INSTRUMENTATION FIRE DETECTION LIMITING CONDITION FOR OPERATION 3.3.3.8 As a minimum, the fire detection instrumentation for each fire detection zone shown in Table 3.3-8 shall be OPERABLE.

APPLICABILITY: At all times when equipment in that fire detection zone is required to be OPERABLE.

ACTION:

With the number of OPERABLE fire detection instruments less than required by Table 3.3-8; 1.

Within 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br />, establish a fire watch patrol to inspect the zone with the inoperable instrument (s) at least once per hour, and 2.

Restore the inoperable instrument (s) to OPERABLE status within 14 days or prepare and submit a special report to the Comis-sion pursuant to Specification 6.9.2 within the next 10 days outlining the cause of the malfunction and the plans for restoring the instrument (s) to OPERABLE status.

3.

The provisions of Specifications 3.0.3 and 3.0.4 are not applicable.

SURVEILLANCE REQUIREMENTS 4.3.3.8.1 Each of the above fire detection instruments shall be demcn-strated OPERABLE:

a.

At least once pe 6 months by a CHANNEL FUNCTIONAL TEST, and b.

At least once per 12 months by performance of a Channel Calibration.

4.3.3.8.2 The circui'.ry associated with the detector alarms shall be demonstrated OPERABLE at least once per 62 days for all NFPA Code 72D Class A supervised circu'ts.

ALL STS MAY 121977 912130 7

TABLE 3.3-8 FIRE DETECTION INSTRUMENTS INSTRUMENT LOCATION (Illustrative)*

MINIMUM INSTRUMENTS OPERABLE HEAT SMOKE 1.

Containment Zone 1 Elevation Zone 2 Elevation 2.

Control Room 3.

Cable Spreading Zone 1 Elevation Zone 2 Elevation 4.

Computer Room 5.

Switchgear Room 6.

Remote Shutdown Panels 7.

Station Battery Rooms Zone 1 Elevation Zone 2 Elevation 8.

Turbine Zone 1 Elevation Zone 2 Elevation 9.

Diesel Generator Zone 1 Elevation Zone 2 Elevation

~

10. Diesel Fuel Storage

~

11. Safety Related Pumps Zone 1 Elevation Zone 2 Elevation
12. Fuel Storage Zone 1 Elevation Zone 2 Elevaticn
  • List all detectors protecting. safety related equipment or located in areas which contain potential fire hazards to safety related equipment.

Ad SIS MAY 121977

P PLANT SYSTDKS FIRE SUPPRESSION WATER SYSTEM LIMITING CONDITION FOR OPERATION 3.7.11.1 The FIRE SUPPRESSION WATER SYSTEM shall be OPERABLE with; (2) high pressure pumps each with a capacity of gpm.

a.

with their discharge aligned to the fire suppression header.

b.

Separate water supplies each containing a minimum of gallons.

1 c.

Automatic initiation logic for each fire pump.

APPLICABILITY: At all times.

ACTION:

a.

With less than the above required equipnent, restore the inoperable equipment to OPERABLE status within 7 days or prepare and submit a Special Report to the Connission pursuant to Specifi-cation 6.9.2 within the next 10 days outlining the plans and procedures to be used to provide for the loss of redundancy in this systen.

b.

With no FIRE SUPPRESSION WATER SYSTEM OPERABLE,within 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br />; 1.

Establish a backup FIRE SUPPRESSION WATER SYSTEM.

2.

Notify the Commission hursuant to Sepcification 6.9.2 outlining the actions taken and the plans and schedule for restoring the system to OPERABLE status, c.

Restore the FIRE SUPPRESSION WATER SYSTEM to OPERABLE status within 14 days or prepare and submit a Special Report to the Commission pursuant to Specificatidn 6.9.2 within the next 10 days outlining the cause of the malfunction and the plans for restoring the system to OPERABLE status.

AL STS MAY 121977 O $

et

PLANT SYSTEMS WATER SYSTEM SURVEILLANCE REQUIREMENTS (Continued) 4.7.11.1 The FIRE SUPPRESSION WATER SYSTEM shall be demonstrated OPERABLE:

a.

At least once per 7 days by verifying the water supply volume.

b.

At least once per 31 days on a STAGGERED TEST BASIS by starting each pump and operating it for at least 15 minutes on recircu-lation flow.

c.

At least once per 92 days by cycling each testable valve through one complete cycle.

~

d.

(At least once per 6 months by performance of a system flush if required by local water conditions).

e.

At least once per 18 months:

1.

By performing a system functional test which includes simulated automatic actuation of th' system throughout e

its operating sequence and verifying that each automatic valve in the flow path actuates to its correct position.

2.

By verifying that each pump develops at least (2500) gpm at a system head of (250) feet, f.

At least once per 3 years by performing flow tests of the system in accordance with Chapter 5, Section 11 of Fire Protection Handbook,14th Edition published by National Fire Protection Association.

