IERA pa a f c.,,

e y,

UNrTED STATES y;

( (,g NUCLEAR REGULATORY COMMISSION E

WASHINGT ON, D. C. 20555 a

,g II 8

o August 8,1979 Docket No. 50-219 Mr. I. R. Finfrock, Jr.

Vice President - Generation Jersey Central Power & Light Company Madison Avenue at Punch Bowl Road Morristown, New Jersey 07960

Dear Mr. Finfrock:

We have reviewed your letters of April 7, August 1, and September 22, 1978 concerning incomplete items (Section 3.2) of our Fire Protection Safety Eval:ation Report dated March 3, 1978.

Additional information is required to compkte our review of these items.

Please provide the infonnation identified in the enclosure along with the Section 3.1 data you have scheduled to send to us August 31, 1979.

Sincerely, Dennis L. Ziemann, Chief Operating Reactors Branch #2 Division of Operating Reactors

Enclosure:

Request for Additional Infonnation cc:

See next page o

b t

i 790821 W T$

"r.

1. R. rinfreck, Jr.

_p_

Auonet R. 107c CC G. F. Trowbridge, Esquire Shaw, Pittman, Potts and Trowbridge 1800 M Street, N. W.

'Ja shi ngton, D. C.

20036 GPU Service Corporation ATTN:

Mr. E. G. Wallace Licensing Manager 260 Cherry Hill Road Parsippany, New Jersey 07054 Anthony Z. Roisman Natural Resources Defense Council 91715th Street, N. W.

Washington, D. C.

20005 5teven P. Russo, Esquire 2481,'ashington Street P. O. Box 1060 Toms River, New Jersey 08753 Joseph W. Ferraro, Jr., Esquire Deputy Attorney General State of New Jersey Department of Law and Public Safety 1100 Raymond Boul evard Newark, New Jersey 07012 Ocean County Library Brick Township Branch 401 Chanbers Bridge Road Brick Town, New Jersey 08723 4

REQUEST FOR ADDITIONAL INFORMATION FIRt PROTECTION EVALUATION OY' STER CREEK HUCLEAR GENERATING STATION DOCKET No. 50-219 SER Item q

3.2.1 Administrative Controls I UUit d

Provide an 'mplementation schedule for changes '.o procedures identified in JCP&L letters of April 7,1978 and September 22, 1978 concerning administrative controls.

3.2.2 Raddaste Fires The radwaste facility evaluation provided by letter of April 7,1978 indicates that solid wastes are stored in drums, but that there is an accumulation of combustible contaminateo material waiting to be compacted.

Provida the results of an evaluation in terms of off-site releases for a fire that consumes these combustibles.

3 2.3 Fire Barrier Penetrations The JCP&L letter of August 1,1978 provides an analysis a.

of fire barrier penetration protection.

Certain electrical cable penetration seals are to be upgraded to a 3-hoce fire rating.

Identify the construction of the new or modified cable penetration fire seals, and provide the results of tests to demonstrate the rating of these seals.

b.

The above analysis indicates that the doors to the control room are being upgraded for security purposes, bJt will not be 3-ho r fi re ra ted doors.

It apptars fror the drawings that all such doors are into corricors and not into other sa' :ty related arets or into the turbine building.

Verify that no doors are provided between

.e turbine building and control room.

Provide an implementation schedule for completion of fire c.

door and penetration modifications.

3.2.4 Cormunications Equioment The JCP&L letter indicates that a modification to :ne co munications system will be made to provide co = unications ben.een the co trol room and all safety related areas, and ina the use of a -epeater system was being cor.sidered to provide inis ta: ability.

Please identify the rodification tha:

111 be used and th e inplerentation date for completion of this rodi#ication.

78'(S 49