LER-1979-028, /03L-0:on 790807,during Routine Surveillance of Core Spray Sys 1,parallel Isolation Valve V-20-15 Became Inoperable in Open Position.Caused by High Motor Current Drawn When Close Signal Inadvertently Initiated |
| Event date: |
|
|---|
| Report date: |
|
|---|
| 2191979028R03 - NRC Website |
|
text
u,,
LICENSEE EVENT REPORT ccbactelocK.j i
i l
l
)
l@
(PLE AsE F RINT CR TYPE ALL REQUIRED INFORf.iAT!oN) t
@l4 1 l1 Il 1 @!
l lo li N iJ 0 lC lP l1 @l0 0
0 0
0 010
- - l0 0
7 8 9
.lCENS EE COCE 14
.E LICENSE NUYtE A
.t LICE NSE TYPE A 53.A i SE CoTT oi1
$ 'n2 l M @ l0 l5 lo lo lo l2 11 b l@l0I81017l719 l@l0 19 10 16 17 19 @
S f,)
td DOCK ET NyV9ER C4 EP Et ENT C ATE 74 75 HEPORT D AT E 80 d
EVENT DEsCRIDTtoN AND FFoBAsLE CONSECUENCEs h a 12'l l On August 7, 1979, during routine surveillance of Core spray system I, I
o 3
L parallel isolation valve v-20-Is became inope-able in the open position.
l i a3 4i i The circuit breaker for the motor operator tripped when the actuation j
i oisi i pressure sensor was reset.
A parallel valve V-20-40, which is actuated l
!:le by the same pressure sensor, operated normally.
Valve stroking currents l
were read with the breaker reset and found to be normal.
The valve was lal : i i
, O i E I i_
stroked to determine operability and resurveilled without incident.
l E y Y *-
'.YE!
S
- $$t
=
t c:.; T C= E
! 19]
!S ! F @
X l@ lZl@ lC lK 'T B lR lK @lA @ lZ l@
t a
u 2
3 o
a SEOLENTI AL OCC A E E '.CE REFONT A E' 'i'ON c: ;-
E' :NT N E:A EE80HT NO CODE TvFE f. O.
@ 4..id 17 l9 l l-l l012l8l l/l l0l3l Ll l-l0l
__ ; 1 22 a
- 4
- C
- 7
- E C3 31 22 ACT;O'
- - JT GE EFFEC'
$ * ', 7 0 C.* '.
ATT AC <* ' E NT t.P R D-4 FRYE CCY8 COYPONENT TarEt ACT CN ON PL ANT
. E T ** O C eCUAS id SUE YtTT ED F C A '. SLS.
SLFPL'E A
AN U F AC T L, A E G l 0 l0 l0 l0 lY l@
lNl@
lN @
lGl018 0 l(g
!X l Z l@
lZl@
40 41 4
43 44 47 Jo Ji ct _ *,Es:P'eT;c, - so CcaaEcrive actions @
5:_t l_
The apparent cause of the occurrence was the high motor current drawn L
when a valve close signal was inadvertently initiated during the period l
l when the valve was still stroking open.
All associated electrical l
components were. functionally tested and found satisfactory.
The sur-l veillance procedure was revised.
Motor current tests were performed.
j 1 i; 7
2 3 80 F ACILITY l
v YETHCD C5 STAT 5 F O.N E A OT*d E R ST ATUS ~
D'5CC% E hY DiSCOV E R N C ESC R1DTiO'.
Je LEj h l1 l0 l0 @
NA l
lR l@l Operator observation.
i s
7 E 9 10 52 1 "3 44 45 46 EO ACT:vtTV CONTENT Rest-;EG OF RE LE ASE A*'Ou'iT OF ACTIVITY LOC ACN Cc RELE ASE ~"
lc l l Z @ Zl@l NA l
NA l
1 7
8 9 10
$ 1 44 45 pa FEa
. '.E L ! y PCS R E$
o_
i. E r*
TY E CESCMTION --
D
'i 0l0l0lhlZIhl NA e.
n u
o 3,'
' C *, '. E L i, ;., n FC
- - r e
C E,. '. P i p i i., *.
