ND-19-1324, Unit 4 - Notice of Uncompleted ITAAC 225-days Prior to Initial Fuel Load Item 2.7.06.03.1 (Index Number 726)
| ML19304C243 | |
| Person / Time | |
|---|---|
| Site: | Vogtle |
| Issue date: | 10/29/2019 |
| From: | Yox M Southern Nuclear Operating Co |
| To: | Document Control Desk, Office of Nuclear Reactor Regulation |
| References | |
| ND-19-1324 | |
| Download: ML19304C243 (9) | |
Text
Southern Nuclear OCT 2 9 2019 Michael J. Yox Regulatory Affairs Director Vogtie 3 & 4 7825 River Road Waynesboro, GA 30830 706-848-6459 tel Docket Nos.:
52-025 52-026 U.S. Nuclear Regulatory Commission Document Control Desk Washington, DC 20555-0001 ND-19-1324 10 CFR 52.99(c)(3)
Southern Nuclear Operating Company Vogtie Electric Generating Plant Unit 3 and Unit 4 Notice of Uncompleted ITAAC 225-davs Prior to Initial Fuel Load Item 2.7.06.03.1 (Index Number 7261 Ladies and Gentlemen:
Pursuant to 10 CFR 52.99(c)(3), Southern Nuclear Operating Company hereby notifies the NRC that as of October 25, 2019, Vogtie Electric Generating Plant (VEGP) Unit 3 and Unit 4 Uncompleted Inspections, Tests, Analyses, and Acceptance Criteria (ITAAC) Item 2.7.06.03.1
[Index Number 726] has not been completed greater than 225-days prior to initial fuel load. The Enclosure describes the plan for completing this ITAAC. Southern Nuclear Operating Company will, at a later date, provide additional notifications for ITAAC that have not been completed 225-days prior to initial fuel load.
This notification is informed by the guidance described in NEI-08-01, Industry Guideline for the ITAAC Closure Process Under 10 CFR Part 52, which was endorsed by the NRC in Regulatory Guide 1.215. In accordance with NEI 08-01, this notification includes ITAAC for which required inspections, tests, or analyses have not been performed or have been only partially completed.
All ITAAC will be fully completed and all Section 52.99(c)(1) ITAAC Closure Notifications will be submitted to NRC to support the Commission finding that all acceptance criteria are met prior to plant operation, as required by 10 CFR 52.103(g).
This letter contains no new NRC regulatory commitments.
If there are any questions, please contact Tom Petrak at 706-848-1575.
Respectfully submitted.
CUn-Michael J. Yox Regulatory Affairs Director Vogtie 3 & 4
Enclosure:
Vogtie Electric Generating Plant (VEGP) Unit 3 and Unit 4 Completion Plan for Uncompleted ITAAC 2.7.06.03.1 [Index Number 726]
MJY/DLW/sfr
U.S. Nuclear Regulatory Commission ND-19-1324 Page 2 of 3 To:
Southern Nuclear Operating Company/ Georgia Power Company Mr. Peter P. Sena III (w/o enclosures)
Mr. D. L. McKinney (w/o enclosures)
Mr. M. D. Meier (w/o enclosures)
Mr. D. H. Jones (w/o enclosures)
Mr. G. Chick Mr. M. Page Mr. M. J. Yox Mr. A. S. Parton Ms. K. A. Roberts Mr. T. G. Petrak Mr. C. T. Defnall Mr. C. E. Morrow Mr. J. L. Hughes Mr. S. Leighty Ms. A. C. Chamberlain Mr. J. C. Haswell Document Services RTYPE: VND.LI.L06 File AR.01.02.06 cc:
Nuclear Regulatory Commission Mr. W. Jones (w/o enclosures)
Mr. F. D. Brown Mr. C. P. Patel Mr. G. J. Khouri Ms. S. E. Temple Mr. N. D. Karlovich Mr. A. Lerch Mr. C. J. Even Mr. B. J. Kemker Ms. N. C. Coovert Mr. C. Welch Mr. J. Gaslevic Mr. V. Hall Mr. G. Armstrong Ms. T. Lamb Mr. M. Webb Mr. T. Fredette Mr. C. Weber Mr. S. Smith Qqlethorpe Power Corporation Mr. R. B. Brinkman Mr. E. Rasmussen
U.S. Nuclear Regulatory Commission ND-19-1324 Page 3 of 3 Municipal Electric Authority of Georgia Mr. J. E. Fuller Mr. 8. M. Jackson Dalton Utilities Mr. T. Bundros Westinqhouse Electric Company. LLC Dr. L. Orlani (w/o enclosures)
Mr. D. 0. Durham (w/o enclosures)
Mr. M. M. Corletti Ms. L. G. Iller Mr. Z. 8. Harper Mr. J. L. Coward Other Mr. J. E. Hosier, Bechtel Power Corporation Ms. L. Matis, Tetra Tech NU8, Inc.
