 2 ML20236P6401987-07-31031 July 1987 Review of Recirculation Pump Trip Design for Brunswick Steam Electric Plants, Informal Rept ML20215L8821987-05-31031 May 1987 Final Conformance to Generic Ltr 83-28,Item 2.2.2 - Vendor Interface Programs for All Other Safety-Related Components: Brunswick 1 & 2, Informal Rept ML20214R0681987-04-30030 April 1987 Conformance to Item 2.1 (Part 2) of Generic Ltr 83-28, Reactor Trip Sys Vendor Interface,Arnold,Brunswick-1 & 2, Informal Rept ML20215L8631987-04-30030 April 1987 Final Conformance to Generic Ltr 83-28,Item 2.2.1 - Equipment Classification for All Other Safety-Related Components,Brunswick 1 & 2, Informal Rept ML20211P0781986-07-16016 July 1986 Structural Evaluation of Vacuum Breakers (Mark I Containment Program),Brunswick Steam Electric Plant Units 1 & 2, Supplementary Technical Evaluation Rept ML20203P9991986-03-0707 March 1986 Site Survey of Brunswick Steam Electric Plant Units 1 & 2 Maint Program & Practices, Technical Ltr Rept ML20127P3631985-06-30030 June 1985 IN-PLANT Source Term Measurements at Brunswick Steam Electric Station ML20128N6481985-05-31031 May 1985 Adequacy of Station Electric Distribution Sys Voltages, Brunswick Steam Electric Station,Units 1 & 2, Informal Rept ML20128A5741985-03-25025 March 1985 Conformance to Reg Guide 1.97,Brunswick Steam Electric Plant Units 1 & 2, Informal Rept ML20127D6251985-03-15015 March 1985 Evaluation of Detailed Control Room Design Review Program Plan for Brunswick Steam Electric Plant,Units 1 & 2 ML20115A3821984-11-16016 November 1984 Masonry Wall Design,Brunswick Steam Electric Plant Units 1 & 2, Interim Technical Evaluation Rept ML20106G0091984-11-16016 November 1984 Masonry Wall Design,Brunswick Steam Electric Plant Units 1 & 2, Technical Evaluation Rept ML20100R7141984-10-30030 October 1984 Conformance to Reg Guide 1.97,Brunswick Steam Electric Plant Units 1 & 2, Interim Rept Covering Emergency Response Capability ML20090H7121984-04-23023 April 1984 Control of Heavy Loads,Brunswick Units 1 & 2, Technical Evaluation Rept ML20085J3181983-10-0707 October 1983 Audit for Mark 1 Containment Long-Term Program - Structural Analysis for Operating Reactors,Brunswick Units 1 & 2, Technical Evaluation Rept ML20085J0541983-09-30030 September 1983 Technical Evaluation of Brunswick Units 1 & 2,Plant-Unique Analysis Rept ML20091D6541983-07-31031 July 1983 Integrity of Brunswick Steam Electric Plant,Units 1 & 2 Reactor Coolant Boundary Piping Sys, Technical Evaluation ML20079Q7261983-06-13013 June 1983 ECCS Repts (F-47) TMI Action Plan Requirements,Brunswick Steam Electric Plant,Units 1 & 2, Technical Evaluation Rept ML20127A2891982-10-0505 October 1982 Containment Leak Rate Testing Investigations, Progress Summary for Sept 1982 ML20126F2541982-08-26026 August 1982 Containment Leak Rate Testing, Monthly Progress Rept for Aug 1982 ML20065R2451982-07-15015 July 1982 Operating Reactors - TMI Lessons Learned,NUREG-0737 Response Evaluations (Program Ii);Project 1,RCS Vents for Brunswick 1 & 2, Final Technical Evaluation Rept ML20078Q6001982-07-0909 July 1982 Control of Heavy Loads,Brunswick Units 1 & 2, Draft Technical Evaluation Rept ML20069E1781982-06-30030 June 1982 Investigation of Raychem Cable Installed in Brunswick Plant,Phase 2-Evaluation & Test Recommendation ML20069E4381982-04-26026 April 1982 Technical Evaluation Rept on Monitoring of Electric Power to Reactor Protection Sys for Brunswick Steam Electric Plant,Units 1 & 2 ML20069E1761981-10-23023 October 1981 Investigation of Raychem Cable Installed in Brunswick Plant,Phase 1-Preliminary Evaluation & Test Plan, Interim Rept ML20009F1711981-06-30030 June 1981 Adequacy of Station Electric Distribution Sys Voltages, Brunswick Nuclear Power Station Units 1 & 2, Technical Evaluation Rept ML20009H1121981-06-10010 June 1981 Equipment Environ Qualification,Brunswick Steam Electric Plant Unit 2, Technical Evaluation Rept ML20009H1111981-06-10010 June 1981 Equipment Environ Qualification,Brunswick Steam Electric Plant Unit 1, Technical Evaluation Rept ML20003F1101981-03-31031 March 1981 Adequacy of Station Electric Distribution Sys Voltages, Preliminary Technical Evaluation Rept ML20004E2911981-01-31031 January 1981 Equipment Environ Qualification,Brunswick Unit 2, Final Draft Technical Evaluation Rept ML19338G5661980-10-0909 October 1980 Feedwater Nozzle Cracking,Brunswick Steam Electric Plant Unit 1, Technical Evaluation Rept ML19338G5681980-10-0909 October 1980 Feedwater Nozzle Cracking,Brunswick Steam Electric Plant Unit 2, Technical Evaluation Rept ML20010E4231980-07-31031 July 1980 Technical Evaluation Rept:Electrical,Instrumentation & Control Aspects of Override of Containment Purge Valve Isolation & Other Safety Feature Signals. ML19330A7231980-07-31031 July 1980 Electrical,Instrumentation & Control Aspects of Override of Containment Purge Valve Isolation & Other Safety Feature Signals,Brunswick Steam Electric Plant,Unit 2. ML19326D9631980-07-31031 July 1980 Electrical,Instrumentation & Control Aspects of Override of Containment Purge Valve Isolation & Other Safety Feature Signals,Brunswick Steam Electric Plant,Unit 1. ML19327A0401980-07-23023 July 1980 Miscellaneous Nozzle Cracking:Brunswick Steam Electric Plant,Unit 2, Technical Evaluation Rept ML19327A0301980-07-23023 July 1980 Technical Evaluation Rept for Brunswick Steam Electric Plant,Units 1 & 2 ML19331D9351980-07-21021 July 1980 Primary Coolant Sys Pressure Isolation Valves,Brunswick Units 1 & 2, Technical Evaluation Rept ML19323H4201980-02-29029 February 1980 Degraded Grid Protection for Class IE Power Sys at Brunswick Steam Electric Plant,Units 1 & 2, Technical Evaluation Rept ML19210E0361979-11-15015 November 1979 IE-116-B, Rept of Evaluation of Stresses in Recirculation Inlet Nozzle Safe-End at Brunswick Steam Electric Plant Units 1 & 2, Final Rept by Parameter,Inc.Recommends Continued Inservice Surveillance 1992-06-30
