ML19322E242
| ML19322E242 | |
| Person / Time | |
|---|---|
| Site: | Humboldt Bay, Diablo Canyon |
| Issue date: | 03/14/1980 |
| From: | Engelken R NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION V) |
| To: | Crane P PACIFIC GAS & ELECTRIC CO. |
| References | |
| NUDOCS 8003260344 | |
| Download: ML19322E242 (1) | |
Text
r l{
p uso o.
UNITnD STATES E"
'n NUCLEAR REGULATORY COMMISSION REGION V 0, i g
1990 N. CALIFORNI A BOULEVARD
%,,
- e, +,e SUITE 202, WALNUT CREE K PLAZA WALNUT CREEK, CALIFORNI A 94596 March 14, 1980 Docket Hos. 50-133, 50-275, 50-323 Pacific Gas and Electric Company 77 Ber.le Street San Francisco, California 94106 Attention: Mr. Philip A. Crane, Jr.
Assistant General Counsel Gentlemen:
The enclosed Circular No. 80-04 is foniarded to you for information. No written response is required. Should you have any questions related to your understanding of the recomendations on this matter, please contact this office.
Sincerely, LJ f ?dW
/R'.
. Engelken, 7/
/ Director s
Enclosures:
- 1. IE Circular No. 80-04
- 2. List of Recently Issued IE Circulars cc w/ enclosures:
W. Barr, PG&E W. Raymond, PG&E R. Ramsay,- PG&E, Diablo Canyon E. Weeks, PG&E, Humboldt Bay E. B. Langley, PG&E 8 0 03260 Mk
f SSIfl5 N0. 6830 Accession No.:
UNITED STATES 7912190662 NUCLEAR REGULATORY C0fNISSION
((j)[JD OFFICE OF INSPECTION AND ENFORCEMENT
[U)({J)
[
WASHINGTON, D.C.
20555 Ift March 14,1980 IE Circular No. 80-04 SECURIflG 0F THREADED LOCKING DEVICES ON SAFETY-RELATED EQUIPMENT Description of Circumstances:
In recent months, several licensee event reports have been submitted that address the inoperability of safety-related equipment caused by loosened threaded locking devices.
Some of tha events are listed below:
I.
MAIN STEAM CHECK VALVE HEX fluf LOCKING DEVICES, TURKEY POINT N0. 3 REPORTABLE OCCURRENCE 250-79-31 (Oct. 22, 1979)
During a planned outage of Turkey Point Unit flo. 3 on October 7,1979, a two-inch internal diameter hex nut was discovered in the internals of a steam supply valve for a moisture separator-reheater.
Investigation revealed that the nut was missing from the disc stud of the 3A main steam check valve. The disc and disc stud were in the proper position and the valve was fully operable. The 3B and 3C main steam check valves were inspected and the disc stud, nut and locking washer were in place although some distress was noted on the 3C locking washer in that the tack welds on the locking pin had separated.
The licensee installed an improved locking device on the disc stud on each of the three main steam check valves.
The locking device consists of a tab washer that is prevented from rotating by a pin and by fingers that extended on either side of the valve arm; the tabs are bent up(MSIV) against two faces of the hex nut. The main steam isolation valves have the same type of hex nut locking device. The valves are Schutte and Koerting SK Type 828.
II. SLIPPAGE AND MISALIGlHENT OF VALVE LIflKAGES, DAVIS-BESSE LICENSEE EVENT REPORT fl0S78-101 (Nov.1,1978),78-126 (Jan. 26,1979),79-068 (July 19, 1970, and 79-098 (Oct. 30, 1979)
These reports involve the inoperability of two service water system valves and one component cooling water system valve. The valves were declared inoperable because the nut on the actuator linkage was either missing or had loosened to the point where there was slippage and r
misalignment of the valve linkage. These valves were provided by Hamel-Dahl.
The supplier has provided the licensee with an addendum to the instruction manual that defines the torque requirements for the cap screw that is used to retain the actuator link arm to the valve disc arm.
l l
4 IE Circular No. 80-04 March 14, 1980 Pace 2 of 3 III. ECCS SUBSYSTEM INOPERABLE - NO 12 SAFETY INJECTION PUMP IMPELLER LOCKNUTS LOOSE, SALEM NO. 1 LICENSEE EVENT REPORT NO. 79-68 (Dec. 20, 1979).
