Mr. Bradley J. Sawatzke Chief Executive Officer Energy Northwest 76 North Power Plant Loop P.O. Box 968 (Mail Drop 1023)
Richland, WA 99352 UNITED STATES WASHfNGTON, O.C. 20555-0001 June 20, 2019
SUBJECT:
COLUMBIA GENERA TING STATION - ISSUANCE OF AMENDMENT NO. 253 RE: RENEWED FACILITY OPERATING LICENSE AND TECHNICAL SPECIFICATION CLEAN UP (EPID L-2018-LLA-0176)
Dear Mr. Sawatzke:
The U.S. Nuclear Regulatory Commission (the Commission) has issued the enclosed Amendment No. 253 to Renewed Facility Operating License No. NPF-21 for the Columbia Generating Station. The amendment consists of changes to the Technical Specifications (TSs) in response to your application dated June 12, 2018 (Agencywide Documents Access and Management System (ADAMS) Accession No. ML18163A351 ), as supplemented by letter dated August 7, 2018 (ADAMS Accession No. ML18219C797).
The amendment revises the Columbia renewed facility operating license and technical specifications, including editorial changes and the removal of obsolete information.
A copy of the related Safety Evaluation is also enclosed. The Notice of Issuance will be included in the Commission's biweekly Federal Register notice.
Docket No. 50-397
Enclosures:
- 1. Amendment No. 253 to NPF-21
- 2. Safety Evaluation cc: Listserv L. ohn os, Project Manager Plant Licensing Branch IV Division of Operating Reactor Licensing Office of Nuclear Reactor Regulation
WASHINGTON, O.C. 20555-0001 ENERGY NORTHWEST DOCKET NO. 50-397 COLUMBIA GENERA TING STATION AMENDMENT TO RENEWED FACILITY OPERATING LICENSE Amendment No. 253 License No. NPF-21
- 1.
The Nuclear Regulatory Commission (the Commission) has found that:
A The application for amendment by Energy Northwest (licensee), dated June 12, 2018, as supplemented by letter dated August 7, 2018, complies with the standards and requirements of the Atomic Energy Act of 1954, as amended (the Act) and the Commission's rules and regulations set forth in 10 CFR Chapter I; B.
The facility will operate in conformity with the application, the provisions of the Act, and the rules and regulations of the Commission; C.
There is reasonable assurance (i) that the activities authorized by this amendment can be conducted without endangering the health and safety of the public, and (ii) that such activities will be conducted in compliance with the Commission's regulations; D.
The issuance of this amendment will not be inimical to the common defense and security or to the health and safety of the public; and E.
The issuance of this amendment is in accordance with 10 CFR Part 51 of the Commission's regulations, and all applicable requirements have been satisfied.
- 2.
Accordingly, the license is amended by changes to the Technical Specifications as indicated in the attachment to this license amendment, and paragraph 2.C.(2) of Renewed Facility Operating License No. NPF-21 is hereby amended to read as follows:
(2)
Technical Specifications and Environmental Protection Plan The Technical Specifications contained in Appendix A, as revised through Amendment No. 253 and the Environmental Protection Plan contained in Appendix B, are hereby incorporated in the license. The licensee shall operate the facility in accordance with the Technical Specifications and the Environmental Protection Plan.
- 3.
The license amendment is effective as of its date of issuance and shall be implemented within 90 days from the date of issuance.
Attachment:
Changes to the Renewed Facility Operating License No. NPF-21 and Technical Specifications FOR THE NUCLEAR REGULA TORY COMMISSION Robert J. Pascarelli, Chief Plant Licensing Branch IV Division of Operating Reactor Licensing Office of Nuclear Reactor Regulation
. Date of Issuance:
June 2 o, 2 o 1 9
A TI ACHMENT TO LICENSE AMENDMENT NO. 253 RENEWED FACILITY OPERATING LICENSE NO. NPF-21 COLUMBIA GENERATING STATION DOCKET NO. 50-397 Replace the following pages of the Renewed Facility Operating License No. NPF-21 and Appendix A, Technical Specifications, with the attached revised pages. The revised pages are identified by amendment number and contain vertical lines indicating the areas of change.
Renewed Facility Operating License REMOVE Attachment 1 INSERT Technical Specification REMOVE ii iii iv 1.1-5 3.1.6-2 3.2.4-1 3.2.4-2 3.3.1.1-1 through 3.3.1.1-181 3.3. 1.3-1 3.3.1.3-2 3.3.2.1-1 through 3.3.2.1-131 3.3.6.1-4 3.3.6.1-7 3.3.6.1-8 3.3.6.1-9 3.3.8.1-3 3.4.1-1 through 3.4. 1-41 3.5.1-1 3.10.8-1 through 3. 10.8-71 5.5-3 5.6-2 INSERT 1.1-5
- 3. 1.6-2 3.3.1.1-1 through 3.3.1.1-102 3.3.2.1-1 through 3.3.2.1-72 3.3.6. 1-4 3.3.6.1-7 3.3.6.1-8 3.3.6.1-9 3.3.8.1-3 3.4.1-1 through 3.4.1-22 3.5.1-1 3.10.8-1 through 3.10.8-32 5.5-3 5.6-2 1 Prior to Implementation of Power Range Neutron Monitor (PRNM) Upgrade 2 After Implementation of PRNM Upgrade (2)
Technical Specifications and Environmental Protection Plan The Technical Specifications contained in Appendix A, as revised through Amendment No. 253 and the Environmental Protection Plan contained in Appendix B,are hereby incorporated in the renewed license. The licensee shall operate the facility in accordance with the Technical Specifications and the Environmental Protection Plan.
