ML19320B451
| ML19320B451 | |
| Person / Time | |
|---|---|
| Site: | Brunswick |
| Issue date: | 04/18/1980 |
| From: | NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION II) |
| To: | |
| Shared Package | |
| ML19320B424 | List: |
| References | |
| 50-324-80-10, 80-325-80-11, NUDOCS 8007100398 | |
| Download: ML19320B451 (1) | |
Text
__
-~
_ _. _ _ _ _ _ _ -. ~. _ _.. -
/O t
v APPENDIX B NOTItt: OF DEVIATION Carolina Power and Light Company License Nos. DPR-71 Brunswick
& DPR-62 Based on the results of the NRC inspection conducted on March 31 and April 1-3, 1980, certain of your activities appear to deviate from your commitments to the Commission as indicated below:
Section IV.C.3.c of the Fire Protection Program review of January 1, 1977, states in part that the sprinkler systems provided meet the criteria of National Fire Protection Association Standard 13 (NFPA-13), Sprinkler System.
Contrary to the above, the water flu. olarms for the deluge sprinkler systems to the standby gas treatment filters do not meet the criteria of NFPA-13 due to the following:
1.
The water flow alarm devices can not be properly tested except by a full flow test or operational test of each deluge valve.
Sections 3-17.3.3 and 3-17.4.4 of NFPA-13 require alarm devices for sprinkler systems to be equipped with a test connection which takes water from the supply side of the deluge valve.
2.
The control valves in the supply piping to the alarm devices are not of the type which clearly indicate if the valves are open or closed and are not constructed so that they may be locked or sealed in the open position as required by Section 3-17.4.5 of NPFA-13.
0007100
-