[Table view] Category:QUICK LOOK
MONTHYEARML20101Q3431992-06-30030 June 1992 Metallurgical Evaluation of Weld Overlaid Pipe Sections from Brunswick Unit 2 Nuclear Power Station ML20065C9611990-08-24024 August 1990 Rev 2 to Technical Evaluation Rept Brunswick Steam Electric Plant Units 1 & 2 Station Blackout Evaluation, Final Rept ML20011D9151989-11-30030 November 1989 Review of the Brunswick Steam Electric Plant Probabilistic Risk Assessment ML20071P7151989-11-30030 November 1989 Rev 1 to Brunswick Steam Electric Plant Unit 2 Risk-Based Insp Guide, Final Version ML20005E9971989-11-30030 November 1989 Technical Evaluation Rept Pump & Valve Inservice Testing Program,Brunswick Steam Electric Plant,Units 1 & 2. ML19325C1451989-07-10010 July 1989 Technical Evaluation Rept for Dcrdr at CP&L Brunswick Steam Electric Plant,Units 1 & 2. ML19325C1471989-07-0707 July 1989 Post-Implementation Audit Rept for CP&L Brunswick Steam Electric Plant Units 1 & 2 SPDS 890515-18. ML20070Q5251989-01-31031 January 1989 Nuclear Power Plant Sys Sourcebook,Brunswick 1 & 2 ML20246P9671988-01-31031 January 1988 Technical Evaluation Rept on Second 10-yr Interval Inservice Insp Program Plan,Brunswick Steam Electric Plant Unit 1 ML20246B7221988-01-31031 January 1988 Technical Evaluation Rept on First 10-Yr Interval Inservice Insp Relief Requests:Cp&L,Brunswick Steam Electric Plant, Units 1 & 2 ML20236P6401987-07-31031 July 1987 Review of Recirculation Pump Trip Design for Brunswick Steam Electric Plants, Informal Rept ML20215L8821987-05-31031 May 1987 Final Conformance to Generic Ltr 83-28,Item 2.2.2 - Vendor Interface Programs for All Other Safety-Related Components: Brunswick 1 & 2, Informal Rept ML20214R0681987-04-30030 April 1987 Conformance to Item 2.1 (Part 2) of Generic Ltr 83-28, Reactor Trip Sys Vendor Interface,Arnold,Brunswick-1 & 2, Informal Rept ML20215L8631987-04-30030 April 1987 Final Conformance to Generic Ltr 83-28,Item 2.2.1 - Equipment Classification for All Other Safety-Related Components,Brunswick 1 & 2, Informal Rept ML20211P0781986-07-16016 July 1986 Structural Evaluation of Vacuum Breakers (Mark I Containment Program),Brunswick Steam Electric Plant Units 1 & 2, Supplementary Technical Evaluation Rept ML20203P9991986-03-0707 March 1986 Site Survey of Brunswick Steam Electric Plant Units 1 & 2 Maint Program & Practices, Technical Ltr Rept ML20127P3631985-06-30030 June 1985 IN-PLANT Source Term Measurements at Brunswick Steam Electric Station ML20128N6481985-05-31031 May 1985 Adequacy of Station Electric Distribution Sys Voltages, Brunswick Steam Electric Station,Units 1 & 2, Informal Rept ML20128A5741985-03-25025 March 1985 Conformance to Reg Guide 1.97,Brunswick Steam Electric Plant Units 1 & 2, Informal Rept ML20127D6251985-03-15015 March 1985 Evaluation of Detailed Control Room Design Review Program Plan for Brunswick Steam Electric Plant,Units 1 & 2 ML20115A3821984-11-16016 November 1984 Masonry Wall Design,Brunswick Steam Electric Plant Units 1 & 2, Interim Technical Evaluation Rept ML20106G0091984-11-16016 November 1984 Masonry Wall Design,Brunswick Steam Electric Plant Units 1 & 2, Technical Evaluation Rept ML20100R7141984-10-30030 October 1984 Conformance to Reg Guide 1.97,Brunswick Steam Electric Plant Units 1 & 2, Interim Rept Covering Emergency Response Capability ML20090H7121984-04-23023 April 1984 Control of Heavy Loads,Brunswick Units 1 & 2, Technical Evaluation Rept ML20085J3181983-10-0707 October 1983 Audit for Mark 1 Containment Long-Term Program - Structural Analysis for Operating Reactors,Brunswick Units 1 & 2, Technical Evaluation Rept ML20085J0541983-09-30030 September 1983 Technical Evaluation of Brunswick Units 1 & 2,Plant-Unique Analysis Rept ML20091D6541983-07-31031 July 1983 Integrity of Brunswick Steam Electric Plant,Units 1 & 2 Reactor Coolant Boundary Piping Sys, Technical Evaluation ML20079Q7261983-06-13013 June 1983 ECCS Repts (F-47) TMI Action Plan Requirements,Brunswick Steam Electric Plant,Units 1 & 2, Technical Evaluation Rept ML20127A2891982-10-0505 October 1982 Containment Leak Rate Testing Investigations, Progress Summary for Sept 1982 ML20126F2541982-08-26026 August 1982 Containment Leak Rate Testing, Monthly Progress Rept for Aug 1982 ML20065R2451982-07-15015 July 1982 Operating Reactors - TMI Lessons Learned,NUREG-0737 Response Evaluations (Program Ii);Project 1,RCS Vents for Brunswick 1 & 2, Final Technical Evaluation Rept ML20078Q6001982-07-0909 July 1982 Control of Heavy Loads,Brunswick Units 1 & 2, Draft Technical Evaluation Rept ML20069E1781982-06-30030 June 1982 Investigation of Raychem Cable Installed in Brunswick Plant,Phase 2-Evaluation & Test Recommendation