7 0 l 0 l@[
NA 1
i, l
j.
0 OFACIL*TVg
'l 9 0 9 1 2 0 Q L
A t.
7 l1 l9l d!y NA u
EUC UCL O.LY
,, 5 _
It!l\\lC,l Weekly news release - september 12, 1979.
l ll ll llIiltl l l u
Donald A. Ross 201 !.55-8784
.a.t c c :+ p e.,
pggyg
rw Jersey Central Pcwer & Light Company
( ) C q {,'
ff i
f/ad son A.eque at Punch Bowl Road 4
ac.
f/ctr;stchn. New Jersey 07960 1-a' (201)455-8200 OYSTER CREEK NUCLEAR GENERATING STATION Forked River, New Jersey 08731 Licensee Event Report Reportable Occurrence No. 50-219/79-28/3L-0 Report Date September 6, 1979 Occurrence Date August 7, 1979 Identification of Occurrence Core Spray System parallel isolation va!ve V-20-15 became inoperable in the open position when the motor breaker tripped.
This event is considered to be a reportable occurrence as defined in the Technical Specifications, pa rag ra ph 6. 9. 2. B. 2.
Conditions Prior to Occurrence The plant was operating at steady state power.
Power:
Core, 1930 MWt Electric, 641 MWe 4
Floa:
Recirculating, 15.2 x 10 gpm Feedwater, 7.143 x 106 lb/hr Stack Gas:
34,100 pci/sec Description of Occurrence On Tuesday, August 7, 1979, at approximately 2:00 p.m.,
during routine surveillance of Core Spray System I, parallel isolation valve V-20-15 motor circuit breaker tripped when the actuation pressure sensor was reset.
The parallel valve V-20-40, which is actuated by the same pressure sensor, operated normally.
The circuit breaker for V-204 5 was meggered as were the motor and cables with no abnormal conditions found.
Valve stroking currents were read with the breaker reset and the tripping elements were tested to determine their setpoints.
All parameters were found to be normal.
The valve was stroked to determine operability and resurveilled without incident.
(p?
' R
, -, a c.
u s - y C.-c'% Pon. L@ Cony n, r ' ' m : r c' in-Gr c < R a c U:- _: : eT
Reportable Occurrence No. 50-219/79-28/3L-0 Page 2 September 6, 1979 Apparent Cause of Occurrence The apparent cause of the occurrence was the inadvertent initiation of a valve close signal during the period when the valve was still stroking open.
This occurs when the valve open signal is removed in less time than is re-quired for the valve to assume the full open stop position.
The i.
.itaneous reversal in direction of the motor operator is not the intended mode of operation.
Reversal cf motor inertia while driving requires greater torque causing greater than normal starting current to be seen by the motor circuit breaker.
The added current is believed to have causea the circuit breaker to trip.
Analysis of Occurrence The safety significance of this event is ;onsidered to be minimal, since each of the parallel isolation valve: are designed fcr rated system flow and the alternate parallel valve, V-20 43, functioned as designed.
Had the Core Spray System been required at the time the valve became inoperable, the system would have operated as intended.
Corrective Action
initial corrective action consisted of the testing of the breaker and electrical valve components to assure proper functional capability and designed setpoints.
In addition, the surveillance procedure was revised to include more specific guidance to avoid inadvertent operational modes.
Subsequently, a test was conducted by the electrical staff to demonstrate the changes in current magnitude during simulated identical conditions.
The starting current during an instantaneous reversal in motor direction was found to be approximately 20% higher than normal starting current which tends to confirm the susoected cause for breaker trip.
The same current / time traces were made under similar conditions for parallel isolation valve V-20-40.
Since the results show the identical response found for V-20-15, we are assured that such response is not indicative of component failure or abnormal rea:tions of circuit elements.
