Forwards IE Bulletin 79-24, Frozen Lines. Action Required
ML19275A847
Person / Time
Site: McGuire Duke Energy icon.png
Issue date: 09/27/1979
From: James O'Reilly
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION II)
To: Parker W
DUKE POWER CO.
References
NUDOCS 7910190250
Download: ML19275A847 (2)


Text

'o,,

UNITED STATES 8

g NUCLEAR REGULATORY COMMISSION

a REGION ll 0,,

101 MARIETTA ST., N.W., SUITE 3100

%, * * * * *,o ATLANTA, GEORGIA 34303 SEP ^ ? 1979 In Reply Refer To:

RII:JPO Q 369 3 50-269 50-270 50-287 Duke Power Company Attn:

W. O. Parker, Jr.

Vice President, Steam Production P. O. Box 2178 Charlotte, North Carolina 28242 Gentlemen:

The enclosed Bulletin 79-24 is forwarded to you for action. Written responses are required.

If you desire additional information regarding this matter, please contact this office.

Sincerely, James P. O'Reilly Director anclosure:

1.

IE Bulletin No. 79-24 2.

Designated Applicants for Operating Licenses 1185 251 7910190 M 8

SEP ~'t id/S Duke Power Company,

cc w/ encl:

M. D. McIntosh, Project Manager Post Office Box 488 Cornelius, North Carolina 28031 J. C. Rogers, Project Manager Post Office Box 33189 Charlotte, North Carolina 28242 J. E. Smith, Station Manager Post Office Box 1175 Seneca, South Carolina 29678 O

4 f#

9

Accession No. 7908220114 SSINS No:

6820 UNITED STATES NUCLEAR REGUIATORY COMMISSION OFFICE OF INSPECTION AND ENFORCEMENT WASHINGTON, D.C.

20555 September 27, 1979 IE Bulletin No. 79-24 FR0 ZEN LINES Summary:

On January 3, 1979, an unusual event occurred at Davis-Besse, Unit 1.

The event involved the freezing of the water in a portion of the high pressure coolant injection (HPCI) system recirculation line that is common to both high pressure coolant injection pumps. The line was not thawed until January 5, 1979, and the event was not reported to NRC until March 12, 1979.

In addition, over the past five years, there have been several events involving frozen instrument and sampling lines.

Description of Circumstances:

The condition was discovered on January 3, 1979, while the reactor was operating at approximately 96 percent power.

During a monthly surveillance test of the HPCI pumps, there was no flow through the recirculation line from the pump discharge to the Borated Water Storage Tank (BWST).

Investigation revealed that water in a portion of the line exposed to the outside weather was frozen.

This portion of the line to the BWST is common to both HPCI pumps. The line has redundant heat tracing (a heated wire to prevent freezing); it is insulated; and it has a low-temperature alarm system to warn of freezing conditions.

Water in the line froze apparently becaase of prolonged sub-freezing temperatures and a defect in the insulation. There was no apparent malfunction of the heat tracing or temperature alarm circuits, although the temperature sensing elements are located in an area not exposed to the coldest temperature conditions.

This recirculation line serves two purposes.

0:.,

is to provide a flow path for surveillance testing, and the other is to provide a minimum flow path to prevent possible damage to the pump in the event it is operated against a closed discharge valve or a reactor coolant system pressure greater than the maximum discharge pressure of the pump (approximately 1600 psig).

In the initial review of the event on January 3, 1979, the licensee concluded that the pumps were still operable with the recirenlatian 1h ' ----

no immediate action was taken to thaw t January 5, 1979, the line was thawed an was successfully completed.