.e APR 7 gg I

'* ~ ~ _

  • Mr. J. R. kay.

flewport News Industrial Corporation 230 41st Street e

Newport News, Virginia 23607 3

r;

Dearfir. Hay:

SUBJECT:

FIREPROTECTIONQUESTIONOS~RACWASTE'YOLUMEREDUCTIONSYSTUI

~

Enclosed is a set of questions concerning our fire protection review E

of subject topical report.

3 Please provide answers to these questions by May 20, 1978.

l Sincerely.

l", ' ' m:d br

.~

~

Karl Xniel. Chief Light flater Reactors Branch No. 2 Division of Project Management

Enclosure:

As Stated I

i s

t 790116Oc4k l

4 I

~~

AFR 7 g7p ENCLOSURE FIRE PROTECTION QUESTIONS ON TOPICAL REPORT RWR-1

,t 1.

Not all fire hazards have teen identified with attendant necessary 1

fire protection. For instance, safety controls on the oil burner I

are not mentioned, nor the fire hazardt associated with fuel oil 1.

storage transfer and use. A fire hazards analysis should be I

submitted by the applicant which identifies all fire hazards *in the process, impact on the rest of th? nuclear power plant, and the protection provided.

?

2.

The radwaste facility should satisfy guidelines contained in Regulatory Guide 1.120, " Fire Protection Guidelines for Nuclear e

Power Plants." Location of the facility within the nuclear power plant is not specified and may vary from plant to plant. A detailed i

fire hazard analysis will be required for any specific proposal identifying fire hazards and how plant safety systems and equipment will be protected.

3.

Utilities referencing this Topical Report in their application will be required to demonstrate that release of radioactive materials to

{

the environment due to fire involving the entire inventory of contaminated waste will not exceed a small fraction of the limits set forth in 10 CFR Part 100.

b i

1 t

I m