ML20069E4381982-04-26026 April 1982 Technical Evaluation Rept on Monitoring of Electric Power to Reactor Protection Sys for Brunswick Steam Electric Plant,Units 1 & 2 ML20069E1761981-10-23023 October 1981 Investigation of Raychem Cable Installed in Brunswick Plant,Phase 1-Preliminary Evaluation & Test Plan, Interim Rept ML20009F1711981-06-30030 June 1981 Adequacy of Station Electric Distribution Sys Voltages, Brunswick Nuclear Power Station Units 1 & 2, Technical Evaluation Rept ML20009H1121981-06-10010 June 1981 Equipment Environ Qualification,Brunswick Steam Electric Plant Unit 2, Technical Evaluation Rept ML20009H1111981-06-10010 June 1981 Equipment Environ Qualification,Brunswick Steam Electric Plant Unit 1, Technical Evaluation Rept ML20003F1101981-03-31031 March 1981 Adequacy of Station Electric Distribution Sys Voltages, Preliminary Technical Evaluation Rept ML20004E2911981-01-31031 January 1981 Equipment Environ Qualification,Brunswick Unit 2, Final Draft Technical Evaluation Rept ML19338G5661980-10-0909 October 1980 Feedwater Nozzle Cracking,Brunswick Steam Electric Plant Unit 1, Technical Evaluation Rept ML19338G5681980-10-0909 October 1980 Feedwater Nozzle Cracking,Brunswick Steam Electric Plant Unit 2, Technical Evaluation Rept ML20010E4231980-07-31031 July 1980 Technical Evaluation Rept:Electrical,Instrumentation & Control Aspects of Override of Containment Purge Valve Isolation & Other Safety Feature Signals. ML19330A7231980-07-31031 July 1980 Electrical,Instrumentation & Control Aspects of Override of Containment Purge Valve Isolation & Other Safety Feature Signals,Brunswick Steam Electric Plant,Unit 2. ML19326D9631980-07-31031 July 1980 Electrical,Instrumentation & Control Aspects of Override of Containment Purge Valve Isolation & Other Safety Feature Signals,Brunswick Steam Electric Plant,Unit 1. ML19327A0401980-07-23023 July 1980 Miscellaneous Nozzle Cracking:Brunswick Steam Electric Plant,Unit 2, Technical Evaluation Rept ML19327A0301980-07-23023 July 1980 Technical Evaluation Rept for Brunswick Steam Electric Plant,Units 1 & 2 ML19331D9351980-07-21021 July 1980 Primary Coolant Sys Pressure Isolation Valves,Brunswick Units 1 & 2, Technical Evaluation Rept ML19323H4201980-02-29029 February 1980 Degraded Grid Protection for Class IE Power Sys at Brunswick Steam Electric Plant,Units 1 & 2, Technical Evaluation Rept ML19210E0361979-11-15015 November 1979 IE-116-B, Rept of Evaluation of Stresses in Recirculation Inlet Nozzle Safe-End at Brunswick Steam Electric Plant Units 1 & 2, Final Rept by Parameter,Inc.Recommends Continued Inservice Surveillance 1992-06-30
[Table view] Category:ETC. (PERIODIC
MONTHYEARML20101Q3431992-06-30030 June 1992 Metallurgical Evaluation of Weld Overlaid Pipe Sections from Brunswick Unit 2 Nuclear Power Station ML20065C9611990-08-24024 August 1990 Rev 2 to Technical Evaluation Rept Brunswick Steam Electric Plant Units 1 & 2 Station Blackout Evaluation, Final Rept ML20011D9151989-11-30030 November 1989 Review of the Brunswick Steam Electric Plant Probabilistic Risk Assessment ML20071P7151989-11-30030 November 1989 Rev 1 to Brunswick Steam Electric Plant Unit 2 Risk-Based Insp Guide, Final Version ML20005E9971989-11-30030 November 1989 Technical Evaluation Rept Pump & Valve Inservice Testing Program,Brunswick Steam Electric Plant,Units 1 & 2. ML19325C1451989-07-10010 July 1989 Technical Evaluation Rept for Dcrdr at CP&L Brunswick Steam Electric Plant,Units 1 & 2. ML19325C1471989-07-0707 July 1989 Post-Implementation Audit Rept for CP&L Brunswick Steam Electric Plant Units 1 & 2 SPDS 890515-18. ML20070Q5251989-01-31031 January 1989 Nuclear Power Plant Sys Sourcebook,Brunswick 1 & 2 ML20246P9671988-01-31031 January 1988 Technical Evaluation Rept on Second 10-yr Interval Inservice Insp Program Plan,Brunswick Steam Electric Plant Unit 1 ML20246B7221988-01-31031 January 1988 Technical Evaluation Rept on First 10-Yr Interval Inservice Insp Relief Requests:Cp&L,Brunswick Steam Electric Plant, Units 1 & 2 ML20236P6401987-07-31031 July 1987 Review of Recirculation Pump Trip Design for Brunswick Steam Electric Plants, Informal Rept ML20215L8821987-05-31031 May 1987 Final Conformance to Generic Ltr 83-28,Item 2.2.2 - Vendor Interface Programs for All Other Safety-Related Components: Brunswick 1 & 2, Informal Rept ML20214R0681987-04-30030 April 1987 Conformance to Item 2.1 (Part 2) of Generic Ltr 83-28, Reactor Trip Sys Vendor Interface,Arnold,Brunswick-1 & 2, Informal Rept ML20215L8631987-04-30030 April 1987 Final Conformance to Generic Ltr 83-28,Item 2.2.1 - Equipment Classification for All Other Safety-Related Components,Brunswick 1 & 2, Informal Rept ML20211P0781986-07-16016 July 1986 Structural Evaluation of Vacuum Breakers (Mark I Containment Program),Brunswick Steam Electric Plant Units 1 & 2, Supplementary Technical Evaluation Rept ML20203P9991986-03-0707 March 1986 Site Survey of Brunswick Steam Electric Plant Units 1 & 2 Maint Program & Practices, Technical Ltr Rept ML20127P3631985-06-30030 June 1985 IN-PLANT Source Term Measurements at Brunswick Steam Electric Station ML20128N6481985-05-31031 May 1985 Adequacy of Station Electric Distribution Sys Voltages, Brunswick Steam Electric Station,Units 1 & 2, Informal Rept ML20128A5741985-03-25025 March 1985 Conformance to