- a. For Surveillance Requirements (SRs) not previously performed by existing SRs or other plant tests, the requirement will be considered met on the implementation date and the next required test will be at the interval specified in the Technical Specifications as revised in Amendment No. 149.
( 3)
Deleted.
(4)
Deleted.
(5)
Deleted.
(6)
Deleted.
(7)
Deleted.
(8)
Deleted.
(9)
Deleted.
(10)
Deleted.
(11)
Shield Wall Deferral (Section 12.3.2, SSER #4, License Amendment #7)
The licensee shall complete construction of the deferred shield walls and window as identified in Attachment 3, as amended by this license amendment.
(12)
Deleted.
(13)
Deleted.
- The parenthetical notation following the title of many license conditions denotes the section of the Safety Evaluation Report and/or its supplements wherein the license condition is discussed.
Renewed License No. NPF-21 Amendment No. 253 (33)
Deleted Renewed License No. NPF-21 Amendment No. ~253
1.1 Definitions LINEAR HEAT GENERATION RATE (LHGR)
LOGIC SYSTEM FUNCTIONAL TEST MINIMUM CRITICAL POWER RA TIO (MCPR)
MODE OPERABLE - OPERABILITY PHYSICS TESTS Columbia Generating Station Definitions 1.1 The LHGR shall be the heat generation rate per unit length of fuel rod. It is the integral of the heat flux over the heat transfer area associated with the unit length.
A LOGIC SYSTEM FUNCTIONAL TEST shall be a test of all required logic components (i.e., all required relays and contacts, trip units, solid state logic elements, etc.) of a logic circuit, from as close to the sensor as practicable up to, but not including, the actuated device, to verify OPERABILITY. The LOGIC SYSTEM FUNCTIONAL TEST may be performed by means of any series of sequential, overlapping, or total system steps so that the entire logic system is tested.
The MCPR shall be the smallest critical power ratio (CPR) that exists in the core for each class of fuel. The CPR is that power in the assembly that is calculated by application of the appropriate correlation(s) to cause some point in the assembly to experience boiling transition, divided by the actual assembly operating power.
A MODE shall correspond to any one inclusive combination of mode switch position, average reactor coolant temperature, and reactor vessel head closure bolt tensioning specified in Table 1.1-1 with fuel in the reactor vessel.
A system, subsystem, division, component, or device shall be OPERABLE or have OPERABILITY when it is capable of performing its specified safety function(s) and when all necessary attendant instrumentation, controls, normal or emergency electrical power, cooling and seal water, lubrication, and other auxiliary equipment that are required for the system, subsystem, division, component, or device to perform its specified safety function(s) are also capable of performing their related support function(s).
PHYSICS TESTS shall be those tests performed to measure the fundamental nuclear characteristics of the reactor core and related instrumentation. These tests are:
- a.
Described in Chapter 14, Initial Test Program of the FSAR;
- b.
Authorized under the provisions of 10 CFR 50.59; or 1.1-5 Amendment No.489 ~. ~
~
2&1-253
ACTIONS CONDITION REQUIRED ACTION B. (continued)
B.2 Place the reactor mode switch in the shutdown position.
SURVEILLANCE REQUIREMENTS SR 3.1.6.1 SURVEILLANCE Verify all OPERABLE control rods comply with BPWS.
Rod Pattern Control 3.1.6 COMPLETION TIME 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br /> FREQUENCY In accordance with the Surveillance Frequency Control Program Columbia Generating Station 3.1.6-2 Amendment No. 449,469 ~
~
253
3.3 INSTRUMENTATION 3.3.1.1 Reactor Protection System (RPS) Instrumentation RPS Instrumentation 3.3.1.1 LCO 3.3.1.1 The RPS instrumentation for each Function in Table 3.3.1.1-1 shall be OPERABLE.
APPLICABILITY:
According to Table 3.3.1.1-1 ACTIONS
NO TE---------------------------------------------------
Separate Condition entry is allowed for each channel.
CONDITION REQUIRED ACTION COMPLETION TIME A. One or more required A.1 Place channel in trip.
12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> channels inoperable.
NOTE--------------
Not applicable for Functions 2.a, 2.b, 2.c, 2.d, or 2.f.