Dr. W. R. Jacobs, Jr., Ph.D., GD8 Associates, Inc.
Mr. 8. Roetger, Georgia Public Service Commission Ms. 8. W. Kernizan, Georgia Public Service Commission Mr. K. C. Greene, Troutman Sanders Mr. 8. Blanton, Balch Bingham
U.S. Nuclear Regulatory Commission ND-19-1324 Enclosure Page 1 of 6 Southern Nuclear Operating Company ND-19-1324 Enclosure Vogtle Electric Generating Plant (VEGP) Unit 3 and Unit 4 Completion Plan for Uncompleted ITAAC 2.7.06.03.1 [Index Number 726]
U.S. Nuclear Regulatory Commission ND-19-1324 Enclosure Page 2 of 6 ITAAC Statement Design Commitment
- 3. The VPS provides the Intermittent flow of outdoor air to purge the containment atmosphere during normal plant operation, and continuous flow during hot or cold plant shutdown conditions.
- 4. Controls exist in the MCR to cause the components identified in Table 2.7.6-1 to perform the listed function.
- 5. Displays of the parameters identified in Table 2.7.6-1 can be retrieved in the MCR.
Inspections/T ests/Analvses i) Testing will be performed to confirm that containment supply AHU fan A when operated with containment exhaust fan A provides a flow of outdoor air.
ii) Testing will be performed to confirm that containment supply AHU fan B when operated with containment exhaust fan 8 provides a flow of outdoor air.
iii) Inspection will be conducted of the containment purge discharge line (VFS-L204) penetrating the containment.
Testing will be performed on the components in Table 2.7.6-1 using controls in the MCR.
Inspection will be performed for retrievability of the parameters in the MCR.
Acceptance Criteria i) The flow rate measured at each fan is greater than or equal to 3,600 scfm.
ii) The flow rate measured at each fan is greater than or equal to 3,600 scfm.
iii) The nominal line size is ^ 36 in.
Controls in the MCR operate to cause the components listed in Table 2.7.6-1 to perform the listed functions.
The displays identified in Table 2.7.6-1 can be retrieved in the MCR.
ITAAC Completion Description Testing and inspections are performed in accordance with Unit 3 and Unit 4 preoperational tests (References 1 and 2), Unit 3 and 4 ITAAC Technical Report (References 3 and 4), and Unit 3 and Unit 4 component test packages (References 5 and 6) to confirm the Containment Air Filtration System (VFS) provides the intermittent flow of outdoor air to purge the containment atmosphere during normal plant operation, and continuous flow during hot or cold plant
U.S. Nuclear Regulatory Comnnission ND-19-1324 Enclosure Page 3 of 6 shutdown conditions, that controls exist in the Main Control Room (MGR) to cause the components identified in Combined License (COL) Appendix C Table 2.7.6-1 to perform the listed function, and displays of the parameters identified in COL Appendix C Table 2.7.6-1 can be retrieved in the MGR.
i) The flow rate measured at each fan is greater than or eouai to 3.600 scfm Testing is performed in accordance with Unit 3 and Unit 4 preoperationai test procedures (References 1 and 2). The test is conducted by running containment supply fan A (VFS-MA-01 A) and containment exhaust fan A (VFS-MA-02A) and measuring airflow for each fan. The measured airflow readings are corrected for instrument accuracy and for standard conditions.
The corrected airflow is compared to the acceptance criteria and verified to exceed the minimum flow.
The Unit 3 A containment supply fan produced a minimum flow of XXXX scfm and the Unit 3 A containment exhaust fan produced a minimum flow of YYYY scfm during testing. The Unit 4 A containment supply fan produced a minimum flow of XXXX scfm and the Unit 4 A containment exhaust fan produced a minimum flow of YYYY scfm during testing.
The Unit 3 and Unit 4 preoperationai test results (References 1 and 2) confirm that each VFS A containment supply fan and containment exhaust fan produces a flow rate measured at each fan that is greater than or equal to 3,600 scfm.
ii) The flow rate measured at each fan is greater than or eoual to 3.600 scfm.
Testing is performed in accordance with Unit 3 and Unit 4 preoperationai test procedures (References 1 and 2). The test is conducted by running containment supply fan B (VFS-MA-01B) and containment exhaust fan B (VFS-MA-02B) and measuring airflow for each fan. The measured airflow readings are corrected for instrument accuracy and for standard conditions.
The corrected airflow is compared to the acceptance criteria and verified to exceed the minimum flow.
The Unit 3 B containment supply fan produced a minimum flow of XXXX scfm and the Unit 3 B containment exhaust fan produced a minimum flow of YYYY scfm during testing. The Unit 4 B containment supply fan produced a minimum flow of XXXX scfm and the Unit 4 B containment exhaust fan produced a minimum flow of YYYY scfm during testing.