ALL STS MAY 121977

PLANT SYSTEMS SPRAY AND/OR SPRINKLER SYSTEMS LIMITING CONDITION FOR OPERATION 3.7.11.2 The following spray and/or sprinkler systems located in the following areas shall be OPERABLE:

(Plant dependent - to be listed by name and location.)

a.

b.

C.

j APPLICABILITY: At all times when equipment in the area is re' quired to be OPERABLE.

ACTION:

a.

With a spray and/or sprinkler system inoperable establish a continuous fire watch with backup fire suppression equipment for the unprotected area (s), within 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br />, b.

Restore the system to OPERABLE status within 14 days or pre-1 pare and submit a Special Report to the Commission pursuant to Specification 6.9.2 within the next 10 days outlining the cause of inoperability and the plans for restoring the system to OPERABLE status.

SURVEILLANCE REQUIREMENTS l

4.7.11.2 The spray and/or sprinkler systems shall be demonstrated to be OPERABLE:

a.

At least once per 92 days by cyqling each testable valve through one complete cycle.

b.

At least once per 18 months:

1.

By performing a system functional test which includes simulated automatic actuation of the system and verify-ing that the automatic valves in the flow path actuate to their correct positions.

1 2.

By inspection of spray headers to verify their integrity.

ALL STS MAY 121977

\\

PLANT SYSTEMS SPRAY AND/0R SPRINKLER SYSTEMS SURVEILLANCE REQUIREMENTS (Continued) 3.

By inspection of each nozzle to verify no blockage.

c.

At least once per 3 years by performing an air flow test through each spray / sprinkler header and verifying each spray /

sprinkler nozzle is unobstructed.

ALL STS MAY 121977 m

<,-w-m

=-

-9

i l

PLANT SYSTEMS CO SYSTEM 2

LIMITING CONDITION FOR OPERATION 3.7.11.3 The following CO2 systems shall be OPERABLE with a minimum level of and a minimum pressure of in the associated storage tank (s).

a.

(Plant dependent - to be listed by name and location.)

b.

c.

APPLICABILITY: At all times when the equipment in the area is required to be OPERABLE.

ACTION:

a.

With a CO2 system inoperable, establish a continuous fire watch with backup fire suppression equipment for the unpro-tected area (s), within 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br />.

b.

Restore the system to OPERABLE status within 14 days or pre-pare >"? submit a Special Report to the Commission pursuant to Spe*' 4:t tion 6.9.2 within the next 10 days outlining the ca-

' inoperability and the plans for restoring the system to srERABLE status.

SURVEILLANCE REQUIREMENTS 4.7.11.3 The CO system sha,ll be demonstrated OPERABLE:

2 a.

At least once per 7 days by verifying each CO storage tank 2

level and pressure.

b.

At least once per 18 months by verifying the system valves and associated ventilation dampers actuate automatically and manually to a simulated actuation signal. A brief flow test shall be made to verify flow from each nozzle.

(" Puff Test").

ALL STS MAY 12 tg77

PLANT SYSTEMS HALON SYSTEM LIMITINGCONDITIONFOROPERATIbN 3.7.11.4 The following Halon systems shall be OPERABLE with the storage tanks having at least 95% of full charge weight and 90% of full charge

pressure, a.

(Plant dependent - to be listed by name and location.)

b.

c.

APPLICABILITY: At all times when the equipment in the area is required to be OPERABLE.

ACTION:

a.

With a Halon system inoperable establish a continuous fire watch with backup fire suppression equipment for the unpro-tected area (s), within 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br />.

b.

Restore the system to OPERABLE status within 14 days or pre-pare and subm;t a Special Report to the Commission pursuant to Specification 6.0.2 within the next 10 days outlining the cause of inoperability 3nd the plans for restoring the system to OPERABLE status.

SURVEILLANCE REQUIREMENTS 4.7.11.4 The Halon system shall be demonstrated OPERABLE:

a.

At least once per 3 months by verifying each Halon storage tank weight and pressure.

b.

At least once per 18 months by:

1.

Verifying the system, including associa*ed ventilation dampers, actuates automatically to a sk.'sted test signal.

2.

Performance of a flow test through headers and rozzles to assure no blQckage.

ALL STS MAY 121977

PLANT SYSTEMS HALON SYSTEM SURVEILLANCE REQUIREMENTS (Continued) 3.

Verifying the OPERABILITY of the manual initiating system.

1 ij ALL STS l

MAY 121977

.~

l

PLANT SYSTEMS FIRE HOSE STATIONS LIMITING CONDITIONS FOR OPERATION 3.7.11.5 The following fire hose stations shall be OPERABLE:

1.

(Plant dependent - to be listed by location and size.)

2.

3.

APPLICABILITY: At all times when the equipment in the area is required to be OPERABLE.

ACTION:

With a hose station inoperable, route an additional equivalent capacity hose to the unprotected area from an OPERABLE hose station within I hour.

SURVEILLANCE REQUIREMENTS e

4.7.11.5 Each fire hose station shall be verified OPERABLE:

a.

