Notice of Deviation from Insp on 791126-29
ML19305B447
Person / Time
Site: Crystal River 
Issue date: 12/28/1979
From:
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION II)
To:
Shared Package
ML19305B439 List:
References
50-302-79-52, NUDOCS 8003190668
Download: ML19305B447 (1)


Text

.-

5,

^ (-

/#

APPENDIX A 4

NOTICE OF DEVIATION Florida Power Corporation License No. DPR-72 Crystal River 3 Based on the results of the NRC inspection conducted on November 26-29, 1979, certain of your activities app 2ar to deviate from applicable codes, guides, or standards approved by the Commission as indicated below.

Branch Technical Position APCSB 9.5-1, Appendix A, Section C.6 requires in part that " Fire extinguishers should be provided in accordance with guide-lines of NFPA 10 and 10A, " Portable Fire Extinguishers, Maintenance and Use."

The Fire Protection Program Review, Crystal River Unit 3, dated June 1979 and submitted to the NRC states in part in Section 6.E.6 that "the (above) requirement is met.

Fire extinguishers are provided in accordance with NFPA 10."

Contrary to the above, surveillance procedures for portable fire extinguishers SP-800, revision 3 and SP-801, revision 1 do not reference NFPA-10 or the inspection and maintenance sections therein and do not contain all of the checks and acceptance criteria used in NFPA 10.