Forwards IE Info Notice 79-32, Separation of Electrical Cables for HPCI & Automatic Depressurization Sys. No Specific Action or Response Requested
ML19260C496
Person / Time
Site: Atlantic Nuclear Power Plant 
Issue date: 12/21/1979
From: James O'Reilly
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION II)
To: Collier A
OFFSHORE POWER SYSTEMS (SUBS. OF WESTINGHOUSE ELECTRI
References
NUDOCS 8001070248
Download: ML19260C496 (1)


Text

.

  1. pa a849'o,,

m UNITED STATES NUCLEAR REGULATORY COMMISSION

~

3, o

<E REGION 11

$ ~

o,,

f 101 MARIETTA ST., N.W., SUITE 3100 b

o ATLANTA, G EORGIA 30303 DEC 211979 In Reply Refer To:

)

w Offshore Power Systems Attn:

A. R. Collier, President P. O. Box 8000 Jacksonville, Florida 32211 Gentlemen:

This Information Notice is provided as an early notification of a possible significant matter. No specific action or response is requested at.his time.

However, we anticipate that further NRC evaluations will result in issuance of an IE Circular, Bulletin, or NRR Generic Letter in the near future which will recommend or request specific applicant or licensee actions.

If you have any questions regarding the matter, please contact the Director of the appropriate NRC Regional Office.

Sincerely,

=~=:-,-

James P. O'Rei Director

Enclosures:

1.

IE Information Notice No. 79-32 2.

List of Recently Issued

. ger

  • Information Notices 1696 243 80 o, o tu uer

UNITED STATES SSINS No.: 6870 NUCLEAR REGULATORY COMMISSION Accession No:

OFFICE OF INSPECTION AND ENFORCEMENT 7910250511 WASHINGTON, D.C.

20555 3

D

'93 December 21, 1979 sa hJ lE Information Notice No. 79-32 SEPARATION OF ELECTRICAL CABLES FOR HPCI AND ADS Teir notice contains information on boiling water reactors (BWR's) regarding the routing of high pressure coolant injection (HPCI) system and automatic depres-surization system (ADS) cables in the same cable tray.

Such routing violates design criteria for separation of these safety systems.

This potential cable separation problem for BWR's is highlighted as a result of our review of recent Licensee Event Reports (LER's): Hatch Units 1 & 2, Brunswick Unit 1, and James A. FitzPatrick (See references for LER identification).

Description of Circumstances:

The Hatch LER's state that the NSSS supplier (General Electric) contacted plant management about possible irregularities in cable separation between HPCI and ADS.

Plant engineering personnel subsequently confirmed that separation criteria per design notes were not met because HPCI system inboard steam supply isolation valve cables were routed with ADS control cables. The architect-engineer (AE) was notified of the HPIC/ ADS cable separation problem and they are formulating a design change to provide for proper cable separation. Other, immediate corrective action was not provided in the LER.

The Brunswick LER states that cables for the HPCI system steam supply inboard isolation valve are located in sections of cable tray containing ADS cables. Also, their analysis of those cables revealed that if the isolation valve were in the wrong position, then a failure at a tray section containing these cables might result in a combination of cable failures which could impair the operability of both the HPCI and ADS systems. The problem is common to both units at Brunswick.

The AE, United Engineers and Constructors, is said to be preparing plant modifi-cations to provide sufficient isolation of HPCI and ADS cables. The licensee stated that a review of emergency core cooling systems (ECCS) and their primary containment isolation valves is being performed to verify that no other cable separation problems exist. Also, the cable separation criterion for HPCI and ADS systems is to be redefined in the cable separation specifications to prevent future recurrences of this event.

The FitzPatrick plant staff was informed of the HPCI/ ADS cable routing problem by the AE, Stone and Webster, following a fire hazard analysis conducted by the AE.

Six cables which could affect the control of the steam supply inboard isolation valve for the HPCI system are located in the same cable trays as some ADS cables.

