~File No Pl0.2.1 Incident No PAL-79-10-NC32 NPDES NONCOMPLIANCE NOTH' [C\\T IOU Possible Noncompliance With Daily Average/Maximum Limitation December 5, 1979 Plant:
Palisades Permit No MI~0001457 Outfall.
Description:
Laundry Wastes Prior to Dilution Outfall No 800174 Parameter:
Phosphorus - Total Parameter No 00665
- 1.
Date of Incident:
10-20-79
- 2.
Identification of specific effluent limitation e~ceeded:,
Daily maximum total phosphorus limitation of 2.0 mg/l.
- 3.
Description of Incident:
On 10/20/79 a total of 5,000 gallons of laundry water ~ith a total phosphorus.concentration of 2.58 mg/l was. released.
- 4.
Apparent Cause:
A change in the type and quantity of detergent used occurred at this time.
- 5. If not immediately corrected, the anticipated time the condition is expected to continue:
NA
- 6.
Corrective Action - The following corrective action was taken or will be taken to reduce, eliminate and prevent recurrence:
Adjustments were made in. the quantity of soap used.
A possible problem with the testing reagents is also being evaluated.
- 7.
- Additional Comments:
NA
- 8.
Signed:
R L Fobes