The AC supply breaker tripped when No.12 Safety Injection (SI) Pumo was started to fill the accumulators on October 18, 1979. When the rotor could not be turned by hand, the upper casing was removed for an inspec-tion of the pump internals. The radial and thrust locknuts were found loosened to the extent that they could be removed by hand.
The impeller spacer sleeves were worn and the impeller shaft was slightly bent. The pump was reworked, tested and returned to service on November 23 1979.
The locknuts on the three other Unit 1 and Unit 2 Safety Injection (SI)
Pumps were inspected and two pump impeller locknuts were found loose, and one pump impeller locknut was found secured with setscrews that had been installed by mistake at the manufacturing facility and the impeller was sent back to the manufacturer for rework. The locknuts on all of the SI pumps were secured using Locktite compound per Public Service Engineering Department reconmendation and the pump manufacturer's concurrence. The pumps are horizontal, centrifugal, ten stage units manufactured by Pacific Pumps, Inc.
IV.
TARGET ROCK MOTOR OPERATED GLOBE VALVES - BUSHING NOT STAKED, AN0 N0. 2 LICENSEE EVENT REPORT 79-93 (FEB. 14, 1980)
While investigating the failure of a High Pressure Safety Injection (HPSI) header shut-off valve at Arkansas Nuclear One, Unit 2, the threaded bushing was found loose. The bushing was not staked or other-wise secured to prevent, movement. This bushing is part of the mechanism which converts the valvh stem rotation to linear travel of the disk. The full open limit switch is gear driven by the valve operator and movement of the bushing can alter the relationship between stem rotation and linear travel such that valve travel in the open direction nay be terminated prematurely by the limit switch.
The HPSI header shut-off valves at AN0-2 are Target Rock 2-inch 1500# ANSI !10 tor Operated Globe Valves.
Arkansas Power & Light found that a similar problem exists with the Low Pressure Safety Injection (LPSI) header shut-off valves which are Target Rock 6-inch 1500# ANSI Motor Operated Globe Valves.
Target Rock has provided Arkansas Power & Light Company with a procedure for staking the bushing nuts.
V.
OTHER EVENTS Loose locking devices were also identified in one of the I & E Bulletins and two of the I & E Circulars issued in 1979:
IE Circular 79-04 Loose Locking Nut on Limitorque Valve Operators, IE Circular 79-19 Loose Locking Devices on Ingersoll-Rand Punps, IE Bulletin 79-15 Deep Draft Pumps.
IE Circular No. 80-04 tiarch 14, 1980 Page 3 of 3 Recommended Action for Licensees Consideration:
It is recommended that licensees of operating power reactors and holders of construction permits review the specific items presented in the " Description of Circumstances" for applicability at their facilities and review their installation and maintenance procedures to determine that whether securing of locking devices has been addressed in these procedures.
It is further recommended that installation and maintenance procedures for all safety-related components be reviewed to be sure the securing of locking devices is adequately covered.
No written response to this Circular is required.
If you require additional information regarding these matters, contact the Director of the appropriate NRC Regional Office.
i
r O'
ma IE Circular No. 80-04 Enclosure March 14, 1980 RECEllTLY ISSUED IE CIRCULARS Circular Subject Date of Issued to flo.
Issue 80-03 Protection from Toxic Gas 3/6/80 All holders of a Hazards power reactor OL 80-02 fluclear Power Plant Staff 2/1/80 All holders of Reactor Work Hours Ols, including research and test reactors, and cps 80-01 Service Advice for GE 1/17/80 All licensees of Induction Disc Relays nuclear power reactor operating facilities and holder: of nuclear power reactor cps 79-25 Shock Arrestor Strut 12/20/79 All licensees and Assembly Interference holders of power reactor cps 79-24 Proper Installation and 11/26/79 All Holders of a Calibration of Core Spray Power Reactor OL or Pipe Break Detection CP Equipment on BWRs.
79-23 Motor Starters and 11/26/79 All Power Reactor Contactors Failed Operating Facilities to Operate and Holdcrs of Reactor cps 79-22 Stroke Tines for Power 11/16/79 All Power Reactor Operated Relief Valves Operating Facilities and all Utilities having a CP 79-21 Prevention of Unplanned 10/19/79 All holders of Power Releases of Radioactivity Reactor OLs and cps 79-20 Failure of GTE Sylvania 9/24/79 All holders of Power Relay, Type PM Bulletin Reactor OLs and cps 7305, Catalog SU12-11-AC with a 12V AC Coil 79-19 Loose Locking Devices 9/13/79 All Holders of Power on Ingersoll-Rand Pumps Reactor OLs and cps