ML19273B836
| ML19273B836 | |
| Person / Time | |
|---|---|
| Site: | Comanche Peak |
| Issue date: | 05/22/1979 |
| From: | Seidle W NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION IV) |
| To: | Gary R TEXAS UTILITIES ELECTRIC CO. (TU ELECTRIC) |
| References | |
| NUDOCS 7906180250 | |
| Download: ML19273B836 (1) | |
Text
[
Sa pic UNITE D STATES
+ -
E' h
NUCLEAR REGULATORY COMMISSION q y,. g G J' j
REGION IV O'
c 611 RYAN PLAZA DRIVE, SUITE 1000 s
D
%, ' \\
,o AH LINGTON, TE X AS 76012 May 22, 1979 Docket No. 50-445 50-446 Texas Utilities Generating Company ATTN: Mr. R. J. Gary, Executive Vice President and General Manager 2001 Bryan Tower Dallas, Texas 75201 Gentlemen:
Enclosed is supplement A0 to Preliminary Notification PNO-79-67, " Nuclear Incident at Three Mile Island," dated May 21, 1979.
Should you have any questions regarding this review, please contact this office.
Sincerely, f
d<G-W. C. Seidle, Chief Reactor C6hstruction and Engineering Support Branch
Enclosure:
PN0-79-67A0 7906180250
Y IMMEDIATE PRELIMINARY NOTIFICATION May 21, 1979 PRELIMINARY NOTIFICATION OF EVENT OR UNUSUAL OCCURRENCE - PNO-79-67A0 This preliminary notification constitutes summary information of an event of safety or public interest significance.
The, information presented is a summary of information as of 7:00 a.m. on May 21, 1979.
Facility: Three Mile ' Island Unit I Middletown, Pennsylvania (DN 50-320) w.
Subject:
NUCLEAR INCIDEh7 AT THREE MILE ISLAND
'sy Plant Status
' '5,
-;i.
Operational
-'^3 1.
The average coolaat temperature is being maintained at 170 degrees F by natural circulation.
Pressure is about 300 psi.
steam is being admitted to the main condenser through the turbine bypass valves from the A Steam Generator. The highest incore temperature reading is 301 degrees F.
2.
Hydrostatic testing of the existing decay heat removal systen "B" loop
~'
has been performed satisfactorily.
Leaks have been identified and are being corrected in the "A" loop.
3.
The pressurizer has been taken " solid" periodically to obtain confirmatory information on pressurizer level and to check primary systcc leak rate.
4.
The water level in the reactor building was measured and found to be 6.I' above floor level.
This is.about 450,000 gallons.
5.
One of two primary system pressure indications now in use is giving erratic readings.
Direct reading pressure gages can be connected to the system if needed.
Environmental. Status Environmental radiation levels continue to be consistent with natural background levels. Approximately six minor releases have occurred during the past week (May 14-20) in conjunction with changing levels in the primary make-up tank and sampling the primary system.
Aerial and ground surveys taken during these releases indicated no radiation IcVels above background, except for a release at 1300 on May 16, when an aerial measurement above the stack read 0.05 mR/hr.
No radiation was detected on the ground.
During the period May 14-20, approxi, mately 36 air samples were collected and all were less than MDA.
Vegetation -
and milk samples collected during this period also showed no activity sbove MDA. ' EPA and FDA air, water milk and food samples collected during this past week up to May 19 showed no detectable activity from TMI.
-s n ca na
[bmM S
C NTINUED 7906060181 baPe.
- f Continuad May 21, 1979 Page 2:
PNO-79-67AO s
Contact:
RCPaulus, IE x27246 DThompson, IE x28487 Distribution:
Transmitted H St it:04 Chairman Hendrie Comissioner Bradford S. J. Chilk, SECY Cozzaissioner Kennedy Conanissioner Ahearne C. C. Kan=erer, CA Commissioner Gilinsky ACRS (For Distribution)
~
Transmitted: HNBB P. Bldg litoo J. G. Davis, IE L. V. Gossick, EDO H. R. Denton, NRR Region I fr t4 11.*t7 a
i H. L. Ornstein, EDO R. C. DeYcung, NRR Region II ff *. In J. J. Fouchard, PA R. J. Mattson, NRR Region III lt'. M__
N. M. Haller, MPA V. Stello, NRR Region IV 12tto R. G. Ryan, OSP R. S. Boyd, NRR Region V D 'on H. K. Shapar, ELD SS Bldg (MJA)
W. J. Dircks, NMSS J. J6 Cunxnings, OIA S. Levine, PF.S R. Minogue, SD IE ('It!I) Sita (Piuvide supj Lu STATE) c.m.t
, ra vuddlat6wa - Ini-intormation Center)
White House Situation Rocc Eg (Provide'cooies to the Adminimermenv and rh. nn.ratinn= c.n e. A
~
DCPA HEW n.-
..., o,m >
JMMEDIATE PRELIMINPRY NOTIFICATION e
e e.'
.