LER-1979-004, /03L-0 on 790130:reactor Protection Sys Reactor Coolant Loop Tests Exceeded Tech Spec Response Time.Cause Unknown.Resistance Temp Detector Will Be Replaced During Spring 1979 Outage |
| Event date: |
|
|---|
| Report date: |
|
|---|
| 3361979004R03 - NRC Website |
|
text
'
ATTACHMENT LER 79-04/3L-0 tiillstone Unit 2 Docket t'o. 50-336 EyENT DESCRIPTION Technical Specification Table 3.3-2 requires that RPS RTD's have a response tir.e of less than or equal to 10.0 seconds.
The testing program used by liillstone to satisfy this requirement included removal of the RTD's from their wells and subjecting them to a response time plunge test by the manufacturer, Rosemount, Inc.
Subsequent investigations of alternate test methods by Northeast Utilities led to an evaluation of in-situ testing of RID time response by the loop current step response (LCSR) tethod. The test results for al' bdor Coolant System RPS input RTD's were received for evaluation of the test method on 1/30/79.
Testing was performed by Analysis and lleasurement Services, and the validity of the LCSR test method and results was accepted by Northeast Utilities on 2/28/79.
Hence the LCSR test method and results will be utilized to determine RTD response times per Technical Specification Table 3.3-2.
The test results received on 1/30/79 indicated that the RCS loop 1 channel C hot leg RTD, TE-ll2HC, had a response time of 11.2 seconds.
All other RTD's were within specification, with the highest response time measurcd for any other RTD of 6.7 seconds.
The TE-ll2HC RTD is a Rosemount Madel No. 104ADA.
CAUSE DESCRIPTION The cause of the increase in TE-ll2HC response time is unknown.
The TE-112HC RTD instrument loop provides a loop 1 hot leg signal which is averaged with the corresponding loop 2 cl anel C signal.
This average hot leg temperature is then input to the RPS for the calculation of thermal power level by development of a delta-T power signal.
The resultant delta-T power signal is used for generation of the variable high power trip, thermal margin / low pressure trip and local power density trip.
Since only one channel was affected and the RPS trip scheme relies on a 2 out of 4 logic, the safety significance was minimal with the higher response time measured for TE-ll2HC.
Upon receipt of the test results a design change was evaluated and implemented which deleted the TE-ll2HC temperature loop input to the channel C hot leg temperature averaging circuit.
An evaluation by Combustion Engineering and Northeast Utilities confirmed the acceptability of this change.
RTD TE-ll2HC will be replaced during the spring 1979 refueling outage.
790'3200764
(7 77)
LICENSEE EVLNT HEPORT oNTnot stock- [
l l
l l
1 l@
(PLE ASE PHINT On TYPC ALL RLOUHtED ir# 0nf.'ATIONI 1
0 0_l-j_d _R_l0_b.. k l_-. l L b__} @[.L d [.1. b_ h l @ J J @
L.p LIClie;.t. !4u!/i f.n 2:s
- u UCt t.a t 1)vL JO
$1 C AI tu 7
8 9 LICt t.' f E COR[
14 l 's 5 1, 0_1__0.,.],0._,l 1 l 1_j _d@ __0 {_._.lDDD_ l 3_@ l _.0J _3. L018 CON'T 1]
[<
l__y t.d 1,3 EVCPJTUAIL 14 70 f ttrOH T D AIL EO O
0']
bl Do" h t i t U*.'e t H l
8 EVENI DESCntPHO1 AND PaoCAct.f Co%EGUENCEO h l
[QJ l_ Testing o f RPS reactor coolant loop _ RID'S_ indica ted_.a._rcl.panse_ time._for_.the_ loop.1 l
EEJ L annel C TH RTD (TE-ll2HC)_of 11.2 seconds exceeding _tN._T_ech. Snec._._Iahlel3-2 Ch [o gj [ value of less than or equal to 10 seconds.
l e s t i n'h __p e r fo rmel_ by_ An a ly sis _and j
l EE) Lrmsurement Services, was by the loop current step responsc_ method 's SR) of in-situ c
J T!
J Eg,'] [ testing, and the test method was evaluated and accepted _bL ortheast Utilities on
, g l 2/28/_79.
RTD's are Rosemount flodel fio.104ADA.
j t
I Ell L_
f> 3 cot'P.
VAtyg 7
1 9 S Y '. l E ?.1 C A l! T C Al'O f CG.4 CODE LV;LO;A CGYru',l'. t CODr E U 0 CO D L' 50;':Obt LlLAl@ LtJ@ LIJ@ LIJ.1tLsJ1LLLnl@ LEJ@ tzJ @
IIE
/
0 9
10 11 17 fl 16 la 20 HL VISION Sf r;uf N nAt 3CCU3141 N C!
nt_r001
_' V E ';1 1 ( A l t Oll OHT f.O C(d'E TYFC N o.