A.2 Place associated trip 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> system in trip.
NOTE--------~--
8.1 Place channel in one trip 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> Not applicable for system in trip.
Functions 2.a, 2.b, 2.c, 2.d, or 2.f.
OR 8.2 Place one trip system in 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br />
- 8. One or more Functions trip.
with one or more required channels inoperable in both trip systems.
Columbia Generating Station 3.3.1.1-1 Amendment No.~~~ 253
ACTIONS CONDITION C. One or more Functions with RPS trip capability not maintained.
D. Required Action and associated Completion Time of Condition A, B, or C not met.
E. As required by Required Action D.1 and referenced in Table 3.3.1.1-1.
F. As required by Required Action D.1 and referenced in Table 3.3.1.1-1.
G. As required by Required Action D.1 and referenced in Table 3.3.1.1-1.
H. As required by Required Action D.1 and referenced in Table 3.3.1.1-1.
Columbia Generating Station C. 1 D.1 E.1 F.1 G.1 H.1 REQUIRED ACTION Restore RPS trip capability.
Enter the Condition referenced in Table 3.3.1.1-1 for the channel.
Reduce THERMAL POWER to< 29.5% RTP.
Be in MODE 2.
Be in MODE 3.
Initiate action to fully insert all insertable control rods in core cells conta!ning one or more fuel assemblies.
RPS Instrumentation 3.3.1.1 COMPLETION TIME 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br /> Immediately 4 hours4.62963e-5 days <br />0.00111 hours <br />6.613757e-6 weeks <br />1.522e-6 months <br /> 6 hours 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> Immediately 3.3.1.1-2 Amendment No. 4W ~
~
253
ACTIONS CONDITION I.
As required by Required 1.1 Action D.1 and referenced in Table 3.3.1.1-1.
AND 1.2 J. Required Action and J.1 associated Completion Time of Condition I not met.
SURVEILLANCE REQUIREMENTS REQUIRED ACTION Initiate alternate method to detect and suppress thermal hydraulic instability oscillations.
-~----~-~-NOTE-~----------
LCO 3.0.4 is not applicable.
Restore required channels to OPERABLE.
Reduce THERMAL POWER to less than the value specified in the COLR.
RPS Instrumentation 3.3.1.1 COMPLETION TIME 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> 120 days 4 hours4.62963e-5 days <br />0.00111 hours <br />6.613757e-6 weeks <br />1.522e-6 months <br />
~--~-~-~-~----------~--~~---~-~--~-NOTES-----~---~-~-~-----~-~----~--------~-------~--~
- 1.
Refer to Table 3.3.1.1-1 to determine which SRs apply for each RPS Function.
- 2.
When a channel is placed in an inoperable status solely for performance of required Surveillances, entry into associated Conditions and Required Actions may be delayed for up to 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> provided the associated Function maintains RPS trip capability.
SURVEILLANCE SR 3.3.1.1.1 Perform CHANNEL CHECK.
Columbia Generating Station 3.3.1.1-3 FREQUENCY In accordance with the Surveillance Frequency Control Program Amendment No. 4eQ. ~
~
253
SURVEILLANCE REQUIREMENTS SR 3.3.1.1.2 SR 3.3.1.1.3 SR 3.3.1.1.4 SR 3.3.1.1.5 SR 3.3.1.1.6 SURVEILLANCE
NOTE-----------
Not required to be performed until 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> after THERMAL POWER;?: 25% RTP.
Verify the absolute difference between the average power range monitor (APRM) channels and the calculated power :;; 2% RTP while operating at
- ?
- 25% RTP.
NOTE-------------
Not required to be performed when entering MODE 2 from MODE 1 until 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> after entering MODE2.
Perform CHANNEL FUNCTIONAL TEST.
Perform CHANNEL FUNCTIONAL TEST.
Verify the source range monitor (SRM) and intermediate range monitor (IRM) channels overlap.
NOTE---------------
Only required to be met during entry into MODE 2 from MODE 1.
Verify the IRM and APRM channels overlap.
RPS Instrumentation 3.3.1.1 FREQUENCY In accordance with the Surveillance Frequency Control Program In accordance with the Surveillance Frequency Control Program In accordance with the Surveillance Frequency Control Program Prior to withdrawing SRMs from the fully inserted position In accordance with the Surveillance Frequency Control Program Columbia Generating Station 3.3.1.1-4 Amendment No. 479 225 226 253
SURVEILLANCE REQUIREMENTS SURVEILLANCE SR 3.3.1.1.7 Calibrate the local power range monitors.
SR 3.3.1.1.8 Perform CHANNEL FUNCTIONAL TEST.
SR 3.3.1.1.9 Deleted.
SR 3.3.1.1.10
~----~--~--------~-~----NOTES--~-----~-~--~-~~----
- 1.
Neutron detectors are excluded.
- 2.
For Function 1, not required to be performed when entering MODE 2 from MODE 1 until 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> after entering MODE 2.
