ML19263E948

From kanterella
Jump to navigation Jump to search
Forwards IE Info Notice 79-19, Pipe Cracks in Stagnant Borated Water Sys at PWR Plants. No Action Required
ML19263E948
Person / Time
Site: Fermi 
Issue date: 07/18/1979
From: James Keppler
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION III)
To: Hines E
DETROIT EDISON CO.
References
NUDOCS 7907260389
Download: ML19263E948 (1)


Text

Tic

/

UNITED ST ATES

! \\, <,., rf,' %

NUCLEAR REGULATORY COMMISSION i

REGION lli o, k l/,rJ 799 NOOSE VE LT ROAD

'%.,- g G L E N E L L YN, IL LINOIS 6013 7 dVL 181SG Docket No. 50-341 The Detroit Edison Company ATTN:

Mr. Edward flines, Assistant Vice President and Manager Quality Assurance 2000 Second Avenue Detroit, MI 48226 Gentlemen:

This Information Not;ce is provided as an early notification of a possibly significant matter.

It is expected that recipients will review the infor-mation for possible applicability to their facilities.

No respcase is requested at this time, however, licensees should be aware that the NRC is evaluating the issuance of a Bulletin to operating PWR's requesting infor-mation on previous inservice inspections of stagnant borated water systems and requesting inspection of systems which have not been inspected recently.

If you have questions or comments regarding this matter, please contact the Director of the appropriate NRC Regional Office.

Sincerely,

%s.9)Og0~

(/ James G. Keppler Director

Enclosure:

IE Information Notice No. 79-19 cc w/ encl:

Cen:ral Files Director, NRR/DPM Directcr, NRR/ DOR PDR Local PDR NSIC TIC Ronald Callen, Michigan Public Service Commission Eugene B. Thomas, Jr.,

Attorney 1

790726 0 3 K.

UNITED STATES NUCLEAR REGULATORY CO*0 FISSION OFFICE OF INSPECTION AND ENFORCEMENT WASHINGTON, D. C.

20555 July 17, 1979 IE Information Notice No. 79-19 PIPE CRACKS IN STAGNANT BORATED WATER SYSTEMS AT PWR PLANTS Description of Circumstances:

~

During the period of November 1974 to February 1977 a number of cracking incidents have been experienced in safety-related stainless steel piping systems and portions of systems which contain oxygenated, stagnant or essentially stagnant borated water. Metallurgical investigations revealed these cracks occurred in the weld heat affected zone of 8-inch to 10-inch type 304 material (schedule 10 and 40), initiating on the piping I.D. surface end propagating in either an intergranular or transgranular mode typical of Stress Corrosion Cracking. Analysis indicated the probable corrodents to be chloride and oxygen contamination in the affected systems. Plants affected up to this time were Arkansas Nuclear Unit 1, R. E. C'.nna, H.B. Robinson Unit 2 Crystal River Unit 3, San Onofre Unit 1, and Surry Units 1 and 2.

The NRC issued Circular 76-06 (copy attached) in view of the apparent generic nature of the problem.

During the refueling outage of Three Mile Island Unit 1 which began in February of this year, visual inspections disclosed five (5) through-vall cracks at welds in the spent fuel cooling system piping and one (1) at a weld in the decay heat removal system. These cracks were found as a result of local boric acid build-up and later confirmed by liquid penetrant tests. This initial identification of cracking was reported to the NRC in a Licensee Event Report (LER) dated May 16, 1979. A preliminary metallurgical analysis was performed by the licensee on a section of cracked and leaking weld joint from the spent fuel cooling system.

The conclusion of this analysis was that cracking was due to Intergranular Stress Corrosion Cracking (ICSCC) originating on the pipe I.D.

The cracking was localized to the heat affected zone where the type 304 stainless steel is sensitized (precipitated carbides) during welding. In addition to the main through-wall crack, incipient cracks were observed at several locations in the veld heat affected zone including the weld rooc fusion area where a miniscule lack of fusion had occurred. The stresses responsible for cracking are believed to be primarily residual welding stresses in as much as the calculated applied stresses were found to be less than code design limits. There is no conclusive evidence at this time to identify those aggressive chemical species which promoted this IGSCC attack. Further analytical efforts in this area and on other system welds is being pursued.

DUPLICATE DOCUMENT Entire document previously entered into system under:

9 lb ]A3 0 lb Y ANO N o.

of pages:

9