APPENDIX B NOTICE OF DEVIATION Tennessee Valley Authority License Nos. CPPR-150 Hartsville, Unit A-1, A-2, CPPR-151 and B-1, and B-2 CPPR-152 CPPR-153 Based on the results of the NRC inspection conducted on January 2-5, 1979, certain of your activities appear to deviate from your commitments to the Commission as indicated below.

The response to PSAR Question Number 130.23 states that, unless other-wise specified, placement, inspection and testing of concrete would be i:. accordance with requirements of ANSI N45.2.5.

ANSI N45.2.5-1974 was the current edition of the Standard at the time the response to the question was made and SER Section 3.8.4 designates ANSI N45.2.5-1974 as the effective revision of the standard upon which evaluation of the construction program was made.

ANSI N45.2.5-1974 requires that pumped concrete must be sampled at the pump line discharge. No exceptions were taken to this requirement in response to PSAR Question 130.23.

Contrary to the above, concrete was not sampled at the pump line discharge as requi red by ANSI N45.2.5-1974.