- 3.
For Functions 2.b and 2.f, the recirculation flow transmitters that feed the APRMs are included.
Perform CHANNEL CALIBRATION.
SR 3.3.1.1.11 Deleted.
SR 3.3.1.1.12 Verify Turbine Throttle Valve - Closure, and Turbine Governor Valve Fast Closure Trip Oil Pressure - Low Functions are not bypassed when THERMAL POWER is 2 29.5% RTP.
SR 3.3.1.1.13 Perform CHANNEL FUNCTIONAL TEST.
RPS Instrumentation 3.3.1.1 FREQUENCY In accordance with the Surveillance Frequency Control Program In accordance with the Surveillance Frequency Control Program In accordance with the Surveillance Frequency Control Program In accordance with the Surveillance Frequency Control Program In accordance with the Surveillance Frequency Control Program Columbia Generating Station 3.3.1.1-5 Amendment No. 469 ~
~
253
SURVEILLANCE REQUIREMENTS SR 3.3.1.1.14 SR 3.3.1.1.15 SR 3.3.1.1.16 SR 3.3.1.1.17 SURVEILLANCE Perform LOGIC SYSTEM FUNCTIONAL TEST.
~-~~---------~-~-~-NOTES~--~-----~~~-~--~--
- 1.
Neutron detectors are excluded.
- 2.
Channel sensors for Functions 3 and 4 are excluded.
Verify the RPS RESPONSE TIME is within limits.
---~--~---------~~------~NOTES------------~~-~----~-
- 1.
For Function 2.a, not required to be performed when entering MODE 2 from MODE 1 until 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> after entering MODE 2.
- 2.
For Functions 2.b and 2.f, the CHANNEL FUNCTIONAL TEST includes the recirculation flow input processing, excluding the flow transmitters.
Perform CHANNEL FUNCTIONAL TEST.
Verify the OPRM is not bypassed when APRM Simulated Thermal Power is greater than or equal to the value specified in the COLR and recirculation drive flow is less than the value specified in the COLR.
RPS Instrumentation 3.3.1.1 FREQUENCY In accordance with the Surveillance Frequency Control Program In accordance with the Surveillance Frequency Control Program In accordance with the Surveillance Frequency Control Program In accordance with the Surveillance Frequency Control Program Columbia Generating Station 3.3.1.1-6 Amendment No. 499 ~*~
253
RPS Instrumentation Table 3.3.1.1-1 (page 1 of 4)
Reactor Protection System Instrumentation APPLICABLE CONDITIONS MODES OR REQUIRED REFERENCED OTHER CHANNELS FROM SPECIFIED PER TRIP REQUIRED SURVEILLANCE FUNCTION CONDITIONS SYSTEM ACTION D.1 REQUIREMENTS
- 1.
- a.
Neutron Flux - High 2
3 G
SR 3.3.1. 1.1 SR 3.3.1.1.3 SR 3.3.1.1.5 SR 3.3.1.1.6 SR 3.3.1.1.10 SR 3.3.1.1.14 5<*)
3 H
SR 3.3.1.1.1 SR 3.3.1.1.4 SR 3.3.1.1.10 SR 3.3.1.1.14
- b.
lnop 2
3 G
SR 3.3.1.1.3 SR 3.3.1.1.14 5(*)
3 H
SR 3.3.1.1.4 SR 3.3.1.1.14
- 2.
Average Power Range Monitors
- a.
Neutron Flux - High 2
3(b)
G SR 3.3.1.1.1 (Setdown)
SR 3.3.1.1.6 SR 3.3.1.1.7 SR 3.3.1.1.1 O(dl.<*l SR 3.3.1.1.16
- b.
Simulated Thermal 3(b)
F SR 3.3.1.1.1 Power-High SR 3.3.1.1.2 SR 3.3.1.1.7 SR 3.3.1.1.1 O(dl,(*l SR 3.3.1.1.16 (a)
With any control rod withdrawn from a core cell containing one or more fuel assemblies.
(b)
Each APRM/OPRM channel provides inputs to both trip systems.
3.3.1.1 ALLOWABLE VALUE s 122/125 divisions of full scale s 122/125 divisions of full scale NA NA s20% RTP s 0.62W + 62.9% RTP ands 114.9% RTP(cl (c)
$ 0.62W + 59.8% RTP and :5 114.9% RTP when reset for single loop operation per LCO 3.4.1, "Recirculation Loops Operating."
(d) If the as-found channel setpoint is outside its predefined as-found tolerance, then the channel shall be evaluated to verify that it is functioning as required before returning the channel to service.
(e)
The instrument channel setpoint shall be reset to a value that is within the as-left tolerance around the Limiting Trip Setpoint (L TSP) at the completion of the surveillance; otherwise, the channel shall be declared inoperable.
