- _ _ _ - - _.
e APPENDIX A NOTICE OF VIOLATION Power Authority of the State of New York Docket No. 50-333 Based on the results of an NRC inspection conducted on February 4-8, and 15, 1980, it appears that certain of your activities were not conducted in full compliance with conditions of your.NRC Facility License No. DPR-59, as indicated below.
Item A is an infraction and Item B is a deficiency.
A.
Technical Specification 3.3A.2.a states in part; " Control rods which cannot be moved with control rod drive pressure shall be considered inoperable."
Technical Specification 4.3A.2.d states in part; "If the a control rod cannot be fully inserted, a shutdown margin test shall be made to demonstrate under this condition that the core can be made sub-critical for any reactivity condition during the remainder of the operating cycle with the analytically detemined, highest worth control rod capable of withdrawal, fully withdrawn, and all other control rods capable of insertion fully inserted."
Contrary to the above, on November 5,1979 at 0900 hours0.0104 days <br />0.25 hours <br />0.00149 weeks <br />3.4245e-4 months <br />, partially inserted control rod 18-35 was isolated and made inoperable, to repair a leak on the hydraulic control unit, without either fully inserting the control rod or perfoming a shutdown margin test prior to making the control rod inoperable.
B.
Environmental Technical Specification 2.2.3 states in part; "The pH of treated water in the waste neutralizer tanks and floor drain sample tanks prior to being discharged into the discharge tunnel shall be between 6.0 and 9.0" Contrary to the above, during the period of December 9,1979 through January 2,1980, an uncontrolled release of regeneration waste water with an estimated pH range of 4.0 to 9.1 was discharged into the discharge tunnel.