Failure Data None O.' (
a
|
|---|
|
|
| | | Reporting criterion |
|---|
| 05000219/LER-1979-001-03, /03L-0 on 790118:valve V-14-35 Failed to Open Completely During Routine Isolation Condenser Valve Operability Test.Caused by Dirty Torque Limit Switch Contacts,Which Were Subsequently Cleaned & Burnished | /03L-0 on 790118:valve V-14-35 Failed to Open Completely During Routine Isolation Condenser Valve Operability Test.Caused by Dirty Torque Limit Switch Contacts,Which Were Subsequently Cleaned & Burnished | | | 05000219/LER-1979-001, Forwards LER 79-001/03L-0 | Forwards LER 79-001/03L-0 | | | 05000219/LER-1979-002, Forwards LER 79-002/03L-0 | Forwards LER 79-002/03L-0 | | | 05000219/LER-1979-002-03, /03L-0 on 790206:while Performing Isolation Condenser Automatic Actuation Test & calibr,RE-15B Trip Point Was Less Conservative than Tech Spec Std.Caused by RE-15B Switch Not Set at 1068 Psig valve.RE-15B Reset | /03L-0 on 790206:while Performing Isolation Condenser Automatic Actuation Test & calibr,RE-15B Trip Point Was Less Conservative than Tech Spec Std.Caused by RE-15B Switch Not Set at 1068 Psig valve.RE-15B Reset | | | 05000219/LER-1979-010-03, /03L-0 on 790417:leak of Isotopic Concentration Noticed Near Inside Penetration within Pipe Tunnel.Caused by Component Failure.Drywell Equipment Drain Tank Line Rerouted to Prevent Further Leakage | /03L-0 on 790417:leak of Isotopic Concentration Noticed Near Inside Penetration within Pipe Tunnel.Caused by Component Failure.Drywell Equipment Drain Tank Line Rerouted to Prevent Further Leakage | | | 05000219/LER-1979-010, Forwards LER 79-010/03L-0 | Forwards LER 79-010/03L-0 | | | 05000219/LER-1979-011-03, /03L-0 on 790419:core Spray Pump NZO1A in Sys 1 Failed to Start Upon Initiation Signal.Caused by Fuse Failure.Fuse Replaced & Pump Test Successfully Completed | /03L-0 on 790419:core Spray Pump NZO1A in Sys 1 Failed to Start Upon Initiation Signal.Caused by Fuse Failure.Fuse Replaced & Pump Test Successfully Completed | | | 05000219/LER-1979-011, Forwards LER 79-011/03L-0 | Forwards LER 79-011/03L-0 | | | 05000219/LER-1979-012-03, /03L-0 on 790419:oxygen Level in Suppression Chamber Atmosphere Was Greater than 5%.Caused by Sensitivity of Sampling Sys & Position of Sample Flow Control Valve. Oxygen Analyzer Recalibr;Level Now Below 5% | /03L-0 on 790419:oxygen Level in Suppression Chamber Atmosphere Was Greater than 5%.Caused by Sensitivity of Sampling Sys & Position of Sample Flow Control Valve. Oxygen Analyzer Recalibr;Level Now Below 5% | | | 05000219/LER-1979-012, Forwards LER 79-012/03L-0 | Forwards LER 79-012/03L-0 | | | 05000219/LER-1979-016, Forwards LER 79-016/03L-0 | Forwards LER 79-016/03L-0 | | | 05000219/LER-1979-016-03, /03L-0 on 790506:during Surveillance Test, Isolator Condenser Isolation Sensor Setpoint a Measured Two Inches of Excess Water.Caused by Instrument Drift in Excess of Design Accuracy.Switch Was Recalibr & Put Back in Svc | /03L-0 on 790506:during Surveillance Test, Isolator Condenser Isolation Sensor Setpoint a Measured Two Inches of Excess Water.Caused by Instrument Drift in Excess of Design Accuracy.Switch Was Recalibr & Put Back in Svc | | | 05000219/LER-1979-017, Forwards LER 79-017/03L-0 | Forwards LER 79-017/03L-0 | | | 05000219/LER-1979-017-03, /03L-0 on 790517:during Routine Surveillance