Setpoints more conservative than the L TSP are acceptable provided that the as-found and as-left tolerances apply to the actual setpoint implemented in the surveillance procedures (Nominal Trip Setpoint) to confirm channel performance. The L TSP and the methodologies used to determine the as-found and as-left tolerances are specified in the Licensee Controlled Specifications.
Columbia Generating Station 3.3.1.1-7 Amendment No. 22& 226 ~
253
RPS Instrumentation 3.3.1.1 Table 3.3.1.1-1 (page 2 of 4)
Reactor Protection System Instrumentation FUNCTION
- 2.
Average Power Range Monitors
- c.
Neutron Flux - High
- d.
lnop
- e.
2-0ut-of-4 Voter
- f.
OPRM Upscale APPLICABLE MODES OR OTHER SPECIFIED CONDITIONS 1,2 1,2 (f)
REQUIRED CHANNELS PER TRIP SYSTEM 2
CONDITIONS REFERENCED FROM REQUIRED ACTION 0.1 F
G G
(b)
Each APRM/OPRM channel provides inputs to both trip systems.
SURVEILLANCE REQUIREMENTS SR 3.3.1.1.1 SR 3.3.1.1.2 SR 3.3.1.1.7 SR 3.3.1.1.1 o<dl,<*>
SR 3.3.1.1.16 SR 3.3.1.1.16 SR 3.3.1.1.1 SR 3.3.1.1.14 SR 3.3.1.1.15 SR 3.3.1.1.16 SR 3.3.1.1.1 SR 3.3.1.1.7 SR 3.3.1.1.1 o<dl,<*l SR 3.3.1.1.16 SR 3.3.1.1.17 ALLOWABLE VALUE s 120% RTP NA NA (d) If the as-found channel setpoint is outside its predefined as-found tolerance, then the channel shall be evaluated to verify that it is functioning as required before returning the channel to service.
(e)
The instrument channel setpoint shall be reset to a value that is within the as-left tolerance around the Limiting Trip Setpoint (L TSP) at the completion of the surveillance; otherwise, the channel shall be declared inoperable.
Setpoints more conservative than the L TSP are acceptable provided that the as-found and as-left tolerances apply to the actual setpoint implemented in the surveillance procedures (Nominal Trip Setpoint) to confirm channel performance. The L TSP and the methodologies used to determine the as-found and as-left tolerances are specified in the Licensee Controlled Specifications.
(f)
THERMAL POWER greater than or equal to the value specified in the COLR.
(g)
The OPRM Upscale does not have an Allowable Value. The Period Based Detection Algorithm (PBDA) trip setpoints are specified in the COLR.
Columbia Generating Station 3.3.1.1-8 Amendment No. ~
~
253
RPS Instrumentation 3.3.1.1 Table 3.3.1.1-1 (page 3 of 4)
Reactor Protection System Instrumentation APPLICABLE CONDITIONS MODES OR REQUIRED REFERENCED OTHER CHANNELS FROM SPECIFIED PER TRIP REQUIRED SURVEILLANCE ALLOWABLE FUNCTION CONDITIONS SYSTEM ACTION D.1 REQUIREMENTS VALUE
- 3.
Reactor Vessel Steam 1,2 2
G SR 3.3.1.1.8 s 1079 psig Dome Pressure - High SR 3.3.1.1.10 SR 3.3.1.1.14 SR 3.3.1.1.15
- 4.
Reactor Vessel Water 1,2 2
- 9.5 inches Level - Low, Level 3 SR 3.3.1.1.8 SR 3.3.1.1.10 SR 3.3.1.1.14 SR 3.3.1.1.15
- 5.
F SR 3.3.1.1.8 s 12.5% closed
- Closure SR 3.3.1.1.10 SR 3.3.1.1.14 SR 3.3.1.1.15
- 6.
Primary Containment 1,2 2
G SR 3.3.1.1.8 s 1.88 psig Pressure - High SR 3.3.1.1.10 SR 3.3.1.1.14
- 7.
Scram Discharge Volume Water Level - High
- a.
Transmitter/Level 1,2 2
G SR 3.3.1.1.1 s 529 ft 9 inches Indicating Switch SR 3.3.1.1.8 elevation SR 3.3.1.1.10 SR 3.3.1.1.14 5<*)
2 H
SR 3.3.1.1.1 s 529 ft 9 inches SR 3.3.1.1.8 elevation SR 3.3.1.1.10 SR 3.3.1.1.14
- b.
Transmitter/Level 1,2 2
G SR 3.3.1.1.8 s 529 ft 9 inches Switch SR 3.3.1.1.1 o<dlC*I elevation SR 3.3.1.1.14 5<*)
2 H
SR 3.3.1.1.8 s 529 ft 9 inches SR 3.3.1.1.1 o<dlC*l elevation SR 3.3.1.1.14 (a)
With any control rod withdrawn from a core cell containing one or more fuel assemblies.
(d)
If the as-found channel setpoint is outside its predefinded as-found tolerance, then the channel shall be evaluated to verify that it is functioning as required before returning the channel to service.
