ML19323D188

From kanterella
Jump to navigation Jump to search
Advises That IE Info Notice 80-15, Axial (Longitudinal) Oriented Cracking in Piping, Was Sent to Listed Utils on 800421
ML19323D188
Person / Time
Site: Dresden 
Issue date: 04/25/1980
From: Carroll D
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION III)
To:
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION III)
References
NUDOCS 8005210232
Download: ML19323D188 (3)


Text

[ -,%<

800sa2ag g Ilc UNITED STATES i

8" NUCLEAR REGULATORY COMMISSION D

y e REGION 111 b[

Q 799 ROOSEVELT ROAD o

GLEN ELLYN. lLLINOIS 60137 APR 2 51980 MEMORANDUM FOR: Those on Attached List FROM:

Dorothy E. Carroll, Acting Chief, Administrative Branch

SUBJECT:

IE INFORMATION NOTICE NO. 80-15 The attached IE Information Notice No. 80-15 titled " Axial (Longitudinal)

Oriented Cracking in Piping" was sent to the licensees listed below on April 21, 1980 for action:

American Electric Power Service Corporation Indiana and Michigan Power Company D. C. Cook 1, 2 (50-315, 50-316)

Cincinnati Gas & Electric Company Zimmer (50-358)

Cleveland Electric Illuminating Company Perry 1, 2 (50-440, 50-441)

Commonwealth Edison Company Braidwood I, 2 (50-456, 50-457)

Byron 1, 2 (50-454, 50-455)

Dresden 1, 2, 3 (50-10, 50-237, 50-249)

LaSalle 1, 2 (50-373, 50-374)

Quad-Cities 1, 2 (50-254, 50-265)

Zion 1, 2 (50-295, 50-304)

Consumers Power Company Big Rock Point (50-155)

Midland 1, 2 (50-329, 50-330)

Palisades (50-255)

Dairyland Power Cooperative LACBWR (50-409)

Detroit Edison Company Fermi 2 (50-341)

Illinois Power Company Clinton 1, 2 (50-461, 50-462)

Those on Attached List APR 2 51960 Iowa Electric Light & Power Company Duane Arnold (50-331)

Northern Indiana Public Service Company Bailly (50-367)

Northern States Power Company Monticello (50-263)

Prairie Island 1, 2 (50-282, 50-306)

Paolic Service of Indiana Marble Hill 1, 2 (50-546, 50-547)

Toledo Edison Company Davis-Besse 1 (50-346)

Union Electric Power Company Callaway 1, 2 (50-483, 50-486)

Wisconsin Electric Power Company Point Beach 1, 2 (50-266, 50-301)

Wisconsin Public Service Corporation Kewaunee (50-305) k i

<sA.A s

~.

rothy E.

rrbll, Acting Chief Administrative Branch

Enclosure:

IE Information Notice No. 80-15 1

Addressees - Memorandum dated April 22, 1980 Central Files Reproduction Unit NRC 20b

O SSINS No.:

6870 Accession No.

UNITED STATES 8002280660 NUCLEAR REGULATORY COMMISSION OFO CE OF INSPECTION AND ENFORCEMENT WASHINGTON, D.C.

20555 April 21, 1980 IE Information Notice No. 8015 AXIAL (LONGITUDINAL) ORIENTED CRACKING IN PIPING

~

On March 8, 1980, the Commonwealth Edison Company reported to the NRC that slight leakage was observed from the "A" loop core spray injection piping during a reactor coolant system leakage test at their Quad-Cities Unit 2 Nuclear Power Station. The source of leakage was subsequently identified to be located adjacent to a shop weld joining a 90 elbow and a wedge section of elbow material used to extend the elbow to 105. Subsequent ultrasonic inspections revealed additional cracking in several other elbows in "A" and "B" core spray loops.

The cracks are located adjacent to welds and oriented transverse to the weld in the axial (longitudinal) piping direction.

The affected elbows have been removed and currently failure analyses are # 1 progress.

Preliminary results from liquid penetrant examinations of the ow interior surface in the counter bore / weld root area revealed axial orients

racks on both sides of the weld in the counter bores adjacent to the weld roots.

From the limited metallography performed to date, the cracking mode appears to be intergranular stress corrosion cracking.

The cracking, however, only appears to be slightly branched.

A determination as to whether or not the cracking extends into and across the welds cannot be made at this time.

It is significant to point out that these service sensitive lines, as defined by NUREG 313, had been examined on an augmented basis per NUREG 313 requirements.

Two of the affected welds were inspected ultrasonically at the current outage prior to the leakage being observed at the pressure test with no indication of cracking repor ted.

Further ultrasonic examinations, using standard ASME Section XI methods, performed after discovery of the leak clearly revealed the cracking (approximately 100% over the reference level).

Licensees are requested to inform NDE inspection personnel of the above stated information anti to emphasize the need for care when performing circumferential UT scan:. of the weld and adjacent areas in piping components.

Particular importance should be stressed when the examinations are performed on BWR service sensitive 304 stainless steel piping and on PWR 304 stainless steel piping in stagnant systems.

This Information Notice is provided as an early notification of a possibly significant matter that is still under review by the NRC staff.

It is expected that recipients will review the information for possible applicability to their facility.

No specific action or response is requested at this time.

If you have any questions regarding this matter, please contact the Director of the appropriate NRC Regional Office.

IE Information Notice No. 80-15 Enclosure April 21, 1980 RECENTLY ISSUED IE INFORMATION NOTICES Information Subject Oate Issued To Notice No, Issued 80-14 Safety Suggestions From 4/2/80 All power reactor Employees facilities with an OL or CP 80-13 General Electric Type SBM 4/2/80 All light water reactor Control Swiches - Defective facilities hol. ding power Cam Followers reactor OLs or cps 80-12 Instrument Failure Causes 3/31/80 All holders of power Opening of PORV and Block reactor OLs and cps Valve 80-11 General Problems with ASCO 3/14/80 All holders of Reactor Valves in Nuclear Application OL, CP, fuel fabrica-Including Fire Protection tion and processing Systems facilities 80-10 Partial Loss of Non-Nuclear 3/7/80 All power reactor Instrument System Power facilities holding i

Supply During Operation OLs and cps 80-09 Possible Occupational 3/7/80 All holders of Health Hazard Associated power reactor OLs with Closed Cooling Systems and near term cps 80-08 The States Company Sliding 3/7/80 All power reactor Link Electrical Terminal facilities with an OL Block or a CP 80-07 Pump Shaft Fatigue Cracking 2/29/80 All Light Water Reactor Facilities holder power f

reactor OLs and cps 80-06 Notification of Significant 2/27/80 All holders of Reactor Events OLs and to near term OL applicants 80-05 Chloride Contamination 2/8/80 All licensees of nuclear of Safety Related Piping power reactor facilities and applicants and holders of nuclear power reactor cps 5

4.

.