of Core Spray Sys Ii,Parallel Isolation Valve V-20-21 Failed to Operate.Caused by Circuit Breaker Contacts Making Poor Contact in B Phase,Creating Overcurrent.Part Replaced | /03L-0 on 790517:during Routine Surveillance of Core Spray Sys Ii,Parallel Isolation Valve V-20-21 Failed to Operate.Caused by Circuit Breaker Contacts Making Poor Contact in B Phase,Creating Overcurrent.Part Replaced | | | 05000219/LER-1979-018, Forwards LER 79-018/03L-0 | Forwards LER 79-018/03L-0 | | | 05000219/LER-1979-018-03, /03L-0 on 790517:snubber 51/21,core Spray Sys II, Had Signs of Grease on Alemite Fitting on Accumulator.Cause Unknown But Appears Related to Rigorous Svc Conditions. Snubber Replaced | /03L-0 on 790517:snubber 51/21,core Spray Sys II, Had Signs of Grease on Alemite Fitting on Accumulator.Cause Unknown But Appears Related to Rigorous Svc Conditions. Snubber Replaced | | | 05000219/LER-1979-019-03, /03L-0 on 790526:reactor High Pressure Isolation Condenser Initiation Switch RE-15A Tripped at 3 Psig Greater than Specified.Caused by Instrument repeatability.RE-158 Reset to Trip at 1,068 Psig | /03L-0 on 790526:reactor High Pressure Isolation Condenser Initiation Switch RE-15A Tripped at 3 Psig Greater than Specified.Caused by Instrument repeatability.RE-158 Reset to Trip at 1,068 Psig | | | 05000219/LER-1979-019, Forwards LER 79-019/03L-0 | Forwards LER 79-019/03L-0 | | | 05000219/LER-1979-020, Forwards LER 79-020/01T-0 | Forwards LER 79-020/01T-0 | | | 05000219/LER-1979-020-01, /01T-0 on 790613:secondary Containment Integrity Breached When Reactor Bldg Airlock Doors Were Opened Simultaneously.Caused by Failure of Procedure to State Correct Method for Securing Airlock Doors.Procedure Revised | /01T-0 on 790613:secondary Containment Integrity Breached When Reactor Bldg Airlock Doors Were Opened Simultaneously.Caused by Failure of Procedure to State Correct Method for Securing Airlock Doors.Procedure Revised | | | 05000219/LER-1979-021-03, /03L-0 on 790620:during Surveillance Testing Activities,Instrument 1P15A Was Found to Trip at Valve Higher than Allowed by Tech Specs.Instrument Found to Be within Expected Accuracy Attainable | /03L-0 on 790620:during Surveillance Testing Activities,Instrument 1P15A Was Found to Trip at Valve Higher than Allowed by Tech Specs.Instrument Found to Be within Expected Accuracy Attainable | | | 05000219/LER-1979-021, Forwards LER 79-021/03L-0 | Forwards LER 79-021/03L-0 | | | 05000219/LER-1979-022, Forwards LER 79-022/03L-0 | Forwards LER 79-022/03L-0 | | | 05000219/LER-1979-022-03, /03L-0 on 790627:leak Detected on Emergency Svc Water Side of Containment Spray Heat Exchanger 1-2.Caused by Leaking Nipple Connection Between Water Box & Piping to Valve V-3-83,due to Corrosion.Nipple Replaced | /03L-0 on 790627:leak Detected on Emergency Svc Water Side of Containment Spray Heat Exchanger 1-2.Caused by Leaking Nipple Connection Between Water Box & Piping to Valve V-3-83,due to Corrosion.Nipple Replaced | | | 05000219/LER-1979-023-01, /01T-0 on 790719:reactor Power Was Reduced Above Value for Removal of a Feedwater String.Caused by Removal of Recirculating Pump Reactor for Maint.Inboard & Outboard Collector Rings Resurfaced & Pump Returned to Svc | /01T-0 on 790719:reactor Power Was Reduced Above Value for Removal of a Feedwater String.Caused