ATTACHMENT (0 LICENSE AMENDMENT NO. 68 FACILITY OPERATING LICENSE NO. DPR-57 DOCKET NO. 50-321 Replace the followir:g pages of the Appendix "A" Technical Specifications with the enclosed pages. The revised pages are identified by amendment number and contain vertical lines indicating the araa of change.

Remove Insert 3.13-2 3.13-2 3.13-5 3.13-5 3.13-6 3.13-6 A

7 9 082713 \\ l 2_

TABLE 3.13-1 FIRE DETECTORS MINIMUM OPERABLE BUILDING NUf'BER OF DETECTORS DETECTORS REOUIRED A.1 Control Building El. 112'-0" 1.1 Station Battery Room 1A 2

1 1.2 Station Battery Room 18 2

1 1.3 Corridor and Work Area 15 7

1.4 RPS Vertical Cableway 4

2 A.2 Control Building El. 130'-0" 2.1 Switchgear Rooms lA, iB, (1 in each 1E, IF, and Transformer Rocm 8

room or 5) 2.2 Corridor 7

3 2.3 RPS Vertical Cableway 2

1 2.4 East Cableway 15 7

A.3 Control Building El. 147'-0" 3.1 Switchgear & MCC Area N.W. Corner 7

3 3.2 Switchgear & MCC Area N.E. Corner 4

2 3.3 Cable Spreading Room 50 25 l

A.4 Control Building El. 164'-0" 4.1 Control Room Unit 1 21 10 4.2 Control Rcom Unit 2 15 7

4.3 Peripheral Rooms 10 5

l B.1 Diesel Generator Building 1.1 Switchgear Room 1E 4

2 1.2 Switchgear Room 1F 4

2 1.3 Switchgear Room 1G 4

2 1.4 Battery Rocm 1 A 1

1 1.5 Battery Rocm 1B 1

1 1.6 Battery Rocm IC 1

1 C.1 River Intake Structure 1.1 Building Area 11 5

D.1 Reactor Building El. 130'-0" 1.1 North Cable Tray Area,

? emote Shutdown Area, and North CRD Area 33 16 1.2 Scuth Cable Tray and South CR0 Area 35 17 J.2 Reactor Building El. 158'-0" 2.1 HVAC Rocm 20 10 Arencrent No.

68 3.13-2

3/4.13

" IRE PROTECTION SYSTEMS 3/4.13.3 SPRAY AND/0R SPRINKLER SYSTEMS LIMITING CONDITIONS FOR OPER.. TION 3.13.3 The following spray and/or sorinkler systems located in the following areas shal' be OPEPABLE:

'a.

Turbine Lube Oil Storage b.

Turbine Lube Oil Reservoir c.

RCIC RocM d.

HPCI Room e.

Recirculation Pump Motor Generator Rocm f.

East 7ableway g.

Cable Spreading Room h.

RPS Vertical Cableway 1.

Control Building Corridor (El.130')

j.

Intake Structure k.

Reactor Building HVAC Rocm APPL.ICABILITY: At all times when equipment in the area is required to be OPERASLE.

ACTION:

a.

With a spray and/or sprinkler system inoperable establish a continuous fire watch with backup fire suppression equipment for the unprotected area (s), within 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br />, provided radiation levels permit personnel access.

b.

Restore the system to OPERABLE status within 14 days or pre-pare and submit a Special Report to the Comission within the next 30 days outlining the cause of incoerability and

ne alans for restoring the system to OPERABLE status.

?rencment No.[, 68 3.13-5

3/4.13 FIRE PROTECTI0ft SYSTEMS 3/4.13.3 SPRAY AtiD/OR SPRIrlKLER SYSTEf',

SURVEILLAtlCE REOUIREMEilTS 4.13.3 The spray and/or sprinkler systems shall be demonstrated to be OPERABLE:

'a.

At least once per 12 months by performing a system functional test which includes simulated automatic actuation of the system and verify that the automatic sprinkler valves in the flow path actuate to their corract position. Deluge system valves will be checked for auto actuation but will not be tripped through a complete cycle.

b.

At least once per 18 months:

1.

By a visual inspection of spray headers to verify their I

integri ty.

2.

By a visual inspection of each nozzle's spray area to verify spray pattern is not obstructed.

c.

At least once per 3 years by performing an air flow test through each spray / sprinkler header and verifying each open head spray /

sprinkler nozzle is unobstructed.

Amendment fio. 68 3.13-6