ML19305B654

From kanterella
Jump to navigation Jump to search
Notice of Violation from Insp on 791218-20 & 800115-18
ML19305B654
Person / Time
Site: Comanche Peak  
Issue date: 01/28/1980
From:
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION IV)
To:
Shared Package
ML19305B649 List:
References
50-445-79-31, 50-446-79-29, NUDOCS 8003200036
Download: ML19305B654 (1)


Text

b 50-445/79-31 50-446/79-29 Appendix A NOTICE OF VIOLATION Based on the results of the NRC inspection conducted on December 18-20, 1979, and January 15-18, 1980, it appears that certain of your activities were not conducted in full compliance with the conditions of your NRC Construction Permit No. CPPR 126 as indicated below:

Failure to Follow Welding Procedures 10 CFR Part 50, Appendix B, Criterion V requires that established instructions, procedures, or drawings be followed for all activities affecting quality.

Brown and Root Weld Procedure Specification 88023, Revision 8, Interim Change Notice 1 requires that type 316 weld material be used when welding type 316 base material to type 304 base material.

Contrary to the above:

The IE inspector observed, on January 15, 1980, that type 308 weld material was being used to tack weld type 316 base material to type 304 base material for a Class 1 socket weld, identified as FW-13 on Drawing 3RP-SI-1-RB-025, Revision 1.

This is an infraction.

4 AW