8 /.=l.
LLL9J trJ l oLo L4J..
Ldl LO_L3 J LLJ 1, 1 L,oJ unto s,
n n
u 2
n u
v n
3 s
Ame,>
a un o -$
rn:vtcn m cre e rs:
';l I t D F C' LUR OmeUIH nANUF ACTUilf n ernm r o t o r.<
rirter s e n.-
H O L'P S 2h LrJ@L^J@
(.MO Lz.jg t0_J9.JLLJ llj@
llJO LLtJ@
lR !316 l9 K T A r. t N
/ C it O'd O'dPLANT f/Lif'G3 3J J4 3,
J1 43 41 42 43 44 47
.cAuct otr.cioerioN r.No connccuvt Action O
_ __J
[ y [The lE-ll2HC response time increase cause is unknown._ All other RTD's were in I
g [ spc,ification.
A temporary modi fication was implemented to delete the TE-112E_as This j
g [ an RPS input., using the loop 2 TH signal as the average channel C input.
RTO will be replaced
_J hul Ec nditi n was evaluated as acceptable by the flSSS vendor.
I p G L uring the Spring 1979 refueling outage.
d 83 7
8 9 DISCOVt liY D[SCHIP T103 5T AN.
% t'07.r Fi oiHE n s i A 7vs i,
t Surveillance testing j
flA l
[CJgl
[ g jEj@ [1l0l0 g
'4 toc,nonor,4u m @
A!nvity Co'8 u.a A20ons omCi,v 1v @ I I
,,< u m o m ou m.,
rut L
un EED L7J @ llj@L 00 44 0
7 h 3 10 11 Pf ft 50N '.f 1 E ' UCU4LS fiTT) 1 o! ol oi@L zj@l ran
- - l N
NU' 419 [ R 1YPf Ot 0(. p4lP f lO'J Pt ic.G*4:4 L L l'aju i f_5 NWM 61 D C LC 411P ilO'4 l
li I n~1 LoJ_o l o @L_
r:^
C0 7
8 9 11 12 10".$ of OH OA'st.r,t 1o,Ac UTY
OE 'A.hi p i t oy Ujjtjlzj@l tJA 01 7
H 9 10 nne use oNov 17 I o f L z]["@I't7 uni.nwag l
t4A i-i I i i i i_j i i i i i 1 ino 8J' 68 09 203-447-1791 7
8 9 10 J. Crockett pg nc.
|
|---|
|
|
| | | Reporting criterion |
|---|
| 05000336/LER-1979-001, Forwards LER 79-001/03L-0 | Forwards LER 79-001/03L-0 | | | 05000336/LER-1979-001-03, /03L-0 on 790105:during Normal Operation,Failure of Inverter 4 Interrupted 120V Vital AC Power to Channel D Components.Inverter Malfunction Caused by Failure of Several Capacitors (C1) & Oscillator Board (SC1-PL-1163) | /03L-0 on 790105:during Normal Operation,Failure of Inverter 4 Interrupted 120V Vital AC Power to Channel D Components.Inverter Malfunction Caused by Failure of Several Capacitors (C1) & Oscillator Board (SC1-PL-1163) | | | 05000245/LER-1979-001-01, /01T-0 on 790106:circumferential Crack Found in Heat Affected Zone of Weld Clean Up Sys Return Line.Caused by Intergranular Stress Corrosion Cracking Accelerated by Mechanical & Thermal Stresses | /01T-0 on 790106:circumferential Crack Found in Heat Affected Zone of Weld Clean Up Sys Return Line.Caused by Intergranular Stress Corrosion Cracking Accelerated by Mechanical & Thermal Stresses | | | 05000245/LER-1979-001, Forwards LER 79-001/01T-0 | Forwards LER 79-001/01T-0 | | | 05000245/LER-1979-002, Forwards LER 79-002/03L-0 | Forwards LER 79-002/03L-0 | | | 05000245/LER-1979-002-03, /03L-0 on 790107:reactor Low Water Level Signal Resulted from Failure of a Standby Gas Treatment Sys. Caused by Misalignment of Movable Contact Cover on Relay That Starts a Standby Gas Treatment Sys | /03L-0 on 790107:reactor Low Water Level Signal Resulted from Failure of a Standby Gas Treatment Sys. Caused by Misalignment of Movable Contact Cover on Relay That Starts a Standby Gas Treatment Sys | | | 05000336/LER-1979-002-03, /03L-0 on 790116:following Return to sub-critical Conditions,Investigations Showed Faulty Position Indication for Control Element Assembly 63,indicating About 6 Steps High.Caused by Position Indication Unit Drift | /03L-0 on 790116:following Return to sub-critical Conditions,Investigations Showed Faulty Position Indication for Control Element Assembly 63,indicating About 6 Steps High.Caused by Position Indication Unit Drift | | | 05000336/LER-1979-002, Forwards LER 79-002/03L-0 | Forwards LER 79-002/03L-0 | | | 05000245/LER-1979-003, Forwards LER 79-003/03L-0 | Forwards LER 