Submits Summary of Assessment Re Safety Significance from Alleged Welding Defects in Neutron Shield Tanks.Failure of Welds Would Result in Operational Inconvenience Rather than Safety Concern
ML19322D337
Person / Time
Site: Surry  
Issue date: 12/16/1976
From: Seyfrit K
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE)
To: Grier B
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION I)
Shared Package
ML19322D327 List:
References
FOIA-79-416 NUDOCS 8002110501
Download: ML19322D337 (2)


Text

. - _ _ _ _ _

%' 6ec %

( UCLEAR REGULATORY COMMISS

(

o UrnT C D si AT ts

_s'-

f.

a "l

[....

,t.

j,..)3,.$ :,, y WAsHiraciors, D.C. 2055s

- f (>/

s Decembe'r 16, 1976

% ='.,. <

..e g.

?

MEMORANDUM FOR:

Boyce H. Grier, Dir., RIP, IE FROM:

K. V. Seyfrit, Chief, RTA SUB' JECT:

ALLEGATIONS OF DEFECTIVE WELDING IN THE SURRY NEUTRON SHIELD TANKS This sunmarizes our assessment of the safety significan:e which might result from alleged welding defects in the Surry 1 and/or 2 neutron shieldtank(s).

Failure of the neutron shielding tank welds would be expected to result in an operational inconvenience rather than a safety concern for the following reasons:

1.

The shield tank is constructed of ductile material and is maintained with only the hydrostatic head of perhaps 40 ft., so that a weld failure would likely develop gradually rather than catastrophically.

The shield tank is kept full of water by means of a surge tank which has a low level alarm.

Should the surge tank level drop to the alarm point, an annunciator in the control room is rece:ved.

Any significant leakage would be detected in time to permit a reactor shutdown prior to loosing the protection of the water.

2.

The primary purpose of the shield tank is to prevent overheating and dehydration of the inner surface of the concrete primary shield wall, due to heating from neutron flux and heat from the reactor vessel.

Most reactor designs provide this protection with cooling coils imbedded in the concrete shield.

If all of the water were lost from the shield tank due to sudden failure, heat-up and damage to the inner surface of the concrete would develop gradually.

The reactor could be shut down before significant weakening or loss of sheilding capability would occur.

3.

Once the reactor is shut down, the concrete shield, which is 54 inches thick, provides adequate shielding without the water in the neutron shield tank.

Lead shielding is located beneath the neutron shield tank to protect station service personnel during reactor shutdown.

CONTACT:

D. C. Kirkpatrick s

9 4

.I 0

_._-._ g o o n 1 CO /

"l'

(

r' f

Boyce H. Grier

-2 December 16, 1976

~

For these reasons, it is concluded that the possible existence of defective welding in the Surry neutron shield. tank (s) has-virtually no real safety significance.

11 f

~f )

j~ /

K. V. Seyfri t'yvi~

UL at f.)._

, Chief Reac. tor Technical Assistance Branch i