DEC 07 B78 APPENDIX A NOTICE Of VIOLATION Tennessee Valley Authority License Ws. DPR-52 Based on the results of the NRC iispection conducted 'n November 13-17, 1978, o

it appears that certain of your adivities were not conducted in full compliance with NRC requirements as indicated below. These items have been categorized as described in our correspondence to you dated December 31, 1974.

Technical Specification 3.1 and Table 3.1.A required that the trip level setting on the main steam line high radiation monitors be set at less than or equal to 3 times the normal full power background.

Contrary to the above, on November 14, 1978, an NRC inspector determined that the Trip Level Settitgs for channels B, C and D of the Unit 2 main steam line high radiation monitors vere respectively 3.4, 5.3 and 3.4 times the normal full power background.

This is an infraction.

c 7901260W9