05000339/LER-1980-020-03, /03L-0:on 800529,during Mode 3 condition,72-h Periodic Test of Containment Personnel Hatch Was Not Accomplished Due to Failure of Doors to Close.Caused by Failure of Limit Switch on Inner Door.Switch Replaced

From kanterella
(Redirected from ML19318A604)
Jump to navigation Jump to search
/03L-0:on 800529,during Mode 3 condition,72-h Periodic Test of Containment Personnel Hatch Was Not Accomplished Due to Failure of Doors to Close.Caused by Failure of Limit Switch on Inner Door.Switch Replaced
ML19318A604
Person / Time
Site: North Anna 
Issue date: 06/18/1980
From: Cartwright W
VIRGINIA POWER (VIRGINIA ELECTRIC & POWER CO.)
To:
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION II)
Shared Package
ML19318A601 List:
References
LER-80-020-03L-01, LER-80-20-3L-1, NUDOCS 8006230447
Download: ML19318A604 (2)


LER-1980-020, /03L-0:on 800529,during Mode 3 condition,72-h Periodic Test of Containment Personnel Hatch Was Not Accomplished Due to Failure of Doors to Close.Caused by Failure of Limit Switch on Inner Door.Switch Replaced
Event date:
Report date:
3391980020R03 - NRC Website

text

~

U.S. NUCLEAR REGULATORY COMMISSION LICENSEE EVENT REPORT CONTROL BLOCK / / / / / / / (1)

(PLEASE PRINT OR TYPE ALL REQUIRED INFORMATION)

/0/1/

/V/A/N/A/S/2/ (2)

/0/0/-/0/0/0/0/0/-/0/0/ (3)

/4/1/1/1/1 (4)

/ / / (5)

LICENSEE CODE LICENSE NUMBER LICENSE TYPE CAT

/0/1/

RE [L[ (6)

/0/5/0/0/0/3/3/9/

(7)

/0/5/2/9/8/0/

(8)

/0/6/1/8/8/0 (9)

OU DOCKET NUMBER EVENT DATE REPORT DATE EVENT DESCRIPTION AND PROBABLE CONSEQUENCES (10)

/0/2/

/

On May 29, 1980, the 72 hour8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br /> periodic test of the containment personnel hatch /

/0/3/

/

was not accomplished due to the failure of the limit switches governing the

/

/0/4/

/

opening and closing of the doors.

The unit was in Mode 3 condition and the

/

/0/5/

/

doors closed, therefore the health and safety of the public was not affected.

/

/0/6/

/

This item is reportable pursuant to T.S. 6.9.1.9.c.

/

/0/7/

/

/

/0/8/

/

/

SYSTEM

CAUSE

CAUSE COMP.

VALVE CODE CODE SUBCODE COMPONENT CODE SUBCODE SUBCODE

/0/9/

/S/A/ (11)

/E/ (12)

/A/ (13) /P/E/N/E/T/R/ (14)

/A/ (15)

/Z/ (16)

SEQUENTIAL OCCURRENCE REPORT REVISION LER/RC EVENT YEAR REPORT NO.

CODE TYPE NO.

(17) REPORT NUMBER

/8/0/

/-/ /0/2/0/

/\\/

/0/3/

/L/

/-/

[0/

ACTION FUTURE EFFECT SHUTDOWN ATTACHMENT NPRD-4 PRIME COMP.

COMPONENT TAKEN ACTION ON PLANT METHOD HOURS SUBMITTED FORM SUB. SUPPLIER MANUFACTURER

/A/ (18) /X/ (19)

/Z/ (20)

/Z/ (21) /0/0/0/0/ (22) [Y/ (23)

/N/ (24) /A/ (25) /C/3/1/0/ (26)

CAUSE DESCRIPTION AND CORRECTIVE ACTIONS (27)

/1/0/

/

The personnel hatch doors would not operate due to the failure of the limit

/

/1/1/

/

switch on the inner door. The limit switch was replaced.

The periodic test

/

/1/2/

/

(PT 62.4) was performed to prove operability of the personnel access hatch.

/

/1/3/

/

/

/1/4/

/

/

FACILITY METHOD OF STATUS

% POWER OTHER STATUS

/ (30) DISCOVERY DISCOVERY DESCRIPTION (32)

/1/5/

/B/ (28)

/0/0/0/ (29) /

NA

/A/ (31)

/ OPERATOR OBSERVATION /

ACTIVITY CONTENT RELEASED OF RELEASE AMOUNT OF ACTIVITY (35)

LOCATION OF RELEASE (36)

/1/6/

/Z/ (33)

/Z/ (34)

/

NA

/

/

NA

__/

PERSONNEL EXPOSURES KUMBER TYPE DESCRIPTION (39)

/1/7/ /0/0/0/ (37) /2/ (38)

/

NA

/

PERSONNEL INJURIES NUMBER DESCRIPTION (41)

/1/8/ /0/0/0/ (40) /

NA

/

LOSS OF OR DAMAGE TO FACILITY (43)

TYPE

DESCRIPTION

/1/9/

/Z/ (42)

/

NA

/

PUBLICITY ISSUED DESCRIPTION (45)

NRC USE ONLY

/2/0/

/N/ (44)

/

NA

/////////////

8 0 0 6 2 3 0(p0F PREPARER W. R. CARTWRIGHT PHONE (703) 894-5151

Virg' inia Electric'and Power Company North Anna Power Station, Unit #2

Attachment:

Page 1 of 1 Docket No. 50-339 Report No. LER 80-020/03L-0

Description of Event

On May 29, 1980 during Mode 3 operation, the containment personnel access hatch doors'would not open, therefore PT 62.4 could not be per-formed.

the inability to open the hatch door was due to the failure of a limit switch on the inner door.

Probable Consequences of Occurrence Since the unit was in Mode 3 cond. tion and the containment hatch doors remained closed, the health and safety of the public were not affected by this occurrence.

Cause of Event

The event was caused by the failure of a limit switch on the hatch inner door preventing the electro-hydraulic system from moving the door to the open position.

Immediate Corrective Action

The-failed limit switch was replaced.

Scheduled Corrective Action The periodic test (PT 62.4) was performed to demonstrate operability of the hatch doors.

Actions Taken to Prevent Recurrence No further action required.