Reg Guide 1.97,Brunswick Steam Electric Plant Units 1 & 2, Informal Rept ML20127D6251985-03-15015 March 1985 Evaluation of Detailed Control Room Design Review Program Plan for Brunswick Steam Electric Plant,Units 1 & 2 ML20115A3821984-11-16016 November 1984 Masonry Wall Design,Brunswick Steam Electric Plant Units 1 & 2, Interim Technical Evaluation Rept ML20106G0091984-11-16016 November 1984 Masonry Wall Design,Brunswick Steam Electric Plant Units 1 & 2, Technical Evaluation Rept ML20100R7141984-10-30030 October 1984 Conformance to Reg Guide 1.97,Brunswick Steam Electric Plant Units 1 & 2, Interim Rept Covering Emergency Response Capability ML20090H7121984-04-23023 April 1984 Control of Heavy Loads,Brunswick Units 1 & 2, Technical Evaluation Rept ML20085J3181983-10-0707 October 1983 Audit for Mark 1 Containment Long-Term Program - Structural Analysis for Operating Reactors,Brunswick Units 1 & 2, Technical Evaluation Rept ML20085J0541983-09-30030 September 1983 Technical Evaluation of Brunswick Units 1 & 2,Plant-Unique Analysis Rept ML20091D6541983-07-31031 July 1983 Integrity of Brunswick Steam Electric Plant,Units 1 & 2 Reactor Coolant Boundary Piping Sys, Technical Evaluation ML20079Q7261983-06-13013 June 1983 ECCS Repts (F-47) TMI Action Plan Requirements,Brunswick Steam Electric Plant,Units 1 & 2, Technical Evaluation Rept ML20127A2891982-10-0505 October 1982 Containment Leak Rate Testing Investigations, Progress Summary for Sept 1982 ML20126F2541982-08-26026 August 1982 Containment Leak Rate Testing, Monthly Progress Rept for Aug 1982 ML20065R2451982-07-15015 July 1982 Operating Reactors - TMI Lessons Learned,NUREG-0737 Response Evaluations (Program Ii);Project 1,RCS Vents for Brunswick 1 & 2, Final Technical Evaluation Rept ML20078Q6001982-07-0909 July 1982 Control of Heavy Loads,Brunswick Units 1 & 2, Draft Technical Evaluation Rept ML20069E1781982-06-30030 June 1982 Investigation of Raychem Cable Installed in Brunswick Plant,Phase 2-Evaluation & Test Recommendation ML20069E4381982-04-26026 April 1982 Technical Evaluation Rept on Monitoring of Electric Power to Reactor Protection Sys for Brunswick Steam Electric Plant,Units 1 & 2 ML20069E1761981-10-23023 October 1981 Investigation of Raychem Cable Installed in Brunswick Plant,Phase 1-Preliminary Evaluation & Test Plan, Interim Rept ML20009F1711981-06-30030 June 1981 Adequacy of Station Electric Distribution Sys Voltages, Brunswick Nuclear Power Station Units 1 & 2, Technical Evaluation Rept ML20009H1121981-06-10010 June 1981 Equipment Environ Qualification,Brunswick Steam Electric Plant Unit 2, Technical Evaluation Rept ML20009H1111981-06-10010 June 1981 Equipment Environ Qualification,Brunswick Steam Electric Plant Unit 1, Technical Evaluation Rept ML20003F1101981-03-31031 March 1981 Adequacy of Station Electric Distribution Sys Voltages, Preliminary Technical Evaluation Rept ML20004E2911981-01-31031 January 1981 Equipment Environ Qualification,Brunswick Unit 2, Final Draft Technical Evaluation Rept ML19338G5661980-10-0909 October 1980 Feedwater Nozzle Cracking,Brunswick Steam Electric Plant Unit 1, Technical Evaluation Rept ML19338G5681980-10-0909 October 1980 Feedwater Nozzle Cracking,Brunswick Steam Electric Plant Unit 2, Technical Evaluation Rept ML20010E4231980-07-31031 July 1980 Technical Evaluation Rept:Electrical,Instrumentation & Control Aspects of Override of Containment Purge Valve Isolation & Other Safety Feature Signals. ML19330A7231980-07-31031 July 1980 Electrical,Instrumentation & Control Aspects of Override of Containment Purge Valve Isolation & Other Safety Feature Signals,Brunswick Steam Electric Plant,Unit 2. ML19326D9631980-07-31031 July 1980 Electrical,Instrumentation & Control Aspects of Override of Containment Purge Valve Isolation & Other Safety Feature Signals,Brunswick Steam Electric Plant,Unit 1. ML19327A0401980-07-23023 July 1980 Miscellaneous Nozzle Cracking:Brunswick Steam Electric Plant,Unit 2, Technical Evaluation Rept ML19327A0301980-07-23023 July 1980 Technical Evaluation Rept for Brunswick Steam Electric Plant,Units 1 & 2 ML19331D9351980-07-21021 July 1980 Primary Coolant Sys Pressure Isolation Valves,Brunswick Units 1 & 2, Technical Evaluation Rept ML19323H4201980-02-29029 February 1980 Degraded Grid Protection for Class IE Power Sys at Brunswick Steam Electric Plant,Units 1 & 2, Technical Evaluation Rept ML19210E0361979-11-15015 November 1979 IE-116-B, Rept of Evaluation of Stresses in Recirculation Inlet Nozzle Safe-End at Brunswick Steam Electric Plant Units 1 & 2, Final Rept by Parameter,Inc.Recommends Continued Inservice Surveillance 1992-06-30
[Table view] Category:RESEARCH AND TECHNICAL ASSISTANCE REPORTS
MONTHYEARML20009F1711981-06-30030 June 1981 Adequacy of Station Electric Distribution Sys Voltages, Brunswick Nuclear Power Station Units 1 & 2, Technical Evaluation Rept ML20003F1101981-03-31031 March 1981 Adequacy of Station Electric Distribution Sys Voltages, Preliminary Technical Evaluation Rept ML19330A7231980-07-31031 July 1980 Electrical,Instrumentation & Control Aspects of Override of Containment Purge Valve Isolation & Other Safety Feature Signals,Brunswick Steam Electric Plant,Unit 2. ML19326D9631980-07-31031 July 1980 Electrical,Instrumentation & Control Aspects of Override of Containment Purge Valve Isolation & Other Safety Feature Signals,Brunswick Steam Electric Plant,Unit 1. ML19323H4201980-02-29029 February 1980 Degraded Grid Protection for Class IE Power Sys at Brunswick Steam Electric Plant,Units 1 & 2, Technical Evaluation Rept 1981-06-30
