DUKE PowEn COMPANY NoUnib,Dbit.prwo 422 Sot:Tn Cut:acu STnzzT, CruutnTTE, N. C. 2a242 WI L LI AM O. PA R E E R, J R,
" October 19,'197d vier p.e.,oc~.
wr -o~c: ^* ta 7:4 Svea Pecovceion 3 7 3-4 0 e )
Mr. J. P. O'Reilly, Director U.S. Nuclear Regulatory Commission Region II IC' Marietta Street, Suite 3100 Atlanta, GA 30303 Re:
RII:TDG 50-370/79-18
Dear Mr. O'Reilly:
Attached is the response to Infraction 79-18-01 which was identified in IE Inspection Report 50-370/79-18. Duke Power Company does not consider any information contained in this inspection report to be proprietary.
I
/
Ve ' truly yours, p
w.-
lb.
b
' William O. Parker, Jr.
THH/sch Attachment e "" %,
1531 141 I
.:powend
,eus
, u_,. sw2,c,
/
IE Inspection Report 50-370/79-18 APPENDIX A NOTICE OF VIOLATION Duke Power Company McGuire Nuclear Station License No. CPPR-84 Based on the NRC inspection September 4-7, 1979, certain of your activities were appar ntly not conducted in full compliance with NRC requirements as indicated-below.
As required by 10 CFR 50, Appendix B, Criterion V and implemented by DPC Topical Report, paragraph 17.1.5 activities affecting quality shall be prescribed by documunted instructions, procedures, or drawings...and shall be accomplished in accordance with these instructions, procedures, or drawings.
Contrary to the above, Conduit Box stiffenings were installed on safety related motors without approved drawings. The stiffenings were installed on the centrifugal charging pump motor which is safety related.
This is an Infraction.
Response
Sketches of the subject electrical bracing installed on safety-related motors have been made. These sketches will be reviewed and approved in accordance with existing procedures to assure the adequacy of this bracing. This review will be complete by November 15, 1979, and at that time an Installation Specification will be written detailing both the approved method of installation and any necessary modifications to the bracing.
Construction work on the bracing will be completed and inspected by January 15, 1980.
Electrical design personnel currently receive annual training in the quality assurance procedures for nuclear safety-related work.
This training will now be conducted quarterly.
In addition,by November 1, 1979, all electrical design personnel will have received special instruction in the procedures to be followed whenever they are involved in safety-related work in the field.
In order to provide still further assurance against the recurrence of a similar violation, special procedural meetings will be held whenever an unusual quality assurance situation arises which should be brought to the attention of all electrical design personnel.
153\\
\\4nL