Forwards IE Circular 79-12, Potential Diesel Generator Turbocharger Problem. No Action Required
ML19225A111
Person / Time
Site: Hatch, Vogtle  
Issue date: 06/28/1979
From: James O'Reilly
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION II)
To: John Miller
GEORGIA POWER CO.
References
NUDOCS 7907180436
Download: ML19225A111 (2)


Text

[pa atcg UNITED ST ATES

'c, NUCLE AR REGULATORY COMMISSION i

8 ')

REGION 11

$.Edh,b[I

' v o,

f 101 MARIE TT A ST, N W. SUIT E 3100 AT L ANT A, G E ORGI A 30303 6

3,,

j j@ g [: };. ' '

In Reply Refer To:

RII:JPO 50-321, 50-366 50-424, 50-ch,

c Georgia Power Company Attn:

J. H. Miller, Jr.

Executive Vice President 270 Peachtree Street, S. W.

Atlanta, Georgia 30303 Gentlemen:

The enclosed IE Circular 50. 79-12, is forwarded to you for infornation.

So written response is required.

Shoulc you have any questions related to your understanding of this natter, please contact this office.

Sincerely, s~

n-James P. O'Reill,.

Director

Enclosures:

1.

IE Circular No. 79-12 2.

List of IE Circulars Issued in Last 12

&ntE-r

, m[q

)

/

U'

~

79 0718 0 t/3f,

JUN 2 8197a Georgia Power Company cc w/ encl:

M. Manry, Plant Manager Post Office Box 442 Baxley, Georgia 31513 C. E. Belflower Site QA Supervisor Post Office Box 442 Baxley, Georgia 31513 K. M. Gillespie Construction Project Manager Post Office Box 282 Waynesboro, Georgia 30830 E. D. Groover QA Site Supervisor Post Office Box 282 Waynesboro, Georgia 30830 c' I P

e UNITED STATES NUCLEAR REGULATORY COMMISSION OFFICE OF INSPECTION AFD ENFORLEMENT WASHINGTON, D.C.

20555 June 28, 1979 IE Circular No. 79-12 (7906210065)

POTENTIAL DIESEL GENERATOR TURBOCRARGER PROBLEM Description of Circumstances:

The Electro-Motive Division (EMD) of General Motors Corporation has recently identified a potential failure mode of turbochargers used on EMD diesels in nuclear plant standby service.

When an engine is in the normal standby mode, the lubricating oil temperature is maintained at about 115 degrees F and the circulating oil pump supplies ware oil to the turbocharger bearings at a flow rate of about 2 gpe.

Since the total oil pump flow rate is 6 gpm, 4 gpm is also circulated, via a 30 psi rel,ef valve, through the lube oil filter and cooler which serves to keep the entire accessory lubricating oil system primed to support a fast start.

If a power outage occurs, the oil circulating pump may stop 5 to 10 seconds before the engine receives a start signal; but the main bearing and piston cooling pump will immediately receive oil f rom the primed lube oil filter-cooler system thus providing a rapid buildup of engine lube oil pressure throughout the engine bearing and turbocharger systems.

A potential problem occurs, however, if the diesel engine receives a repeat rapid start within a minimum of 15 minutes and a maximum of 3 bours af ter a shutdown from a previous run in which the engine has reached full operating t e =p e r a t u r e.

If, for example, the engine had been operated for about I hour at full load, the lube oil temperature would be at about 200 degrees F at time of shutdown.

Under these circumstances, the full 6 gpm output of the circu-lating pump will flow only to the turbocharger bearings because of the lower vascosity of the bot lubricant.

At this temperature, the circulating pump pressure will not reach 30 psi.

Until the lube oil cools to about 160 degrees F, no oil will be supplico via the relief valve to the equipment rack for the first 2 to 3 hours3.472222e-5 days <br />8.333333e-4 hours <br />4.960317e-6 weeks <br />1.1415e-6 months <br /> after engine shutdowm During this cooling period some of the oil contained in the cooler and filter will drain back to the engine sump via the lube oil scavenging pump, and some of the oil from the strainer box will be drawn into the cooler by the system vacuum that develops.

The result is that when a repeat fast start occurs within the above 15 minute to 3 hour3.472222e-5 days <br />8.333333e-4 hours <br />4.960317e-6 weeks <br />1.1415e-6 months <br /> time frame after a bot shutdown, lack of prime oil system pressure can cause engine damage.

In the worst case of a repeat fast start, the engine may actually reach operating speed, 900 RPM, before the required oil pressure as established at the turbocharger thrust bearing.

This may cause soec smea ring of the bearing metal so that cumulative damage from several similar starts would result in a turbocharger failu c.

r O 322 nUUV

IE Circular No. 79-12 June 28, 1979 Page 2 of 2 EMD is currently developing a modificacion to improve the lube oil system.

