ML19275A359

From kanterella
Jump to navigation Jump to search
Forwards IE Info Notice 79-23, Emergency Diesel Generator Lube Oil Coolers. No Action Required
ML19275A359
Person / Time
Site: Crystal River 
Issue date: 09/26/1979
From: James O'Reilly
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION II)
To: Stewart W
FLORIDA POWER CORP.
References
NUDOCS 7910040170
Download: ML19275A359 (2)


Text

'o, UNITED STATES 8

NUCLEAR REGULATORY COMMISSION 4

g a

REGION 11 o,

101 MARIETTA ST., N.W., SUITE 3100 g

ATLANTA, GEORGIA 30303 1

SEP 2 6 979 In Reply Refer To:

RII:JPO Q D-302 7)

Florida Power Corporation Attn:

W. P. Stewart Director, Nuclear Operations P. O. Box 14042, Mail Stop C-4 St. Petersburg, Florida 33733 Gentlemen:

The enclosed Information Notice provides information with regard to failures of lube oil coolers for emergency diesel generators.

Sincerely,

_ _ =

James P. O'Reilly Director

Enclosures:

1.

Information Notice 79-23 2.

List of IE Information Notices Issued in the Last Six Months 1100 l.niu.

7010040 [7o

SEP 261979 Florida Power Corporation t cc w/ enc 1:

G. P. Beatty, Jr.

Nuclear Plant Superintendent Post Office Box 1240 Crystal River, Florida 32629 e

V 1'100 111 b

,,e-pm m9

    • S

~ *

  • d

Y Accession No:

7908220121 SSINS:

6870 UNITED STATES NUCLEAR REGULATORY COMMISSION OFFICE OF INSPECTION AND ENFORCEMENT WASHINGTON, D.C.

20555 September 26, 1979 IE Information Notice No. 79-23 EMERGENCY DIESEL GENERATOR LUBE OIL COOLERS Within a two week time span (August 27 to September 11, 1979), the tube sheets failed in the Arkansas Nuclear One (ANO) Unit I lube oil coolers for both of the Unit 1 Emergency Diesel lenerators. The introduction of water into the diesel lube oil system resulted in trips of both diesels during surveillance testing. The diesels were not considered capable of sustained operation.

Investigation by the licensee has indicated cracks around the outer periphery of the tube sheets. The exact failure mode has not been assessed; however, the licensee bas replaced the Emergency Diesel lube oil coolers for both diesels with a cooler of different d-ign.

The original lube oil coolers had tube sheets which were one-eighth (1/8, lach in thickness and the tubes were soldered in place.

Epoxy was also used as a sealer on the tube (water side) of the lube oil cooler.

The new coolers have one-half (1/2) inch tube sheets and the tubes are rolled.

The ANO, Unit 1 Emergency Diesel Generators were purchased in 1970 and were manufactured by the Electromotive Division of General Motors Corporation. The lube oil coolers (Model Number D-191700) were manufactured by Young Radiator Corpora tion.

This information is provided as an early notification of a possible significant matter.

It is expected that recipients will review the information for possible applicability to their facilities. No specific action or response is requested at this time.

If further NRC evaluations so indicate, an IE Circular or Bulletin will be issued to recommend or request specific licensee actions.

If you have questions regarding thie matter, please contact the Director of the appropriate NRC Regional Offic.

\\\\UG \\\\2 a n,.-

DUPLICATE ACUMENT into systemEntire document previousl under:

y entered ANL No. of pages:

,