by Removal of Recirculating Pump Reactor for Maint.Inboard & Outboard Collector Rings Resurfaced & Pump Returned to Svc | | | 05000219/LER-1979-023, Forwards LER 79-023/01T-0 | Forwards LER 79-023/01T-0 | | | 05000219/LER-1979-024, Forwards LER 79-024/03L-0 | Forwards LER 79-024/03L-0 | | | 05000219/LER-1979-024-03, /03L-0:on 790730,control Rod Drive Pump a Discovered Spraying Water Through Seal.Caused by Failure of Mechanical Seal.Inboard Mechanical Seal & Inboard Bearing Replaced | /03L-0:on 790730,control Rod Drive Pump a Discovered Spraying Water Through Seal.Caused by Failure of Mechanical Seal.Inboard Mechanical Seal & Inboard Bearing Replaced | | | 05000219/LER-1979-025, Forwards LER 79-025/03L-0 | Forwards LER 79-025/03L-0 | | | 05000219/LER-1979-025-03, /03L-0:on 790806,10,000 Gallons of Torus Water Drained & Ability of Primary Containment Degraded.Caused by Isolation Valve Left Open After Water Samplings.Change to Sampling Procedure Submitted on Use of Valve | /03L-0:on 790806,10,000 Gallons of Torus Water Drained & Ability of Primary Containment Degraded.Caused by Isolation Valve Left Open After Water Samplings.Change to Sampling Procedure Submitted on Use of Valve | | | 05000219/LER-1979-026-03, /03L-0:on 790807,while Excavating to Repair Equipment Drain Tank Line,Leak in Laundry Tank Discharge Pipe Discovered.Caused by Levels of Mn-54 & Co-60.Line Temporarily Rerouted Until Repairs Made | /03L-0:on 790807,while Excavating to Repair Equipment Drain Tank Line,Leak in Laundry Tank Discharge Pipe Discovered.Caused by Levels of Mn-54 & Co-60.Line Temporarily Rerouted Until Repairs Made | | | 05000219/LER-1979-026, Forwards LER 79-026/03L-0 | Forwards LER 79-026/03L-0 | | | 05000219/LER-1979-027, Forwards LER 79-027/01T-0 | Forwards LER 79-027/01T-0 | | | 05000219/LER-1979-027-01, /01T-0 on 790807:four Seismic restraints,NZ-2-R5 NZ-2R7,NZ-2-R8 & NZ-2-R9,in Positions Other than Required by Original Design.Caused by Improper Installation & Damage Due to Unrestrained Pipe Movement | /01T-0 on 790807:four Seismic restraints,NZ-2-R5 NZ-2R7,NZ-2-R8 & NZ-2-R9,in Positions Other than Required by Original Design.Caused by Improper Installation & Damage Due to Unrestrained Pipe Movement | | | 05000219/LER-1979-028, Forwards LER 79-028/03L-0 | Forwards LER 79-028/03L-0 | | | 05000219/LER-1979-028-03, /03L-0:on 790807,during Routine Surveillance of Core Spray Sys 1,parallel Isolation Valve V-20-15 Became Inoperable in Open Position.Caused by High Motor Current Drawn When Close Signal Inadvertently Initiated | /03L-0:on 790807,during Routine Surveillance of Core Spray Sys 1,parallel Isolation Valve V-20-15 Became Inoperable in Open Position.Caused by High Motor Current Drawn When Close Signal Inadvertently Initiated | | | 05000219/LER-1979-029, Forwards LER 79-029/03L-0 | Forwards LER 79-029/03L-0 | | | 05000219/LER-1979-029-03, /03L-0:on 790822,rod Block Trip Setting Was Below 100 Counts Per Second 26 Times During QA Audit.Caused by Calibr Procedure Setting Rod Trip at Tech Spec Limit.Rod Withdrawal Block Setpoint Increased | /03L-0:on 790822,rod Block Trip Setting Was Below 100 Counts Per Second 26 Times During QA Audit.Caused by Calibr Procedure Setting Rod Trip at Tech Spec Limit.Rod Withdrawal Block Setpoint Increased | | | 05000219/LER-1979-030, Revised