[Table view] Category:TEXT-PROCUREMENT & CONTRACTS
MONTHYEARML20101Q3431992-06-30030 June 1992 Metallurgical Evaluation of Weld Overlaid Pipe Sections from Brunswick Unit 2 Nuclear Power Station ML20058A1131990-09-27027 September 1990 Notification of Contract Execution,Awarding Task Order 3, NDE Support at Brunswick 1 Nuclear Power Plant. Contractor:Tet,Inc ML20065C9611990-08-24024 August 1990 Rev 2 to Technical Evaluation Rept Brunswick Steam Electric Plant Units 1 & 2 Station Blackout Evaluation, Final Rept ML20005E9971989-11-30030 November 1989 Technical Evaluation Rept Pump & Valve Inservice Testing Program,Brunswick Steam Electric Plant,Units 1 & 2. ML20071P7151989-11-30030 November 1989 Rev 1 to Brunswick Steam Electric Plant Unit 2 Risk-Based Insp Guide, Final Version ML20011D9151989-11-30030 November 1989 Review of the Brunswick Steam Electric Plant Probabilistic Risk Assessment ML19325C1451989-07-10010 July 1989 Technical Evaluation Rept for Dcrdr at CP&L Brunswick Steam Electric Plant,Units 1 & 2. ML19325C1471989-07-0707 July 1989 Post-Implementation Audit Rept for CP&L Brunswick Steam Electric Plant Units 1 & 2 SPDS 890515-18. ML20070Q5251989-01-31031 January 1989 Nuclear Power Plant Sys Sourcebook,Brunswick 1 & 2 ML20246B7221988-01-31031 January 1988 Technical Evaluation Rept on First 10-Yr Interval Inservice Insp Relief Requests:Cp&L,Brunswick Steam Electric Plant, Units 1 & 2 ML20246P9671988-01-31031 January 1988 Technical Evaluation Rept on Second 10-yr Interval Inservice Insp Program Plan,Brunswick Steam Electric Plant Unit 1 ML20236P6401987-07-31031 July 1987 Review of Recirculation Pump Trip Design for Brunswick Steam Electric Plants, Informal Rept ML20215L8821987-05-31031 May 1987 Final Conformance to Generic Ltr 83-28,Item 2.2.2 - Vendor Interface Programs for All Other Safety-Related Components: Brunswick 1 & 2, Informal Rept ML20215L8631987-04-30030 April 1987 Final Conformance to Generic Ltr 83-28,Item 2.2.1 - Equipment Classification for All Other Safety-Related Components,Brunswick 1 & 2, Informal Rept ML20214R0681987-04-30030 April 1987 Conformance to Item 2.1 (Part 2) of Generic Ltr 83-28, Reactor Trip Sys Vendor Interface,Arnold,Brunswick-1 & 2, Informal Rept ML20211P0781986-07-16016 July 1986 Structural Evaluation of Vacuum Breakers (Mark I Containment Program),Brunswick Steam Electric Plant Units 1 & 2, Supplementary Technical Evaluation Rept ML20203P9991986-03-0707 March 1986 Site Survey of Brunswick Steam Electric Plant Units 1 & 2 Maint Program & Practices, Technical Ltr Rept ML20127P3631985-06-30030 June 1985 IN-PLANT Source Term Measurements at Brunswick Steam Electric Station ML20128N6481985-05-31031 May 1985 Adequacy of Station Electric Distribution Sys Voltages, Brunswick Steam Electric Station,Units 1 & 2, Informal Rept ML20128A5741985-03-25025 March 1985 Conformance to Reg Guide 1.97,Brunswick Steam Electric Plant Units 1 & 2, Informal Rept ML20127D6251985-03-15015 March 1985 Evaluation of Detailed Control Room Design Review Program Plan for Brunswick Steam Electric Plant,Units 1 & 2 ML20115A3821984-11-16016 November 1984 Masonry Wall Design,Brunswick Steam Electric Plant Units 1 & 2, Interim Technical Evaluation Rept ML20106G0091984-11-16016 November 1984 Masonry Wall Design,Brunswick Steam Electric Plant Units 1 & 2, Technical Evaluation Rept ML20100R7141984-10-30030 October 1984 Conformance to Reg Guide 1.97,Brunswick Steam Electric Plant Units 1 & 2, Interim Rept Covering Emergency Response Capability ML20090H7121984-04-23023 April 1984 Control of Heavy Loads,Brunswick Units 1 & 2, Technical Evaluation Rept ML20085J3181983-10-0707 October 1983 Audit for Mark 1 Containment Long-Term Program - Structural Analysis for Operating Reactors,Brunswick Units 1 & 2, Technical Evaluation Rept ML20085J0541983-09-30030 September 1983 Technical Evaluation of Brunswick Units 1 & 2,Plant-Unique Analysis Rept ML20091D6541983-07-31031 July 1983 Integrity of Brunswick Steam Electric Plant,Units 1 & 2 Reactor Coolant Boundary Piping Sys, Technical Evaluation ML20079Q7261983-06-13013 June 1983 ECCS Repts (F-47) TMI Action Plan Requirements,Brunswick Steam Electric Plant,Units 1 & 2, Technical Evaluation Rept ML20127A2891982-10-0505 October 1982 Containment Leak Rate Testing Investigations, Progress Summary for Sept 1982 ML20126F2541982-08-26026 August 1982 Containment Leak Rate Testing, Monthly Progress Rept for Aug 1982 ML20065R2451982-07-15015 July 1982 Operating Reactors - TMI Lessons Learned,NUREG-0737 Response Evaluations (Program Ii);Project 1,RCS Vents for Brunswick 1 & 2, Final Technical Evaluation Rept ML20078Q6001982-07-0909 July 1982 Control of Heavy Loads,Brunswick Units 1 & 2, Draft Technical Evaluation Rept ML20069E1781982-06-30030 June 1982 Investigation of Raychem Cable Installed in Brunswick Plant,Phase 2-Evaluation & Test Recommendation ML20069E4381982-04-26026 April 1982 Technical Evaluation Rept on Monitoring of Electric Power to Reactor Protection Sys for Brunswick Steam Electric Plant,Units 1 & 2 