It is planned that this modification will be available for installation in approximately 6 montr.s.

In the interim, the following actions are recommended for those having EMD diesel engines:

1.

Repeated fast not starts within a minimum 15 minute to 3 hour3.472222e-5 days <br />8.333333e-4 hours <br />4.960317e-6 weeks <br />1.1415e-6 months <br /> time frame af ter shutdowr. should be avoided.

Allow the engine to cool at least 3 nours after i; has been operated in the " loaded" mode, or otherwise a restart should be performed within 15 minutes of shutdown.

2.

After changing oil filter elements or draining the accessory oil system for any reason, and upon refilling of the system make sure that the circu-lating oil pump is in operation for at least 30 minutes and that the strainer box is full before starting engine.

The engine should then be brought to an idling condition to assure complete filling of accessories before any subsequent fast start is made.

3.

Any small leak at the top of the oil cooler should be corrected.

A leak at this location allows air to be drawn into the cooler during shutdown, which will cause the drain back to be more rapid.

4.

Avoid testing of the redundant diesel engines concurrently.

Where it is necessary to run the redundant diesels concurrently, maintain one diesel in the running mode for a minimum of 3 bours following the shutdown of the other.

No written response to this Circular is required.

If you require additional inf ormation rega rding this subj ect, contact the Director of the appropriate NRC Regional Office.

322 0L'.

IE Circuler No. 79-12 Enclosure June 28, 1979 Page 1 of 3 LISTING OF IE CIRCULARS ISSUED IN LAST TVELVE MONTHS Circular Subject Date Issued To No.

of Issue 78-11 HPCI Turbine Control 6/30/78 All Holders of Valve Lift Rod Bending 5WR Ots or cps for plants with HPCI Terry Turbine 78-13 Inoperability of Multiple 7/10/78 All Holders of Service Water Pumps Reactor OLs and cps except for plants located in: AL, AK, CA, FL, GA, LA, MS, SC 78-14 HPCI Turbine Reversing 7/12/78 All Holders of BWR Chamber Hold Down Bolting OLs or cps for plants with a HPC1 Terry Turbine excepting Duane Arnold and Monticello 78-15 Check <alves Fall to 7/20/78 All Holders of Close In Vertical Reactor OLs or cps Position 7S-16 Limitorque Valve 7/26/78 All Holders of Actuators Reactor OLs or cps 78-17 Inadequate Guard Training /

10/13/78 All Holders of Qualification and Falsified and applicants Training Records for Reac'ar OLs 78-18 UL Fire Test 11/6/78 All Holders of Reactor OLs or cps 78-19 Hanual Override (Bypass) 12/28/78 All Holders of of Safety Actuation Signals (Ps b22. OB

IE Circular No. 79-12 Enclosure June 28, 1979 Page 2 of 3 LISTING OF IE CIRCULA..a ISSUED IN LAST TWELVE MONTHS Circular Subject Date of Issued to No.

Issue 79-01 Administration of 1/12/79 All Holders of Unauthorized Byproduct Licensees except Material to Humans Teletherapy Medir:1 Licensees and each Ra di opha rma c e u t i c a l Suppliers 79-02 Failure of 120 Volt Vital 2/16/79 All Holders of AC Power Supplies Reactor OLs and cps 79-03 Inadequate Guard Training-2/23/79 All Holders of Qualification and Falsified and applicants Training Records for Special Nuclear Material Licenses in Safeguards Group I 79-04 Loose Locking Nut on 3/16/79 All Holders of Limitorque Valve Reactor Ots or cps Operators 79-05 Moisture Leakage In 3/20/79 All Holders of Stranded Wire Conductor.,

Reactor OLs or cps 79-06 Failure to Use Syringe 4/19/79 All Holders of and Battle Shields in Medical Licensees Nuclear Medicine except teletherapy licensees 79-07 Unexpected Speed Increase 5/2/79 All Holders of of Reactc'r Recirculation BVE OL's or CP's MG Set Resulted in Reactor Power In<rease 79-08 Attemptec Extortion - Low 5/18/79 All fuel Facilities Enriched Jranium Licensed by NkC 79-09 0(currences of Split or 6/22/79 All Materials Punctured Regulator Diaphrages Priority I, Fuel In Certain Self Contained Cycle and Operating Breathing Apparatus Reactor Licensees 322 033

IE Circular No. 79-12 Enclosure June 28, 1979 Page 3 of 3 LISTING OF IE CIRCULARS ISSUED IN LAST TVEINE MONTHS Circular Subject Date of Issued to No.

Issued 79-10 Pipefittings Manufactured 6/26/79 All Power Reactor from Unacceptable Material Licensees with a CP and/or OL 79-11 Design / Construction 6/27/79 All Applicants Interface Problem foi, and Holders of Power Reactor cps na rr

[(

UV

.