ML19256F330
| ML19256F330 | |
| Person / Time | |
|---|---|
| Site: | Palisades |
| Issue date: | 12/14/1979 |
| From: | Hoffman D CONSUMERS ENERGY CO. (FORMERLY CONSUMERS POWER CO.) |
| To: | James Keppler NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION III) |
| Shared Package | |
| ML18044A336 | List: |
| References | |
| NUDOCS 7912180508 | |
| Download: ML19256F330 (1) | |
Text
W gsc%
,f
'\\,
CODSum8fS l POW 8r k.g/ C0mpany se p
D)
General Offices 212 West Michigan Avenue, Jackson, Michegan 49201. Area Code St7 789 OSSO December lb,1979 Mr James G Keppler Office of Inspection and Enforcement Region III US Nuclear Regulatory Co=nission T99 Roosevelt Road Glen Ellyn, IL 60137 DOCKET 50-255 - LICENSE DPR PALISADES PLANT - SPECIAL NONRADIO-ACTIVE ENVIRONMENTAL MONITORING REPCRT Attached is an NPDES Nonce =pliance Notification issued by Ccnstners Power Company on Dece=ber 5, 1979 It is being submitted to you in accordance with Technical Specificatien 6.9.3.1.D.
David P Hoffhan (Signed)
David P Hoffrain Nuclear Licensing Ad=inistrator NPDES Nonce =pliance Notification (3 casca attached)
CC: Director, Office of Nuclear Reactor Regulation Director, Office of Inspection and Enforcement (0 )
0 9
1 i
'g 9 } [3 1 0 0 pu P'E
File No P10.2.1 Incident No PAL-79-10-NC34 NPDES NONCOMPLIANCE NOTIFICATION Possible Noncompliance With Daily Average / Maximum Limitation December 5, 1979 Plant: Palisades Permit No MI-0001457 Outfall Cescription: Turbine Sump Oil Separator Outfall No 800218 Parameter: Oil / Grease Parameter No 00556 1.
Date of Incident:
10-31-79 2.
Identification of specific effluent limitation exceeded:
Monthly average limitation of 15 mg/l for oil and grea_sm>.
3.
Description of Incident:
For the month of October, five samples were collected with a daily average of 21.9 mg/1.
4.
Apparent Cause:
The problem was apparently caused by a failure of the oil separator or improper operation.
5.
If not immediately corrected, the anticipated time the condition is expected to continue:
NA 6.
Corrective Action - The following corrective action was taken or will be taken to reduce, eliminate and prevent recurrence:
The separator was restored to proper operation and subsequent analysis shows results in the ?-10 mg/l range after 11/1/79.
7.
Additional Comments:
NA 8.
Signed: R L Fobes 7t~ u'x rdu i608 170
?0121 80 579 2_'
vvV lU/
File No P10.2.1 Incident No PAL-79-10-NC33 NPDES NONCOMPLIANCE NOTIFICATIO)]
Possible Noncompliance Wit.h Daily Average / Maximum Limi: Lion December 5, 1979 Plant: Palisades Permit No MI-0001457 Outfall
Description:
Turbine Sump Oil Separator Outfall No 800218 Parameter: Oil / Grease Parameter No 00556 1.
Date of Incident:
10-15, 23, 29-79 2.
Identification of specific effluent limitation exceeded:
Daily maximum limitation of 20 mg/l for oil and grease.
3.
Description of Incident:
Date Oil / Grease (Mg/l)
Volume (Gallons) 10/15/79 41 9,000 10/23/79 29 5,000 10/29/79 24.1 3,000 4.
Apparent Cause:
The problem was apparently caused by failure of the oil separator or improper operation.
5.
If not immediately corrected, the anticipated time the condition is expected to continue:
NA 6.
Corrective Action.- The following corrective action was taken or will be taken to reduce, eliminate and prevent recurrence:
The separator was restored to proper operation and subsequent cnalysis shows results in the 1-10 mg/l range after 11/1/79.
7.
Additional Comments:
NA 8.
Signed: R L Fobes ZAM D P*0
]DT y/ftb
@~
UoJ wJuuSJ 1608 171 7 912180 5c/F
4 File No P10.2.1 Incident No PAL-79-10-NC32 NPDES N0?IC0!!PLI.U;CE ?:rirIFIC.iTION Possible Noncompliance With Daily Average / Maximum Limitation December 5,1979 Plant: Palisades Permit No MI-0001457 Outfall
Description:
Laundry Wastes Prior to Dilution Outfall No 800174 Parameter: Phosphorus - Total Parameter No 00665 1.
Date of Incident:
10-20-79 2.
Identification of specific effluent limitation exceeded:.
Daily maximum total phosphorus limitation of 2.0 mg/1.
3.
Description of Incident:
On 10/20/79 a total of 5,000 gallons of laundry water with a total phosphorus concentration of 2.58 mg/l was released.
4.
Apparent Cause:
A change in the type and quantity of detergent used occurred at this time.
5.
If not immediately corrected, the anticipated time the condition is expected to continue:
NA 6.
Corrective Action - The following corrective action was taken or will be taken to reduce, eliminate and prevent recurrence:
Adjustments were made in the quantity of soap used. A possible problem with the testing reagents is also being evaluated.
7.
Additional Comments:
NA 8.
Signed: R L Fobes 5 f&&
1608 172!
7 01218 0 tiG) fi