05000336/LER-1979-017-03, /03L-0 on 790614:auxiliary Feedwater Pump Rendered Inoperable by Inboard Pump Bearing Failure.Caused by Contamination of Bearing Oil W/Water.Pump Bearings & Shaft Replaced & Pump Restored to Svc

From kanterella
(Redirected from ML19246B566)
Jump to navigation Jump to search
/03L-0 on 790614:auxiliary Feedwater Pump Rendered Inoperable by Inboard Pump Bearing Failure.Caused by Contamination of Bearing Oil W/Water.Pump Bearings & Shaft Replaced & Pump Restored to Svc
ML19246B566
Person / Time
Site: Millstone Dominion icon.png
Issue date: 07/13/1979
From: Stratman R
NORTHEAST UTILITIES
To:
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION I)
Shared Package
ML19246B565 List:
References
LER-79-017-03L-01, LER-79-17-3L-1, NUDOCS 7907170229
Download: ML19246B566 (2)


LER-1979-017, /03L-0 on 790614:auxiliary Feedwater Pump Rendered Inoperable by Inboard Pump Bearing Failure.Caused by Contamination of Bearing Oil W/Water.Pump Bearings & Shaft Replaced & Pump Restored to Svc
Event date:
Report date:
3361979017R03 - NRC Website