ML20069E1761981-10-23023 October 1981 Investigation of Raychem Cable Installed in Brunswick Plant,Phase 1-Preliminary Evaluation & Test Plan, Interim Rept ML20010F0751981-07-30030 July 1981 Settlement Agreement Between VEPCO & Nc Municipal Power Agency Number 3 Including Agreement for Interim Electric Svc & Agreement for Transmission Use & Other Electric Svc. ML20010F0711981-07-30030 July 1981 Purchase,Const & Ownership Agreement Between CP&L & Nc Municipal Power Agency Number 3 & Exhibits. ML20010F0671981-07-30030 July 1981 Operating & Fuel Agreement Between CP&L & Nc Municipal Power Agency Number 3 & Exhibits. ML20010F0601981-07-30030 July 1981 Power Coordination Agreement Between CP&L & Nc Municipal Power Agency Number 3 & Exhibits. ML20009F1711981-06-30030 June 1981 Adequacy of Station Electric Distribution Sys Voltages, Brunswick Nuclear Power Station Units 1 & 2, Technical Evaluation Rept ML20009H1111981-06-10010 June 1981 Equipment Environ Qualification,Brunswick Steam Electric Plant Unit 1, Technical Evaluation Rept ML20009H1121981-06-10010 June 1981 Equipment Environ Qualification,Brunswick Steam Electric Plant Unit 2, Technical Evaluation Rept ML20003F1101981-03-31031 March 1981 Adequacy of Station Electric Distribution Sys Voltages, Preliminary Technical Evaluation Rept ML20004E2911981-01-31031 January 1981 Equipment Environ Qualification,Brunswick Unit 2, Final Draft Technical Evaluation Rept ML19338G5681980-10-0909 October 1980 Feedwater Nozzle Cracking,Brunswick Steam Electric Plant Unit 2, Technical Evaluation Rept ML19338G5661980-10-0909 October 1980 Feedwater Nozzle Cracking,Brunswick Steam Electric Plant Unit 1, Technical Evaluation Rept ML19330A7231980-07-31031 July 1980 Electrical,Instrumentation & Control Aspects of Override of Containment Purge Valve Isolation & Other Safety Feature Signals,Brunswick Steam Electric Plant,Unit 2. ML20010E4231980-07-31031 July 1980 Technical Evaluation Rept:Electrical,Instrumentation & Control Aspects of Override of Containment Purge Valve Isolation & Other Safety Feature Signals. ML19326D9631980-07-31031 July 1980 Electrical,Instrumentation & Control Aspects of Override of Containment Purge Valve Isolation & Other Safety Feature Signals,Brunswick Steam Electric Plant,Unit 1. 1992-06-30
[Table view] |
Text
_ _ _ _ . _ _
EGG-EA-5109 Se~0ier. February 1980 HL.;p~n ' % I 11:i . ;G:').'
{iQ'] n u?'*T' :~p
.o .. p l
TECHNICAL EVALUATION REPORT OF THE DECRADED GRID
. p, 'y gI PROTECTION FOR CLASS IE POWER SYSTEMS AT THE l
j BRUNSWICK STEAM ELECTRIC PLANT, UNIT NOS. 1 AND 2, DOCKE'INOS.50-327AND50-36 C. J. Cleveland 1
l 1
U.S. Department of Energy '
Idaho Operations Office
- Idaho National Engineering Laboratory
.3. u7 v.y/3*gy y -
- r y57. ;7 s .. x ,.
i si 4*Ndy.'I .% .
~'
y.f.4 '
. [1, -
r .
-r .
r
.,e.
)
'. e 56 ,
-~
.--_g._ ,
I ~.4 i e i ,g '
f.J . i ' N * *
l
^
h __ s. 4 l
["" *"i. M . N ====imonum
$h77) l
'j; ,; %
c W, ^- m.
-.smasi ' 'sumpum*merzo sauer d' i
gg _n sT4Ww ' %~ S. M 1 u; & . ear ~ we = g,.s ,.;. g F O miiu%-- 74
'E % . , , g --- .. .
i sr - -
-W @*f., V6.
,e'. ~
. i- *:L.? .
~
~; h 7; ~-, . .- :,r. 3 '.'
?; -
,4y
- This is an informal report Intended for use as a preliminary or working document
~
.3.- .
.?
- f. .,
Prepared for the U.S. Nuclear Regulatory Comission l
Under DCE Contract No. DE-AC07-76ID01570 0 yQ gggg'd#*
l l FIN No. A6256 - '
8 006120503 h _ . _ _ .. _ ,_
A p E G n G ,.. . .
peausom:x sne, nra INTERIM REPORT Accession No.
Report No. EGG-EA-5109 Contract Program or Project
Title:
Electrical, Instrumentation, and Control System Support Subject of this Document:
Degraded Grid Protection for Class IE Power Systems at the Brunswick Steam Electric Plant, Unit Nos. 1 and 2 Type of Document: .
Technical Evaluation Report Author (s):
C. J. Cleveland Date of Document:
February 1980 -
Responsible NRC Individual and NRC Office or Division:
Paul Shemanski, Division of Operating Reactors This document was prapared primarily for preliminary or internal use. it has not received full review and approval. Since there .nay be substantive changes, this document should not be considered final.
EG&G Idaho, Inc.
Idaho Falls, Idaho 83415 Prepared for the U.S. Nuclear Regulatory Commission Washington, D.C.
Under DOE Contract No. DE-AC07 761001570 NRC FIN No. A6256 INTERIM REPORT Tl l
1
. . ~ _
1 d
i 1358F 1
4 i
i i
~
2 i
' i
'i I
1 l
l -TECHNICAL EVALUATION REPORT 1 DEGRADED GRID PROTECTION FOR CLASS IE POWER SYSTEMS f
BRUNSWICK STEAM ELECTRIC PLANT, UNIT NOS. 1 AND 2 i
j Docket Nos. 50-325 and 50-326
- C. J. Cleveland i
February 1980 't 4
i a
N i
I k
i i
t
-(TACs 10013,,10014) e b' '
b - -- , . , _ . . , , - . . . . . _ . _ - - , ._-
. ~ . _ - . ._.. _._ -- - - . . . . , ,
ABSTRACT In June 1977, the NRC sent all operating reactors a letter outlining three positions the staff had taken in regards to the onsite emergency power system. Carolina Power & Light Company was to assess the suscepti-bility of the safety-related electrical equipment at the Brunswick Steam Elec tric Plant, Units 1 and 2 to a sustained voltage degradation of the offsite source and interaction of the offsite and onsite emergency power sy s tem. This report contains an evaluation of CP&L's analyses, modifica-tions, and technical spe,cification changes to comply with these NRC pos itions .