Initia1 corrective action by the licensee to preclude spurious closure of the HPCI system inboard steam supply isolation valve was to de-energize the valve by racking out the breaker.

In addition, for purposes of primary containment isolation, the outboard valve was maintained in its normal, closed pos q qpg 2 4 k

e IE Information Notice No. 79-32 December 21, 1979 Page 2 of 2 and checked daily. However, reevaluation of the initial corrective action indicated the preferred method of assuring operability of both the ECCS and primary containment isolation functions would be to provide additional protection against a fire which might involve cables of both the HPCI and ADS, and to restore the inboard isolation valve to a fully operable condition. Accordingly, FitzPatrick initiated an hourly patrolling fire watch and restored the inboard isolation valve to a fully operable condition. The hourly patrolling fire watch parallels that required by Technical Specifications when early warning protection against a potential fire must be taken due to inadequate or inoperable fixed detection systems, The FitzPatrick plant staff was also informed by Stone and Webster that other (third party) cables (not identified in the LER) could affect the operation of the inboard isolation valve for the HPCI steam supply due to their proximity to both HPCI and ADS cables. The licensee has decided to reroute the cables of concern to correct both problems, and states that a preliminary design modification has been completed.

Conclusions Our review indicates that lack of separation of hPCI and ADS cables is a possible generic problem for all BWR4's and that earlier designs may also be affected.

Permanent resolution of this problem, corrective action in the meanwhile, and separation from other systems such as RCIC or iso;ation condenser are under consideration by the NRC. 'It is anticipated that further NRC evaluations will result in issuance of an IE Circular, Bulletin, or NRR Generic Letter in the near future which will recommend or request specific applicant or licensee actions.

This Information Notice is provided to inform licensees of a possible significant matter.

If you have questions regarding this matter, please contact the Director of the appropriate NRC Regional Office.

No written response to this Information Notice is required.

References:

1.

Hatch 1, LER #79-056/0IT-0, dated September 11, 1979 2.

Hatch 2, LER #79-098/0IT-0, dated September 11, 1979 3.

Brunswick 1, LER #79-068/0IT-0, dated October 9, 1979 4.

FitzPatrick, LER #79-056/0IT-0, dated October 9, 1979 5.

FitzPatrick, LER #79-056/0IT-1, dated November 19, 1979 s

1696 245

IE Information Notice No. 79-32 Enclosure December 21, 1979 RECENTLY ISSUED IE INFORMATION NOTICES Information Subject Date Issued To Notice No.

Issued 79-32 Separation of Electrical 12/21/79 All holders of power reactors Cables for HPCI and ads OLs and cps 79-31 Use of Incorrect Amplified 12/13/79 All holders of power reactor Response Spectra (ARS)

OLs and cps 79-30 Reporting of Defects and 12/6/79 All power reactor facilities Noncompliance, 10 CFR Part 21.

holding OLs and cps and vendors inspected by LCVIP 79-29 Loss of Nonsafety-Related 11/16/79 All power reactor facilities Reactor Coolant System holding OLs or cps Instrumentation During Operation 79-28 Overloading of Structural 11/16/79 All power reactor facilities Elements Due to Pipe Support with an OL or CP Loads 79-27 Steam Generator Tube 11/16/79 All power reactor facilities Ruptures at Two PWR holding OLs and cps Facilities79-12A Attempted Damage to New 11/9/79 All Fuel Facilities, Fuel Assemblies research reactors, and power reactors with an OL or CP 79-26 Bresch of Containment 11/5/79 All power reactor facilities Integrity holding OLs and cps 79-25 Reactor Trips at Turkey 10/1/79 All power facilities with Point Units 3 and 4 an OL or a CP 79-24 Overpressurization of 10/1/79 All power reactor facilities Containment of a PWR Plant with a CP After a Main Steam Line Break 79 Emergency Diesel Generator 9/26/79 All power reac. tor Lube Oil Coolers facilities holding OLs and cps 79-22 Qualification of Control 9/14/79 All power reactor Systems facilities with operating licenses and construction permits.

\\

__