The Unit 3 and Unit 4 preoperationai test results (References 1 and 2) confirm that each VFS B containment supply fan and containment exhaust fan produces a flow rate measured at each fan that is greater than or equal to 3,600 scfm.
iin The nominal line size is ^ 36 in.
An inspection is conducted of the containment purge discharge line (VFS-L204) penetrating the containment to verify the containment penetration nominal size is s 36 in. The inspection is performed by walking down and visually verifying the containment penetration location and inspecting the Quality Assurance Data Package (QADP). ITAAC Technical Report (ITR)
(References 3 and 4) documents the inspection and the QADP review and document the line size is 36 in.
U.S. Nuclear Regulatory Commission ND-19-1324 Enclosure Page 4 of 6 The Unit 3 and Unit 4 ITRs (References 3 and 4) confirm the nominal line size is s 36 in.
Controls In the MGR operate to cause the components listed In Table 2.7.6-1 to perform the listed functions.
Testing is performed in accordance with Unit 3 and Unit 4 component test procedures (References 5 and 6) to verify that controls in the MCR operate to cause the components listed in Table 2.7.6-1 (Attachment A) to perform the listed functions.
Testing is conducted at an operator work station in Unit 3 and Unit 4 MCR and the VPS train A and B are verified to be in a standby alignment. The containment air handling unit supply fan A is placed in service in accordance with the operating procedure and verified to start and then removed from service in accordance with the operating procedure. This is repeated for the three remaining fans.
This testing confirms that controls in the Unit 3 and Unit 4 MCR operate to cause the components listed in Table 2.7.6-1 to perform the listed functions.
The displays identified in Table 2.7.6-1 can be retrieved in the MCR.
The inspection is performed in accordance with Unit 3 and Unit 4 component test procedures (References 5 and 6) to verify that the displays identified in Table 2.7.6-1 (Attachment B) can be retrieved in the MCR.
The component test is conducted in the MCR at the PLS displays and verifies the displays in Attachment B can be retrieved in the MCR. Each display in Attachment C is located on the PLS displays and verified to indicate properly.
This confirms that all the displays identified in Table 2.7.6-1 can be retrieved in Unit 3 and Unit 4 MCR.
References 1 through 6 are available for NRC inspection as part of ITAAC 2.7.06.03.i Unit 3 and 4 Completion Packages (Reference 7 and 8).
List of ITAAC Findings In accordance with plant procedures for ITAAC completion, Southern Nuclear Operating Company (SNC) performed a review of all findings pertaining to the subject ITAAC and associated corrective actions. This review found there are no relevant ITAAC findings associated with this ITAAC.
References (available for NRC inspection)
- 1. 3-VFS-ITPP-501, "Containment Air Filtration System Preoperational Test Procedure"
- 2. 4-VFS-ITPP-501, "Containment Air Filtration System Preoperational Test Procedure"
- 3. SV3-VFS-ITR-800726, "Dimensions of the Containment Purge Discharge Line"
- 4. SV4-VFS-ITR-800726, "Dimensions of the Containment Purge Discharge Line"
U.S. Nuclear Regulatory Commission ND-19-1324 Enclosure Page 5 of 6
- 5. SNC922131, "Containment Air Filtration System Control and Indication Verifications -
ITAAC; SV3-2.7.06.03.i Items 4 and 5"
- 6. SNCXXXXXX, "Containment Air Filtration System Control and Indication Verifications -
ITAAC: SV4-2.7.06.03.i Items 4 and 5"
- 7. 2.7.06.03.i-U3-CP-Rev0, ITAAC Completion Package
- 8. 2.7.06.03.i-U4-CP-Rev0, ITAAC Completion Package
U.S. Nuclear Regulatory Commission ND-19-1324 Enclosure Page 6 of 6 Attachment A "Excerpt from COL Appendix C Table 2.7.6-1
^Equipment
- Tag No.
- Control Function Containment Air Handling Units (AHU) Supply Fan A VFS-MA-01A Start Containment AHU Supply Fan B VFS-MA-01B Start Containment Exhaust Fan A VFS-MA-02A Start Containment Exhaust Fan B VFS-i\\/iA-02B Start Attachment B "Excerpt from COL Appendix C Table 2.7.6-1
^Equipment
- Tag No.
"Display Containment Air Handling Units (AHU) Supply Fan A VFS-MA-01A Yes (Run Status)
Containment AHU Supply Fan B VFS-MA-01B Yes (Run Status)
Containment AHU Supply Fan A Flow Sensor VFS-012A Yes Containment AHU Supply Fan B Flow Sensor VFS-012B Yes Containment Exhaust Fan A VFS-MA-02A Yes (Run Status)
Containment Exhaust Fan B VFS-MA-02B Yes (Run Status)
Containment Exhaust Fan A Flow Sensor VFS-011A Yes Containment Exhaust Fan B Flow Sensor VFS-011B Yes