(e)
The instrument channel setpoint shall be reset to a value that is within the as-left tolerance around the Limiting Trip Setpoint (L TSP) at the completion of the surveillance; otherwise, the channel shall be declared inoperable.
Setpoints more conservative than the L TSP are acceptable provided that the as-found and as-left tolerances apply to the actual setpoint implemented in the surveillance procedures (Nominal Trip Setpoint) to confirm channel performance. The L TSP and the methodologies used to determine the as-found and the as-left tolerances are specified in the Licensee Controlled Specifications.
Columbia Generating Station 3.3.1.1-9 Amendment No. 469 22& ~
253
Table 3.3.1.1-1 (page 4 of 4)
RPS Instrumentation 3.3.1.1 Reactor Protection System Instrumentation APPLICABLE CONDITIONS MODES OR REQUIRED REFERENCED OTHER CHANNELS FROM SPECIFIED PER TRIP REQUIRED SURVEILLANCE ALLOWABLE FUNCTION CONDITIONS SYSTEM ACTION D.1 REQUIREMENTS VALUE
- 8.
Turbine Throttle Valve -
229.5% RTP 4
E SR 3.3.1.1.8 s 7% closed Closure SR 3.3.1.1.10 SR 3.3.1.1.12 SR 3.3.1.1.14 SR 3.3.1.1.15
- 9.
Turbine Governor Valve 229.5% RTP 2
E SR 3.3.1.1.8 2 1000 psig Fast Closure, Trip Oil SR 3.3.1.1.10 Pressure - Low SR 3.3.1.1.12 SR 3.3.1.1.14 SR 3.3.1.1.15
- 10.
Reactor Mode Switch -
1,2 2
G SR 3.3.1.1.13 NA Shutdown Position SR 3.3.1.1.14 5(a) 2 H
SR 3.3.1.1.13 SR 3.3.1.1.14 NA
- 11.
Manual Scram 1,2 2
G SR 3.3.1.1.4 NA SR 3.3.1.1.14 5(a) 2 H
SR 3.3.1.1.4 NA SR 3.3.1.1.14 (a)
With any control rod withdrawn from a core cell containing one or.more fuel assemblies.
Columbia Generating Station 3.3.1.1-10 Amendment No. ~
~
~
~
253
3.3 INSTRUMENTATION Control Rod Block Instrumentation 3.3.2.1 3.3.2.1 Control Rod Block Instrumentation LCO 3.3.2.1 The control rod block instrumentation for each Function in Table 3.3.2.1-1 shall be OPERABLE.
APPLICABILITY:
According to Table 3.3.2.1-1.
ACTIONS CONDITION REQUIRED ACTION COMPLETION TIME A. One rod block monitor A.1 Restore RBM channel to 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> (RBM) channel OPERABLE status.
B. Required Action and B.1 Place one RBM channel in 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br /> associated Completion trip.
Time of Condition A not met.
OR Two RBM channels inoperable.
C. Rod worth minimizer C. 1 Suspend control rod Immediately (RWM) inoperable movement except by during reactor startup.
OR C.2.1.1 Verify :2: 12 rods withdrawn.
Immediately OR Columbia Generating Station 3.3.2.1-1 Amendment No. 469 22a ~
253
ACTIONS CONDITION C. (continued)
D. RWM inoperable during reactor shutdown.
E. One or more Reactor Mode Switch - Shutdown Position channels inoperable.
Columbia Generating Station REQUIRED ACTION Control Rod Block Instrumentation 3.3.2.1 COMPLETION TIME C.2.1.2 Verify by administrative Immediately methods that startup with RWM inoperable has not been performed in the last calendar year.
AND C.2.2 Verify movement of control During control rod rods is in compliance with movement banked position withdrawal sequence (BPWS) by a second licensed operator or other qualified member of the technical staff.
D.1 Verify movement of control During control rod rods is in compliance with movement BPWS by a second licensed operator or other qualified member of the technical staff.
E.1 Suspend control rod Immediately withdrawal.
AND E.2 Initiate action to fully insert Immediately all insertable control rods in core cells containing one or more fuel assemblies.
3.3.2.1-2 Amendment No. 4-eS ~
22e 253
Control Rod Block Instrumentation 3.3.2.1 SURVEILLANCE REQUIREMENTS
--~------~---------~-~----------------~-~---~-~----N()TES--------~-----~--------------------------~----~---
- 1.
Refer to Table 3.3.2.1-1 to determine which SRs apply for each Control Rod Block Function.
- 2.
When an RBM channel is placed in an inoperable status solely for performance of required Surveillances, entry into associated Conditions and Required Actions may be delayed for up to 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> provided the associated Function maintains control rod block capability.
SR 3.3.2.1.1 SR 3.3.2.1.2 SR 3.3.2.1.3 SURVEILLANCE Perform CHANNEL FUNCTl()NAL TEST.
NC) TE-----------------------------
Not required to be performed until 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br /> after any control rod is withdrawn at s 10% RTP in M()DE 2.