Attachment to LER 79-030/03L-0:on 790812,control Rod Drive Pump a Removed from Svc for Repair of Pump Vent Piping.Piping Cracked at Bushing at Entry to Pump Casing. Caused by Operator Carelessness.Bushing Replaced | Revised Attachment to LER 79-030/03L-0:on 790812,control Rod Drive Pump a Removed from Svc for Repair of Pump Vent Piping.Piping Cracked at Bushing at Entry to Pump Casing. Caused by Operator Carelessness.Bushing Replaced | | | 05000219/LER-1979-030-03, /03L-0:on 790812,control Rod Drive Pump Removed from Svc Due to Excessive Leakage from Pump Vent Piping. Piping Was Cracked at Bushing.Caused by Use of Vent Line as Operator Foot Support.Bushing & Pipe Nipple Replaced | /03L-0:on 790812,control Rod Drive Pump Removed from Svc Due to Excessive Leakage from Pump Vent Piping. Piping Was Cracked at Bushing.Caused by Use of Vent Line as Operator Foot Support.Bushing & Pipe Nipple Replaced | | | 05000219/LER-1979-031, Forwards LER 79-031/03L-0 | Forwards LER 79-031/03L-0 | | | 05000219/LER-1979-031-03, /03L-0:on 790829,seal Water Piping Found Cracked on Short Pipe Nipple Section Where Threaded Into Seal Cartridge.Caused by Operator Using half-inch Piping as Foot Support.Pipe Nipple Replaced | /03L-0:on 790829,seal Water Piping Found Cracked on Short Pipe Nipple Section Where Threaded Into Seal Cartridge.Caused by Operator Using half-inch Piping as Foot Support.Pipe Nipple Replaced | | | 05000219/LER-1979-032, Forwards LER 79-032/03L-0 | Forwards LER 79-032/03L-0 | | | 05000219/LER-1979-032-03, /03L-0:on 790914,leaks Discovered in Both Containment Spray Sys.Caused by Corrosion Accelerated by Galvanic Action.Matl Change in Nipple Recommended | /03L-0:on 790914,leaks Discovered in Both Containment Spray Sys.Caused by Corrosion Accelerated by Galvanic Action.Matl Change in Nipple Recommended | | | 05000219/LER-1979-033, Forwards LER 79-033/03L-0 | Forwards LER 79-033/03L-0 | | | 05000219/LER-1979-033-03, /03L-0:on 790917,electromatic Relief Valve Pressure Switch 1A83A Tripped at Pressure in Excess of Limit.Caused by Defective High Pressure Microswitch. Replacement Switch Installed | /03L-0:on 790917,electromatic Relief Valve Pressure Switch 1A83A Tripped at Pressure in Excess of Limit.Caused by Defective High Pressure Microswitch. Replacement Switch Installed | | | 05000219/LER-1979-034, Forwards LER 79-034/01T-0 | Forwards LER 79-034/01T-0 | | | 05000219/LER-1979-034-01, /01T-0:on 791008,both Personnel Access Air Lock 15ors of Reactor Bldg Were Simultaneoulsy Open.Caused by Contractor Personnel Disconnecting Automatic Closing Device on One Door.Device Reconnected | /01T-0:on 791008,both Personnel Access Air Lock 15ors of Reactor Bldg Were Simultaneoulsy Open.Caused by Contractor Personnel Disconnecting Automatic Closing Device on One Door.Device Reconnected | | | 05000219/LER-1979-035, Forwards LER 79-035/03L-0 | Forwards LER 79-035/03L-0 | | | 05000219/LER-1979-035-03, /03L-0:on 790926,during Normal Operation,Reading on Main Steam Line Radiation Monitor Lower than Other Three Monitors.Caused by Drift of Zero Setpoint of Amplifier in Monitor.Setpoint Reset to Zero | /03L-0:on 790926,during Normal Operation,Reading on Main Steam Line Radiation Monitor Lower than Other Three Monitors.Caused by Drift of Zero Setpoint of Amplifier in Monitor.Setpoint Reset to Zero | |
|