ML19256F330

From kanterella
Jump to navigation Jump to search
Forwards 791205 NPDES Noncompliance Notification
ML19256F330
Person / Time
Site: Palisades 
Issue date: 12/14/1979
From: Hoffman D
CONSUMERS ENERGY CO. (FORMERLY CONSUMERS POWER CO.)
To: James Keppler
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION III)
Shared Package
ML18044A336 List:
References
NUDOCS 7912180508
Download: ML19256F330 (1)


Text

W gsc%

,f

'\\,

CODSum8fS l POW 8r k.g/ C0mpany se p

D)

General Offices 212 West Michigan Avenue, Jackson, Michegan 49201. Area Code St7 789 OSSO December lb,1979 Mr James G Keppler Office of Inspection and Enforcement Region III US Nuclear Regulatory Co=nission T99 Roosevelt Road Glen Ellyn, IL 60137 DOCKET 50-255 - LICENSE DPR PALISADES PLANT - SPECIAL NONRADIO-ACTIVE ENVIRONMENTAL MONITORING REPCRT Attached is an NPDES Nonce =pliance Notification issued by Ccnstners Power Company on Dece=ber 5, 1979 It is being submitted to you in accordance with Technical Specificatien 6.9.3.1.D.

David P Hoffhan (Signed)

David P Hoffrain Nuclear Licensing Ad=inistrator NPDES Nonce =pliance Notification (3 casca attached)

CC: Director, Office of Nuclear Reactor Regulation Director, Office of Inspection and Enforcement (0 )

0 9

1 i

'g 9 } [3 1 0 0 pu P'E

File No P10.2.1 Incident No PAL-79-10-NC34 NPDES NONCOMPLIANCE NOTIFICATION Possible Noncompliance With Daily Average / Maximum Limitation December 5, 1979 Plant: Palisades Permit No MI-0001457 Outfall Cescription: Turbine Sump Oil Separator Outfall No 800218 Parameter: Oil / Grease Parameter No 00556 1.

Date of Incident:

10-31-79 2.

Identification of specific effluent limitation exceeded:

Monthly average limitation of 15 mg/l for oil and grea_sm>.

3.

Description of Incident:

For the month of October, five samples were collected with a daily average of 21.9 mg/1.

4.

Apparent Cause:

The problem was apparently caused by a failure of the oil separator or improper operation.

5.

If not immediately corrected, the anticipated time the condition is expected to continue:

NA 6.

Corrective Action - The following corrective action was taken or will be taken to reduce, eliminate and prevent recurrence:

The separator was restored to proper operation and subsequent analysis shows results in the ?-10 mg/l range after 11/1/79.

7.

Additional Comments:

NA 8.

Signed: R L Fobes 7t~ u'x rdu i608 170

?0121 80 579 2_'

vvV lU/

File No P10.2.1 Incident No PAL-79-10-NC33 NPDES NONCOMPLIANCE NOTIFICATIO)]

Possible Noncompliance Wit.h Daily Average / Maximum Limi: Lion December 5, 1979 Plant: Palisades Permit No MI-0001457 Outfall

Description:

Turbine Sump Oil Separator Outfall No 800218 Parameter: Oil / Grease Parameter No 00556 1.

Date of Incident:

10-15, 23, 29-79 2.

Identification of specific effluent limitation exceeded:

Daily maximum limitation of 20 mg/l for oil and grease.

3.

Description of Incident:

Date Oil / Grease (Mg/l)

Volume (Gallons) 10/15/79 41 9,000 10/23/79 29 5,000 10/29/79 24.1 3,000 4.

Apparent Cause:

The problem was apparently caused by failure of the oil separator or improper operation.

5.

If not immediately corrected, the anticipated time the condition is expected to continue:

NA 6.

Corrective Action.- The following corrective action was taken or will be taken to reduce, eliminate and prevent recurrence:

The separator was restored to proper operation and subsequent cnalysis shows results in the 1-10 mg/l range after 11/1/79.

7.

Additional Comments:

NA 8.

Signed: R L Fobes ZAM D P*0

]DT y/ftb

@~

UoJ wJuuSJ 1608 171 7 912180 5c/F

4 File No P10.2.1 Incident No PAL-79-10-NC32 NPDES N0?IC0!!PLI.U;CE ?:rirIFIC.iTION Possible Noncompliance With Daily Average / Maximum Limitation December 5,1979 Plant: Palisades Permit No MI-0001457 Outfall

Description:

Laundry Wastes Prior to Dilution Outfall No 800174 Parameter: Phosphorus - Total Parameter No 00665 1.

Date of Incident:

10-20-79 2.

Identification of specific effluent limitation exceeded:.

Daily maximum total phosphorus limitation of 2.0 mg/1.

3.

Description of Incident:

On 10/20/79 a total of 5,000 gallons of laundry water with a total phosphorus concentration of 2.58 mg/l was released.

4.

Apparent Cause:

A change in the type and quantity of detergent used occurred at this time.

5.

If not immediately corrected, the anticipated time the condition is expected to continue:

NA 6.

Corrective Action - The following corrective action was taken or will be taken to reduce, eliminate and prevent recurrence:

Adjustments were made in the quantity of soap used. A possible problem with the testing reagents is also being evaluated.

7.

Additional Comments:

NA 8.

Signed: R L Fobes 5 f&&

1608 172!

7 01218 0 tiG) fi