79-003/03L-0 | | | 05000245/LER-1979-003-03, /03L-0 on 790108:one of Four Pressure Switches Responsible for Initiation of Group 1 Isolation Tripped Outside Tech Spec Limits.Caused by Instrument Drift | /03L-0 on 790108:one of Four Pressure Switches Responsible for Initiation of Group 1 Isolation Tripped Outside Tech Spec Limits.Caused by Instrument Drift | | | 05000336/LER-1979-003-03, /03L-0 on 790216:control Element Assembly 68 Dropped to Zero Steps,Resulting in Control Element Assembly Misalignment & Tilt to Max .029.No Component Failures. Control Element Assembly Recovered | /03L-0 on 790216:control Element Assembly 68 Dropped to Zero Steps,Resulting in Control Element Assembly Misalignment & Tilt to Max .029.No Component Failures. Control Element Assembly Recovered | | | 05000336/LER-1979-003, Forwards LER 79-003/03L-0 | Forwards LER 79-003/03L-0 | | | 05000245/LER-1979-004, Submits Addl Info to LER 79-04/03L.Control Rod 22-07 Declared Inoperable on 790125.Many Fragments of Broken Source Holder Were Retrieved.All Fragments Have Been Removed | Submits Addl Info to LER 79-04/03L.Control Rod 22-07 Declared Inoperable on 790125.Many Fragments of Broken Source Holder Were Retrieved.All Fragments Have Been Removed | | | 05000336/LER-1979-004-03, /03L-0 on 790130:reactor Protection Sys Reactor Coolant Loop Tests Exceeded Tech Spec Response Time.Cause Unknown.Resistance Temp Detector Will Be Replaced During Spring 1979 Outage | /03L-0 on 790130:reactor Protection Sys Reactor Coolant Loop Tests Exceeded Tech Spec Response Time.Cause Unknown.Resistance Temp Detector Will Be Replaced During Spring 1979 Outage | | | 05000336/LER-1979-004, Forwards LER 79-004/03L-0 | Forwards LER 79-004/03L-0 | | | 05000245/LER-1979-004-03, /03L-0 on 790125:during Routine Stuck Control Rod Surveillance,Control Rod 22-07 Stuck.Cause Unknown;Collet Cracking Ruled Out as Cause.Will Investigate During Upcoming Refueling Outage | /03L-0 on 790125:during Routine Stuck Control Rod Surveillance,Control Rod 22-07 Stuck.Cause Unknown;Collet Cracking Ruled Out as Cause.Will Investigate During Upcoming Refueling Outage | | | 05000336/LER-1979-005-03, /03L-0 on 790218:malfunction in Computer Resulted in Control Element Assembly Pulse Counting Position Being Inoperable.Cause Traced to Circuit Card in Computer Memory; No Fault Discerned.Card Contacts Cleaned | /03L-0 on 790218:malfunction in Computer Resulted in Control Element Assembly Pulse Counting Position Being Inoperable.Cause Traced to Circuit Card in Computer Memory; No Fault Discerned.Card Contacts Cleaned | | | 05000336/LER-1979-005, Forwards LER 79-005/03L-0 | Forwards LER 79-005/03L-0 | | | 05000245/LER-1979-006, Forwards LER 79-006/03L-0 | Forwards LER 79-006/03L-0 | | | 05000245/LER-1979-006-03, /03L-0 on 790201:unit Operated in Degraded Mode Due to Deficient Control Rods.Caused by Personnel Oversight. Rods Were Made Operable & Tech Spec Change Submitted | /03L-0 on 790201:unit Operated in Degraded Mode Due to Deficient Control Rods.Caused by Personnel Oversight. Rods Were Made Operable & Tech Spec Change Submitted | | | 05000336/LER-1979-007, Forwards LER 79-007/03L-0 | Forwards LER 79-007/03L-0 | | | 05000336/LER-1979-007-03, /03L-0 on 790228:both Control Room Chlorine Detection Sys Declared Inoperable.Caused by Improper Calibr of Detectors Due to Use of Inaccurate Calibr Gas.Sys Returned to Svc After Recalibr | /03L-0 on 790228:both Control Room Chlorine Detection Sys Declared Inoperable.Caused by Improper Calibr of Detectors Due to Use of Inaccurate Calibr Gas.Sys Returned to Svc After Recalibr | | | 05000245/LER-1979-007, Forwards LER 79-007/03L-0 | Forwards LER 79-007/03L-0 | | | 05000245/LER-1979-007-03, /03L-0 on 790214:gas Turbine Failed to Complete Starting Sequence While Conducting Fast Start.Caused by Potential Malfunction in Speed Switch.Switches Will Be Replaced During Next Refueling Outage | /03L-0 on 790214:gas Turbine Failed to Complete Starting Sequence While Conducting Fast Start.Caused by Potential Malfunction in Speed Switch.Switches Will Be Replaced During Next Refueling Outage | | | 05000336/LER-1979-008, Forwards LER 79-008/03L-0 | Forwards LER 79-008/03L-0 | | | 05000336/LER-1979-008-03, /03L-0 on 790314:while Steam Generator Eddy Current Testing in Progress,Loss of Structural Design Criteria Experienced.Caused by RCS Draining Down to Low Levels in Hot Leg.Procedures Changed to Ensure Suction | /03L-0 on 790314:while Steam Generator Eddy Current Testing in Progress,Loss of Structural Design Criteria Experienced.Caused by RCS Draining Down to Low Levels in Hot Leg.Procedures Changed to Ensure Suction | | | 05000245/LER-1979-008, Forwards LER 79-008/03L-0 | Forwards LER 79-008/03L-0 | | | 05000245/LER-1979-008-03, /03L-0 on 790214:isolation Condenser Inboard Steam Supply Valve Lost Position Indicator,Making Condenser Inoperable.Caused by Fractured Gear Casing on Valve Operator.Operator Removed,Rebuilt,Reinstalled & Tested | /03L-0 on 790214:isolation Condenser Inboard Steam Supply Valve Lost Position Indicator,Making Condenser Inoperable.Caused by Fractured Gear Casing on Valve Operator.Operator Removed,Rebuilt,Reinstalled & Tested | | | 05000245/LER-1979-009, Forwards LER 79-009/03L-0 | Forwards LER 79-009/03L-0 | | | 05000245/LER-1979-009-03, /03L-0 on 790222:operability of Safety Relief Bellow Monitor Valve (1-MS-3A) Could Not Be Verified.Caused by Crack in Fitting Connecting Bellows Air Tubing to Valve Bonnet Cap.Fitting Replaced | /03L-0 on 790222:operability of Safety Relief Bellow Monitor Valve (1-MS-3A) Could Not Be Verified.Caused by Crack in Fitting Connecting Bellows Air Tubing to Valve Bonnet Cap.Fitting Replaced | | | 05000336/LER-1979-011-03, /03L-0 on 790514:one Electrical Penetration & Several Boundary Valves Had Leakage.Caused by Inadevertent Omission of pre-repair Leak Rate Measurement for Some Valves.Test Procedures to Be Revised | /03L-0 on 790514:one Electrical Penetration & Several Boundary Valves Had Leakage.Caused by Inadevertent Omission of pre-repair Leak Rate Measurement for Some Valves.Test Procedures to Be Revised | | | 05000336/LER-1979-012, Forwards LER 79-012/01T-0 | Forwards LER 79-012/01T-0 | | | 05000336/LER-1979-012-01, /01T-0 on 790522:during Rise to 30% Power,Two of Four Linear Power Range Channels Found to Be Inoperable. Open Connections Found Between Detector Cables & Field Wiring.Caused by Connector Pins Pushed Into Connector | /01T-0 on 790522:during Rise to 30% Power,Two of Four Linear Power Range Channels Found to Be Inoperable. Open Connections Found Between Detector Cables & Field Wiring.Caused by Connector Pins Pushed Into Connector | | | 05000245/LER-1979-013, Forwards LER 79-013/03L-0 | Forwards LER 79-013/03L-0 | | | 05000245/LER-1979-013-03, /03L-0 on 790508:oxygen Pressure 603.5 Check for Source Range Monitors Not Completed for 24-h Period. Surveillance Overlooked.Checklist Added to Indicate Requirement of Procedure | /03L-0 on 790508:oxygen Pressure 603.5 Check for Source Range Monitors Not Completed for 24-h Period. Surveillance Overlooked.Checklist Added to Indicate Requirement of Procedure | | | 05000336/LER-1979-013-03, /03L-0 on 790525:during Check of Control Room Chlorine Detection Sys,Both Detectors Declared Inoperable Due to Low Drip Rates in Sensor.Caused by Clogged Dispensers.Dispensers