l
}
ii e
CONTENTS
1.0 INTRODUCTION
. . . . . .. . . . ., , , , , , , , , , , , , , , , , , y a
1 2.0 DESICN BASE CRITERIA . . . . . . . . . . , , , . , , , , , , , , , , y 4
a 3.0 EVALUATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 i 3.1 Existing Undervoltage Protection . . . . . . . . . . . . . . . 2 3.2 Modifications . . . . . . . . . . . . . . . . . . . . . . . . . 2 3.3 Discussion . . . . . . . ....... . . . . . . . . . . . . 3 4.0 CONCUSIONS . . * * . . . . . . . . . . . . . . . . . . . . . 6
5.0 REFERENCES
. . . . . . .. . . . . . . . . . . . . . . . , . y t
i 1
1 I
l
- i 111 I i i
+~r - - , w - ,e -+-4 <ne'
TECHNICAL EVALUATION REPORT DEGRADED GRID PROTECTION FOR CLASS IE POWER SYSTEMS BRUNSWICK STEAM ELECTRIC PLANT, UNIT NOS. 1 AND 2 1.0 IRIRODUCTION On June 3,1977, the NRC requested the Carolina Power & Light Company (CP&L) to assess the susceptibility of the safety-related electrical equip-ment at the Brunswick Steam Electric Plant, Units 1 and 2 (BSEP-l&2) to a sustained voltage degradation of the offsite source and interaction of the offsite and onsite emergency power systems. The letter contained three positions with which the current design of the plant was to be compared.
After comparing the current design to the Staff Positions, CP&L was required to either propose modifications to satisfy the positions and criteria or furnish an analysis to substantiate that the existing f acility design has equivalent capabilities.
By letter, dated March 6, 1979, CP&L proposed certain design modifica-tions and changes to' the Technical Specifications to satisfy the criteria and Staff Positions. The modifications consist of the installation of a second-level undervoltage protection system for the class lE equipment, and blocking of the load shedding feature when the diesel generator is supplying power to the emergency buses. The NRC required that the setpoint, surveil-lance requirements, test requirements, and allowable limits were to be !
included by CP&L in the plant Technical Specifications.
l 2.0 DESIGN BASE CRITERIA l
i The design base criteria that were applied in determining the accept- '
ability of the system modifications to protect the safety-related equipment from a sustained degradation of the offsite grid are:
- 1. General Design Criterion 17 (GDC 17), " Electrical Power Systems," of Appendix A, " General Design Criteria for Nuclear Power Plants," of 10 CFR 503
- 2. IEEE Standard 279-1971, " Class IE Power Systems for Nuclear Power Generating Stations"4 1
- 3. IEEE Standard 308-1974, " Class IE Power Systems for Nuclear Power Generating Stationsn5
- 4. Staff Positions as detailed in a letter sent to the licensee, dated June 3, 19771
- 5. ANSI Standard C84.1-1977, " Voltage Ratings for Electri-cal Power Systems and Equipment (60 H2)."6 3.0 EVALUATION This section provides, in Subsection 3.1, a brief description of the existing undervoltage protection at the BSEP-l&2; in Subsection 3.2, a description of the licensee's proposed modifications for the second-level undervoltage protection; in Subsection 3.3, a discussion of how the pro-posed modifications meet the design base criteria.
3.1 Existing Undervoltage Protection. The present design uses one inverse time delay voltage relay on each of the four station 4160 V Class IE safety buses to detect a loss-of-of fsite power. These relays have a maxi-mum setpoint of 2940 V (.71%). The characteristics of the relay are such that when the offsite voltage drops to this value and persists for at least ten seconds, the offsite sources are tripped, emergency diesel generator start is initiated, load shedding is initiated, and the undervoltage condi-tion is annunciated at the Reactor-Turbine Generator (RTG) boards.
The existing system does not disable or bypass the load-shedding feature once the emergency diesels are feeding the emergency buses. The time duration and magnitude of any voltage transients caused by starting large motors are stated by the licensee as not being large or long enough to trip the loss-of-power undervoltage relays.
I 3.2 Modifications. The licensee has proposed adding 12 definite time undervoltage relays to the four 4160 V Class IE buses. There will be three relays per bus, one per phase, arranged in a two-of-three coincident logic.
These relays will have a nominal setpoint of 3727 V (89.5% of bus voltage) with a time delay of ten (10) seconds. When an undervoltage condition persists below the setpoint for at least ten seconds, the feeder breaker
[
from the BOP switchgear and the incoming line breaker to the emergency bus 2
?
l
will be tripped. This is accomplished when the undervoltage relay contacts energize an existing auxi* iary relay (94). A contact from a time-delay on drop-out relay, set at two seconds, is wired in series with the undervoltage relay contacts to prevent tripping of the breakers as the emergency bus is initially energized until the voltage reaches rated value. This time-delay relay is energized by a "b" contact of the incoming line breaker.
To block load shedding once the emergency bus is being supplied by its diesel generator, a "b" contact of the diesel generator breaker is being wired in series with the existing undervoltage auxiliary relays that initi-ate load shedding on the ESF busas.
Proposed changes to the plant's Technical Specifications, adding the surveillance requirements, allowable limits for the setpoint and time delay, and limiting conditions for operation for the second-level undervoltage monitors, were also furnished by the licensee. An analysis to substantiate the limiting conditions and minimum and maximum setpoint limits was also part of the proposal.
3.3 Discussion. The first position of the NRC staff letter required that a second level of undervoltage protection for the onsite power system be provided. The letter stipulates other criteria that the undervoltage protec-tion must meet. Each criterion is restated below followed by a discussion regarding the licensee's compliance with that criterion.
- 1. "The selec tion of voltage and time setpoints shall be determined from an analysis of the voltage requirements of the safety-related loads at all onsite system dis-tribution levels."
The lic~ensee's proposed setpoint of 3727 V at the 4160 V 4
bus is 93% of the motor-rated voltage of 4000 V. This setpoint reflected down to the 480 V buses will be greater than 90* of the motor-rated voltage. As the '
motors are the most limiting equipment in the system, this setpoint is acceptable. The licensee's analysis considered other factors such as MCC contactor pick-up voltage and drop-out voltage.