Perform CHANNEL FUNCTl()NAL TEST.
~------------------------N()TE-----------------------------
Not required to be performed until 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br /> after THERMAL P()WER is s 10% RTP in M()DE 1.
Perform CHANNEL FUNCTl()NAL TEST.
FREQUENCY In accordance with the Surveillance Frequency Control Program In accordance with the Surveillance Frequency Control Program In accordance with the Surveillance Frequency Control Program Columbia Generating Station 3.3.2.1-3 Amendment No. ~
~
22& 253
Control Rod Block Instrumentation 3.3.2.1 SURVEILLANCE REQUIREMENTS SR 3.3.2.1.4 SR 3.3.2.1.5 SR 3.3.2.1.6 SURVEILLANCE
~--~------------~--~------N()TE----~--~-~------~~-~-~-
Neutron detectors are excluded.
Verify the RBM is not bypassed:
- a.
Low Power Range - Upscale Function is not "bypassed when APRM Simulated Thermal Power is ~ 28% and < 63% RTP and peripheral control rod is not selected.
- b.
Intermediate Power Range - Upscale Function is not bypassed when APRM Simulated Thermal Power is ~ 63% and < 83% RTP and peripheral control rod is not selected.
- c.
High Power Range - Upscale Function is not bypassed when APRM Simulated Thermal Power is ~ 83% and peripheral control rod is not selected.
--~-~---~-~----------~-~N()TE--~~~-~----~-~~--~--
Neutron detectors are excluded.
Perform CHANNEL CALI BRA Tl()N.
Verify the RWM is not bypassed when THERMAL P()WER is :s:: 10% RTP.
FREQUENCY In accordance with the Surveillance Frequency Control Program In accordance with the Surveillance Frequency Control Program In accordance with the Surveillance Frequency Control Program Columbia Generating Station 3.3.2.1-4 Amendment No. 4-79 ~
22e 253
Control Rod Block Instrumentation 3.3.2.1 SURVEILLANCE REQUIREMENTS SR 3.3.2.1. 7 SR 3.3.2.1.8 SURVEILLANCE
-~~----~-----~----------~-N()TE-----~------~--~-----~---
Not required to be performed until 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br /> after reactor mode switch is in the shutdown position.
Perform CHANNEL FUNCTl()NAL TEST.
Verify control rod sequences input to the RWM are in conformance with BPWS.
FREQUENCY In accordance with the Surveillance Frequency Control Program Prior to declaring RWM ()PERABLE following loading of sequence into RWM Columbia Generating Station 3.3.2.1-5 Amendment No. 499 ~
~253
Control Rod Block Instrumentation 3.3.2.1 Table 3.3.2.1-1 (page 1 of 2)
Control Rod Block Instrumentation APPLICABLE MODES OR OTHER SPECIFIED REQUIRED SURVEILLANCE ALLOWABLE FUNCTION CONDITIONS C.HANNELS REQUIREMENTS VALUE
- 1.
Rod Block Monitor
- a.
Low Power Range - Upscale (a) 2 SR 3.3.2.1.1 (f)
SR 3.3.2.1.4 SR 3.3.2.1.S(d),(e)
- b.
Intermediate Power Range -
(b) 2 SR 3.3.2.1.1 (f)
Upscale SR 3.3.2.1.4 SR 3.3.2.1.S(d),(e)
C.
High Power Range - Upscale (c) 2 SR 3.3.2.1.1 (f)
SR 3.3.2.1.4 SR 3.3.2.1.S(d),(e)
- d.
lnop (a),(b),(c) 2 SR 3.3.2.1.1 NA (a) APRM Simulated Thermal Power is.:: 28% and < 63% RTP and MCPR is less than the limit specified in the COLR and no peripheral control rod selected.
(b) APRM Simulated Thermal Power is.:: 63% and< 83% RTP and MCPR is less than the limit specified in the COLR and no peripheral control rod selected.
(c)
APRM Simulated Thermal Power is.:: 83% and MCPR is less than the limit specified in the COLR and no peripheral control rod selected.
(d) If the as-found channel setpoint is outside its predefined as-found tolerance, then the channel shall be evaluated to verify that it is functioning as required before returning the channel to service.
(e)
The instrument channel setpoint shall be reset to a value that is within the as-left tolerance around the Limiting Trip Setpoint (L TSP) at the completion of the surveillance; otherwise, the channel shall be declared inoperable.
Setpoints more conservative than the L TSP are acceptable provided that the as-found and as-left tolerances apply to the actual setpoint implemented in the surveillance procedures (Nominal Trip Setpoint) to confirm channel performance. The L TSP and the methodologies used to determine the as-found and as-left tolerances are specified in the Licensee Controlled Specifications.
(f)
Allowable Value Specified in the COLR.