Cleaned,Restoring Operability | /03L-0 on 790525:during Check of Control Room Chlorine Detection Sys,Both Detectors Declared Inoperable Due to Low Drip Rates in Sensor.Caused by Clogged Dispensers.Dispensers Cleaned,Restoring Operability | | | 05000336/LER-1979-013, Forwards LER-79-013/03L-0 | Forwards LER-79-013/03L-0 | | | 05000336/LER-1979-014-03, /03X-2:on 790604,during Routine Operations,Small Crack Discovered in Charging Pump Body C.Caused by Stress of Fatigue Failure in Valve Block.Three Charging Pumps Replaced W/Gaulin Pumps | /03X-2:on 790604,during Routine Operations,Small Crack Discovered in Charging Pump Body C.Caused by Stress of Fatigue Failure in Valve Block.Three Charging Pumps Replaced W/Gaulin Pumps | | | 05000245/LER-1979-014, Forwards LER 79-014/03L-0 | Forwards LER 79-014/03L-0 | | | 05000245/LER-1979-014-03, /03L-0 on 790511:during Audit of Refuel Outage Surveillances,Source Range Monitor Functional Surveillance Was Inadvertently Overlooked.Caused by Failure of Monitor Functional to Be Listed in Refueling Checklist | /03L-0 on 790511:during Audit of Refuel Outage Surveillances,Source Range Monitor Functional Surveillance Was Inadvertently Overlooked.Caused by Failure of Monitor Functional to Be Listed in Refueling Checklist | | | 05000336/LER-1979-014, Forwards LER 79-014/03X-2 | Forwards LER 79-014/03X-2 | | | 05000336/LER-1979-015-03, /03L-0 on 790610:leak Identified in RCS & Traced to Isolation Valve.Cause Unknown.Isolation Valve Repaired & power-operated Relief Valve Declared Operable | /03L-0 on 790610:leak Identified in RCS & Traced to Isolation Valve.Cause Unknown.Isolation Valve Repaired & power-operated Relief Valve Declared Operable | | | 05000336/LER-1979-015, Forwards LER 79-015/03L-0 | Forwards LER 79-015/03L-0 | | | 05000245/LER-1979-015-03, /03L-0 on 790528:during Refueling,No Control Rod out-block Occurred When Refuel Bridge Was Over Core W/Fuel Assembly Loaded Grapple.Caused by Worn Track Limit Switch. Switch Replaced & Surveillance Procedure Changed | /03L-0 on 790528:during Refueling,No Control Rod out-block Occurred When Refuel Bridge Was Over Core W/Fuel Assembly Loaded Grapple.Caused by Worn Track Limit Switch. Switch Replaced & Surveillance Procedure Changed | | | 05000245/LER-1979-015, Forwards LER 79-015/03L-0 | Forwards LER 79-015/03L-0 | | | 05000245/LER-1979-016, Forwards LER 79-016/03L-0 | Forwards LER 79-016/03L-0 | | | 05000336/LER-1979-016-03, /03L-0 on 790611:pressurizer Pressure Channel for One of Two power-operated Pressurizer Relief Valves Found to Be Reading 250 PSI Lower than Actual Pressure.Caused by Shift at Zero Point.Zero Point Readjusted | /03L-0 on 790611:pressurizer Pressure Channel for One of Two power-operated Pressurizer Relief Valves Found to Be Reading 250 PSI Lower than Actual Pressure.Caused by Shift at Zero Point.Zero Point Readjusted | | | 05000336/LER-1979-016, Forwards LER 79-016/03L-0 | Forwards LER 79-016/03L-0 | | | 05000245/LER-1979-016-03, /03L-0 on 790530:pressure Switches 263-52A, 263-52C,263-54A & 263-54B Tripped Outside Allowable Band. Caused by Setpoint Drift.Switches Reset within Required Range & Tested | /03L-0 on 790530:pressure Switches 263-52A, 263-52C,263-54A & 263-54B Tripped Outside Allowable Band. Caused by Setpoint Drift.Switches Reset within Required Range & Tested | | | 05000245/LER-1979-017-03, /03L-0 on 790602:steam Tunnel Switch Tripped at Setpoint Higher than Specified in Tech Specs.Caused by Setpoint Drift.Switch Adjusted & Tested Satisfactorily | /03L-0 on 790602:steam Tunnel Switch Tripped at Setpoint Higher than Specified in Tech Specs.Caused by Setpoint Drift.Switch Adjusted & Tested Satisfactorily | |
|