ML18044A335

From kanterella
Jump to navigation Jump to search
NPDES Noncompliance Notification:On 791031,five Oil & Grease Samples Collected Indicated Daily Average of 21.9 mg/1. Caused by Probable Failure of Oil Separator.Separator Restored to Proper Operation
ML18044A335
Person / Time
Site: Palisades Entergy icon.png
Issue date: 12/05/1979
From: Fobes R
CONSUMERS ENERGY CO. (FORMERLY CONSUMERS POWER CO.)
To:
Shared Package
ML18044A336 List:
References
PAL-79-10-NC34, NUDOCS 7912180512
Download: ML18044A335 (1)


Text

6File No Pl0.2.1

~Incident No PAL-79-10-NC34 NPDES NONCOMPLIANCE NOTIFICATION Possible Noncompliance With Daily Average/Maximum Limitation December 5, 1979 Plant:

Palisades Permit No MI-0001457 Outfall

Description:

Turbine Sump Oil Separator Outfall No.800218 Parameter:

Oil/Grease Parameter No 00556

1. -Date of Incident:

10-31-79

2.

Identification of specific effluent.limitation exceeded:

Monthly average limitation of 15 mg/l for oil and gr~**

3.

Description of Incident:

For the month of October,- five samples were collected with a daily average of 21.9 mg/L

4.

Apparent Cause:

The problem was apparently caused by a failure of the oil separator 6r improper operation.

5.

If not immediately corrected, the anticipated tinie the condition is expected to continue:

NA

6.

Corrective Action ~ The follo~ing corrective action was taken or will be taken to re9uce, eliminate and prevent recurrence:

The separator was restored to proper operation and subsequent analysis shows results in the 1-10 mg/l range after 11/1/79.

7..

Additional Comments:

NA.

8.

Signed:

R L Fobes

~£F~.

'79121 so SI~