3 f
- 2. "The voltage protection shall include coincidence logic to preclude spurious trips of the offstite power sources."
The proposed modification incorporates a two-out-of-three logic scheme, thereby satisfying this criterion.
- 3. "The time delay selected shall be based on the following conditions:
- a. "The allowable time delay, including margin, shall not exceed the maximum tLne delay that is assumed in the FSAR accident analysis."
Inasmuch as the time delay proposed is the same as for the time delay for loss-of power relays, the proposed time delay of ten secc.:ds with the margin does not exceed the maximum time delay as analyzed in the FSAR.
The proposed time delay will not be -the cause of any thermal damage to the safety-related equipment.
The setpoint is within voltage ranges recommended by ANSI C84.1-1977 for sustained operation.
- b. "The time delay shall minimize the effect of short-duration disturbances from reducing the unavail-ability of the offsite power source (s)."
The licensee's proposed time delay of ten seconds is long enough to override any short inconsequen-tial grid disturbances. Further, we have reviewed the licensee's analysis and agree with the licen-see's finding that any voltage dips caused from the starting of large motors will not trip the offsite source.
- c. "The allowable time duration of a degraded voltage condition at all distribution system levels shall not result in failure of safety systems or components."
A review of the licensee's voltage analysis 7 indicates that the tLac delay will not cause any failures of the safety-related equipment since the voltage setpoint is within the allowable tolerance ,
of the equipment-rated voltage.
- 4. "The voltage monitors shall automatically initiate the disconnection of offsite power sources whenever the voltage setpoint and time delay limits have been -
exceeded." -
4 t'
T
A review of the licensee's proposal substantiates that this criterion is met.
- 5. "The voltage monitors shall be designed to satisfy the requirements of IEEE Standard 279-1971."
The licensee has stated in his proposal that the modifi-cations are designed to meet or exceed IEEE Standard 279 as well as GDC 17. Also stated in the proposal, the Quality Assurance Program, in effect, incorporating the requirements of 10 CFR 50, Appendix B, will be applied to the extent necessary. A test switch is designed into the circuitry so testing can be performed. The licensees submittal states that the design character-istics of the relays exceed the environmental and seismic load requirmnents.
- 6. "The Technical Specifications shall include Ibniting conditions for operations, surveillance requirements, trip setpoints with minimum and maximum lbsits, and allowable values for the second-level voltage protection monitors."
The licencee's proposal for Technical Specification changes does include all of the required items. An analysis is also provided which assures that the range between thg minimum and maximum trip point settings, as I well as the allowable limits, will not be the cause of
{
spurious trips of the offsite source nor will they allow the voltage to be so low as to allow damage to the safety equipment. Instrument drift, transformer accuracy, and calibration accuracy were factors in this analysis.
The second NRC staff position requires that the system design auto-matica11y prevent load shedding of the emergency buses once the onsite sources are supplying power to all sequenced loads. The load shedding must
, also be reinstated if the onsite breakers are tripped. The licensee's proposal states that modifications will be made to comply with this posi-tion. The addition of a "b" contact of the diesel generator breaker in series with the undervoltage auxiliary relay contact will satisfy this position.
1 1
The third NRC staff position requires that certain test requirements be added to the Technical Specifications. These tests were to demonstrate the full-functional operability and independence of the onsite power sources and are to be performed at least once per 18 months during shutdown. The 5
fi
tests are to simulate loss of offsite power in conjunction with a simulated safety injection actuation signal and to simulate interrruption and subse-quent reconnection of onsite power sources. These tests verify the proper operation of the load shed system, the load shed bypass when the emergency diesel generators are supplying power to their respective buses, and that there is no adverse interaction between the onsite and offsite power sources.
The testing procedures proposed by the licensee do comply with the full intent of this position. Load shedding on offsite power trip is tested. Lead sequencing once the diesel generator is supplying the safety buses is tested. Because of the design of the Brunswick load-shedding circuits, the licensee felt that the test calling for tripping the diesel breaker and restarting was redundant. The addition of the diesel breaker "b" contact is the only change to the logic circuit. Any time the diesel breaker is closed, the existing undervoltage relays that initiate load shedding will be disabled. This is tested adequately by position three (test b). The time durations of the tests (five minutes with full safety loads) will verify that the time delay is sufficient to avoid spurious trips and that the load shed bypass circuit is functioning properly.
4.0 CONCLUSION
S Based on the information provided by CP&L, it has been determined that the proposed modifications comply with NRC staff position 1. All of the staff's requirements and design base criteria have been met. The modifica-tions will protect the class lE equipment from a sustained degraded voltage condition of the offsite power source.
The modifications to the logic of the load shed circuitry do comply '
with staff position 2 and will prevent adverse interaction of the offsite .
and onsite energency power systems.
The proposed changes to the Technical Specifications do adequately test the system modifications and do comply with staff position 3. The surveillance requirements, limiting conditions for operation, minimum and '
6
?
4
maximum 1.imits for the trip point, and allowable values meet the intent of staff position 1.
It is therefore concluded that CP&L's proposed modifications and Tech-nical Specification changes are acceptable.
5.0 REFERENCES
- 1. NRC (Schwencer) letter to CP&L (Utley), dated June 3, 1977.
- 2. CP&L (Utley) letter to NRC (Ippolito), dated March 6, 1979.
- 3. General Design Criterion 17, " Electric Power Systems," of Appendix A,
" General Design Criteria of Nuclear Power Plants," to 10 CFR Part 50,
" Domestic Licensing of Production and Utilization Facilities."
- 4. IEEE Standard 279-1971, " Criteria for Protection Systems for Nuclear Power Generating Stations."
- 5. IEEE Standard 308-1974, " Standard Criteria for Class IE Power Systems for Nuclear Power Generating Stations."
- 6. ANSI C84.1-1977, " Voltage Ratings for Electric Power Systems and Equipment" (60 HZ).
- 7. CP&L (Utley) letter to NRC (Ippolito), dated October 8, 1979.
- 8. Final Safety Analysis Report (FSAR) for the Brunswick Steam Electric Plant, Units 1 and 2.
- 9. CP&L (Utley) letter to NRC (Rusche), dated October 25, 1976.
- 10. CP&L (Utley) letter to NRC (Swencer), dated July 28, 1977.
7 ,