Forwards IE Bulletin 79-17, Pipe Cracks in Stagnant Borated Water Sys at PWR Plants. No Action Required
ML19207B571
Person / Time
Site: Big Rock Point File:Consumers Energy icon.png
Issue date: 07/26/1979
From: James Keppler
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION III)
To: Dewitt R
CONSUMERS ENERGY CO. (FORMERLY CONSUMERS POWER CO.)
References
NUDOCS 7908300399
Download: ML19207B571 (1)


Text

.

pa arcoq'o UNITED STATES

),g,'g NUCLEAR REGULATORY COMMISSION

'[l r

REGION 111

._8 799 ROOSEVELT ROAD 6

0,

[

%, ' Av

,o GLEN ELLYN, ILLINolS 6o137

+....

JUL 2 61979 Docket No. 50-155

?

donsumers Power Company ATTN:

Mr. R. B. DeWitt Manager of Nuclear Plant Operations 212 West Michigan Avenue Jackson, MI 49201 Gentlemen:

The enclosed IE Bulletin No. 79-17 is forwarded to you for information. No written response is required. However, the potential corrosion behavior of safety related systems as it regards your plant over the long term should be taken into consideration. If you desire additional information concerning this matter, please contact this office.

Sincerely, FJames G. y u A.

(>

o. b Kefpier Director

Enclosure:

IE Bulletin No. 79-17 cc w/ enc 1:

Mr. C. J. Hartman, Plant Superintendent Central Files Director, NRR/DPM Director, NRR/ DOR PDR Local PDR NSIC TIC Ronald Callen, Michigan Public Service Commission Anthony Roisman, Esq., Attorney 85R gjj 79083 003Q

i UNITED STATES NUCLEAR REGULATORY COMMISSION E

" " v L E! M B.^ P. zi'08"i" =

July 26*, 1979,

'f,

IE Bulletin Wo. 79-17 PIPE CRACKS IN STAGNANT BORATED WATER SYSTDiS AT PWR PLANTS DeschiptionofCircumstances:

During the period of November 1974 to February 1977 a number of cracking incidents have been experienced in safety-related stainless steel piping systems and portions of systems which contain oxygenated, stagnant or essentially stagnant borated water. Metallurgical investigations revealed these cracks occurred in the veld heat affected zone of 8-inch to 10-inch type 304 material (schedule 10 and 40), initiating on the piping I.D. surface and propagating in either an intergranular or transgranular mode typical of Stress Corrosion Cracking. Analysis indicated the probable corrodents to be chloride and oxygen contamination in the affected systems. Plants affected up to this time were Arkansas Nuclear Unit 1. R. E. Ginna, H.B. Robinson Unit 2. Crystal River Unit 3 San Onofre Unit 1, and Surry Units 1 and 2.

The NRC issued Circular 76-06 (copy attached) in view of the apparent generic nature of the prcblem.

During the refueling outage of Three Mile Island Unit 1 which began in February of this year, visual inspections disclosed five (5) through-wall cracks at velds in the spent fuel cooling system piping and one (1) at a weld in the decay heat removal system. These cracks were found as a result of local boric acid build-up and later confirmed by liquid penetrant tests. This initial identification of cracking was reported to the NRC in a Licensee Event Report (LER) dated May 16, 1979. A preliminary metallurgical analysis was performed by the licensee on a section of cracked and leaking veld joint from the spent fuel cooling system.

The. conclusion of this analysis was that cracking was due to Intergranular Stress Corrosion Cracking (IGSCC) originating on the pipe I.D.

The cracking was localized to the heat affected zone where the type 304 stainless steel is sensitized (precipitated carbides) during velding. In addition to the main through-wall crack, incipient cracks were observed at several locations in the veld heat affected zone including the veld root fusion area where a miniscule lack of fusion had occurred. The stresses responsible for cracking are believed to be primarily residual welding stresses in as much as the calculated applied stresses were found to be less than code design limits. There is no conclusive evidence at this time to identify those aggressive chemical species which promoted this IGSCC attack. Further analytical efforts in this area and on othar system welds are being pursued.