y ).
l Sacramento Municipal Utility District,
!. Docket No. O'n-0312 l
.I Certain' activities under your construction permit appear to be in nonconfor.
t 7, )
mance with statements in your Final Safety Analysis Report, as identified below:
1 ' '.
' l.
Appendix 1.B.l.15 of the Final Safety Analysis Report and your Quality Assurance Procedure Number 17 require that all departures (with the exception of minor rework within n short period of time) from drawing, specification or procedure requiremencs must be documented on a Nonconforming Report and properly dispositioned.
i 4
i s
1 Contrary to the above requiremonen, departures from electrical cable routing and termination specifications that were identified by your
.I
,, Management Inspector were not being documented on Nonconforming Reports.