At least once per 31 days by visual inspection of the station to assure all equipment is available and the pressure in the standpipe is within limits.

b.

At least once per 18 months by removing the hose for inspection and re-racking and replacing all gaskets in the couplings that are degraded.

c.

At least once per 3 years, partially open each hose station valve to verify valve operability and no blockage.

ALL STS NAY 121977

I i

l l

i l

l PLANT SYSTEMS FIRE BARRIFR PENETRATION FIRE SEALS LIMITING CONDITIONS FOR OPERATION 3.7.12 All penetration fire barriers protecting safety related areas shall be functional.

APPLICABILITY: At all times.

ACTION:

a.

With a penetration fire barrier non-functional, a continuous fire watch shall be established on at least one side of the affected penetration within 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br />.

b.

The provisions of 3.0.3 and 3.0.4 are not applicable.

SURVEILLANCE REQUIREMENTS 4.7.12.1 Penetration fire barriers shall be verified to be functional by a visual inspection; a.

At least once per 18 months, and b.

Prior to declaring a fire penetration seal functional following repairs or maintenance.

4.7.12.2 Penetration fire barriers that perform a pressure sealing function shall be verified to be functional by performarce of a local leakage test prior to declaring a penetration fire barrier functional following repairs or maintenance.

l ALL STS IRAY 121977

The following items should be added to the appropriate indicated sections of the Technical Specifications.

DEFINITIONS:

" FIRE SUPPRESSION WATER SYSTEM:

1.27 A FIRE SUPPRESSION WATER SYSTEM shall consist of: a water source (s);

gravity tank (s) or pump (s); and distribution piping with associated sectionalizing control or isolation valves. Such valves shall include yard hydrant curb valves, and the f'irst valve ahead of the water flow alarm device on each sprinkler, hose standpipe or spray system riser."

AD11NISTRATION CONTROLS 6.2.2.f.

A Fire Brigade of at least members shall be maintained onsite at all times. This excludes members of the minimum shift crew nec-essary for safe shutdown of the plant and any personnel required for other essential functions during a fire energency.

Figures 6.2-1 and 6.2-2 Add provisions to include the organizational arrangement for performance and monitoring of the Fire Protection Program.

6.4.2 A training program for the Fire Brigade shall be maintained under the direction of the (Fire Protection Program Manager) and shall meet or exceed the requirements of Section 27 of the NFPA Code-1976.

6.5.2.8.i The Facility Fire Protection Program and implementing pro-cedures at least once per 24 months.

6.5.2.8.j An independent fire protection and loss prevention inspection and audit shall be performed annually utilizing either qualified offsite licensee personnel or an ou,tside fire protection firm.

6.5.2.8.k An inspection and audit of the fire protection and loss prevention program shall be performed by an outside qualified fire con-sultant at intervals no greater than 3 years.

6.8.1.f Fire Protection Program implementation.

ALL STS g@y 12107 r

I BASES 3/4.3.3.8 FIRE DETECTION INSTRUMENTATION' l

OPERABILITY of the fire detection instrumentation ensures that ddequate WUning Capability is available for the prompt detection of fires. Tht!. capability is required in order to detect and locate fires in their early stages. Prompt detection of fires will reduce the poten-tial for danage to safety related equipment and is an integral element in the overall facility fire protection program.

In t'ie event that a portion of the fire detection instrumentation is inoperable, the establishment of frequent fire patrols in the affected areas is required to provide detection capability until the inoperable instrumentation is returned to service.

3/4.7.11 FIRE SUPPRESSION SYSTEMS The OPERABILITY of the fire suppression systems ensures that ade-quate fire suppression capability is available to confine and extinguish fires occurring in any portion of the facility where safety related equipment is located. The fire suppression system consists of the water system, spray and/or sprinklers, C0, Halon and fire hose stations. The 7

collective capability of the fire suppression systems is adequate to minimize potential damage to safety related equipment and is a major element in the facility fire protection prograrn.

In the event that portions of the fire suppression systems are 1

inoperable, alternate backup fire fighting equipment is required to be made available in the affected areas until the affected equipment can be restored to service.

In the event that the. fire suppression water system becomes in-operable, innediate corrective measures must ce taken since this system provides the major fire suppression capability of the plant. The requirement for a twenty-four hour report to the Coanission provides for prompt evaluation of the acceptability of the corrective measures to provide adequate fire suppression capability for the continued pro-tection of the nuclear plant.

ALL-STS 14AY 2 51977

BASES (Continued) 3/4.7.12 FIRE BARRIER PENETRATION SEALS The functional integrity of the fire barrier penetration seals ensures that fires will be confined or adequately retarded from spreading to adjacent portions of the facility. This design feature minimizes the possibility of a single fire rapidly involving several areas of the facility prior to detection and extinguishment. The fire barrier pene-tration seals are a passive element in the facility fire protection program and are subject to periodic inspections.

During periods of time when the seals are not functional, a con-tinuous fire watch is required to be maintained in the vicinity of the affected seal until the seal is restored to functional status.

ALL-STS liAY 2 51977

.