ML19318C218

From kanterella
Jump to navigation Jump to search
Forwards IE Info Notice 80-23, Loss of Suction to Emergency Feedwater Pumps. No Written Response Required
ML19318C218
Person / Time
Site: Hatch, Vogtle  
Issue date: 05/29/1980
From: James O'Reilly
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION II)
To: John Miller
GEORGIA POWER CO.
References
NUDOCS 8007010220
Download: ML19318C218 (1)


Text

._

f e

a ta

' UNITED STATES NUCLEAR REGULATORY COMMISSION n

a$

REGION 11 o

101 MARIETTA ST., N.W., SUITE 3100 l

lll e

ATLANTA, GEORGIA 30303 In Reply Refer To:

MAY 291980 RII:JPO~

Q321,5d'366',

5024W50242F Georgia Power Company Attn:

J. H. Miller, Jr.

Executive Vice President 270 Peachtree Street, N.W.

Atlanta, GA 30303 Gentlemen:

~~

This Information Notice is forwarded for information. No written response to this Information Notice is required.

If you have any questions related to this matter, please contact this office.

Sincerely, O

t J es P. O'Reilly

)

Di ctor

Enclosures:

1.

IE Information Notice No. 80-23 2.

List of Recently Issued IE.information Notices l

l s

8007010$QC

i MAY 2'91900 Georgia Power Company,

cc w/ encl:

M. Maury, Plant Manager Post Office Box 442 Baxley, Georgia 31513 C. E. Belflower Site QA Supervisor Post Office Box 442 Baxley, Georgia 31513 K. M. Gillespie Construction Project Manager Post Office Box 282 Waynesboro, Georgia 30830 E. D. Groover QA Site Supervisor Post Office Box 282 Waynesboro, Georgia 30830 W. A. Widner, General Manager Nuclear Generation Georgia Power Company Post Office Box 4545 4

Atlanta, Georgia 30303 I

O h

a o

e -,ee

,we e-==

g Om ao gen

.e

,'., swmm e e+s.wo%

  • ~

'*'**~'*~**~****'~~'#'**~~~~~

UNITED STATES SSINS No.: 6835 NUCLEAR EEGULATORY COMMISSION Accession No.:

OFFICE OF INSPECTION AND ENFORCEMENT 8005050061 WASHINGTON, D. C.

20555 h O_ '

May 29,19f')

g IE Information Notice No. 80-23 LOSS OF SUCTION TO EMERGENCY FEEDWATER PUMPS Description of Circumstances:

On April 7, 1980, Arkansas Nuclear One, Unit 2, suffered a loss of offsite power due to tornado damage to 500 kv transm.ssion towers. The unit tripped from 98%

power; the diesel generators started and supplied vital loads; natural circula-tion in the reactor coolant system was established; and the emergency feedwater (EFW) pumps supplied feedwater to the steam generators.

The suction of the EFW pumps was aligned to the Condensate Storage Tanks (CST) and to the Startup and Blowdown Demineralizer effluent in parallel. Approxi-mately 15 minutes after the unit tripped, both EFW pumps lost suction. Prompt operator action was taken to isolate the EFW pump suction from the Startup and Blowdown Demineralizer and to vent the EFW pumps. EFW flow was reestablished within one minute.

Investigation revealed that the EFW pump suction loss was caused by flashing in the main feedwater train forcing hot water through the Startup and Blowdown Demineralizers to the EFW pump suction where it flashed to steam. The steam caused cavitation of the EFW pumps, and the pressure in the EFW suction header prevented flow from the CST.

The licensee has submitted Licensee Event Report No. 50-368/80-18/03L-0, dated May 5, 1980, describing this event. Action to prevent recurrence included revising the EFW system operating procedure and the Plant Startup Procedure to require shutting the EFW suction valve from the Startup and Blowdown Demineralizers during plant startup at about 5% full power after the steam generator feedwater source has been shifted to a main feedwater pump.

In addition, the EFW suction valve from the Startup and Blowdown Demineralizers will be verified closed once per shift during Mode 1 operation.

This IE Information Notice is provided as an early notification of a possibly significant matter that is still under review by the NRC staff.

It is expected that recipients will review the information for possible applicability to their facilities. No specific action or response is requested at this time.

If NRC evaluations so indicate, further licensee actions may be requested or required.

No written response to this IE Information Notice is required.

If you have any questions regarding this matter, please contact the Director of the appropriate NRC Regional Office.

?

IE Information Notice No. 80-23 Enclosure May 29, 1980 RECENTLY ISSUED IE INFORMATJ1N NOTICES Information Subject Date Issued To Notice No.

Issued 80-23 Loss of Suction to Emergency 5/29/80 All power reactor Feedwater Pumps facilities with an '

OL or CP 80-22 Breakdown In Contamination 5/28/80 All power reactor Control Programs OLs and near term cps 80-21 Anchorage and Support of 5/16/80 All power reactor Safety-Related Electrical facilities with an Equipment OL or CP 80-20 Loss of Decay Heat Removal 5/8/80 All light water reactor Capability at Davis-Besse facilities holding Unit 1 While in a Refueling pow'r reactor OLs or cps Mode t

80-19 NIOSH Recall of Recircu-5/6/80 All holders of a power lating-Mode (Closed-Circuit) reactor OL, Research Self-Contained Breathing Reactor License, Fuel Apparatus (Rebreathers)

Cycle Facility License and Priority I Material License 80-18 Possible Weapons Smuggling 5/5/80 All power reactor Pouch facilities with an OL, fuel fabrication and processing facilities and Materials Priority I licensees (processors and distributors) 80-17 Potential Hazards Associated 5/5/80 All radiography With Interchangable Parts Licenses On Radiographic Equipment 80-16 Shaft Seal Packing 4/29/80 All power reactor Causes Binding In Main facilities in your Steam Swing Check And Region with an OL or CP Isolation Valves 80-15 Axial (Longitudinal) 4/21/80 All Light Water Reactor Oriented Cracking In Facilities holding power Piping reactor OLs or cps