Columbia Generating Station 3.3.2.1-6 Amendment No. ~
253
Control Rod Block Instrumentation 3.3.2.1 Table 3.3.2.1-1 (page 2 of 2)
Control Rod Block Instrumentation FUNCTION
- 2.
- 3.
Reactor Mode Switch - Shutdown Position (g)
With THERMAL POWER$; 10% RTP.
APPLICABLE MODES OR OTHER SPECIFIED REQUIRED CONDITIONS CHANNELS (h) 2 (h)
Reactor mode switch in the shutdown position.
SURVEILLANCE REQUIREMENTS SR 3.3.2.1.2 SR 3.3.2.1.3 SR 3.3.2.1.6 SR 3.3.2.1.8 SR 3.3.2.1.7 ALLOWABLE VALUE NA NA Columbia Generating Station 3.3.2.1-7 Amendment No. 4eS ~
~
253
Primary Containment Isolation Instrumentation 3.3.6.1 SURVEILLANCE REQUIREMENTS SURVEILLANCE FREQUENCY SR 3.3.6.1.2 Perform CHANNEL FUNCTIONAL TEST.
In accordance with the Surveillance Frequency Control Program SR 3.3.6.1.3 Perform CHANNEL FUNCTIONAL TEST.
In accordance with the Surveillance Frequency Control Program SR 3.3.6.1.4 Perform CHANNEL CALIBRATION.
In accordance with the Surveillance Frequency Control Program SR 3.3.6.1.5 Perform CHANNEL CALIBRATION.
In accordance with the Surveillance Frequency Control Program SR 3.3.6.1.6 Perform LOGIC SYSTEM FUNCTIONAL TEST.
In accordance with the Surveillance Frequency Control Program SR 3.3.6.1. 7
~-~--~--~---~---~--~----NOTE-----------~~--~-----------
Channel sensors for Functions 1.a, 1.b, and 1.c are excluded.
Verify the ISOLATION SYSTEM RESPONSE TIME In accordance is within limits.
with the Surveillance Frequency Control Program Columbia Generating Station 3.3.6.1-4 Amendment No. 4§{},4e9 ~
~
253
Primary Containment Isolation Instrumentation 3.3.6.1 Table 3.3.6.1-1 (page 3 of 6)
Primary Containment Isolation Instrumentation APPLICABLE CONDITIONS MODES OR REQUIRED REFERENCED OTHER CHANNELS FROM SPECIFIED PER TRIP REQUIRED SURVEILLANCE ALLOWABLE FUNCTION CONDITIONS SYSTEM ACTION C.1 REQUIREMENTS VALUE
- 3.
RCIC System Isolation
- e.
RCIC Equipment 1, 2, 3 F
SR 3.3.6.1.3 s 180°F Room Area SR 3.3.6.1.4 Temperature - High SR 3.3.6.1.6
- f.
RCIC Equipment 1, 2, 3 1
F SR 3.3.6.1.3 s 60°F Room Area SR 3.3.6.1.4 Differential SR 3.3.6.1.6 Temperature - High
- g.
Reactor Water 1, 2, 3 1
F SR 3.3.6.1.3 s 180°F Cleanup (RWCU)
SR 3.3.6.1.4 System /RCIC SR 3.3.6.1.6 Steam Line Routing Area Temperature -
High
- h.
Manual Initiation 1, 2, 3 1(b)
G SR 3.3.6.1.6 NA
- 4.
RWCU System Isolation
- a.
1, 2, 3 F
SR 3.3.6.1.1 s 67.4 gpm High SR 3.3.6.1.2 SR 3.3.6.1.5 SR 3.3.6.1.6
- b.
1, 2, 3 1
F SR 3.3.6.1.2 s 46.5 seconds Time Delay SR 3.3.6.1.5 SR 3.3.6.1.6 C.
Slowdown Flow -
1,2,3 1
F SR 3.3.6.1.1 s 271.7 gpm High SR 3.3.6.1.2 SR 3.3.6.1.5 SR 3.3.6.1.6 SR 3.3.6.1.7
- d.
Heat Exchanger 1, 2, 3 1
F SR 3.3.6.1.3 s 160°F Room Area SR 3.3.6.1.4 Temperature - High SR 3.3.6.1.6 (b)
RCIC Manual Initiation only inputs into one of the two trip systems.
Columbia Generating Station 3.3.6.1-7 Amendment No. 4-e-9,4-n ~
253
Primary Containment Isolation Instrumentation 3.3.6.1 Table 3.3.6.1-1 (page 4 of 6)
Primary Containment Isolation Instrumentation APPLICABLE CONDITIONS MODES OR REQUIRED REFERENCED OTHER CHANNELS FROM SPECIFIED PER TRIP REQUIRED SURVEILLANCE ALLOWABLE FUNCTION CONDITIONS SYSTEM ACTION C.1 REQUIREMENTS VALUE
- 4.
RWCU System Isolation
- e.
Heat Exchanger 1, 2, 3 1
- s: 70°F Room Area SR 3.3.6.1.4 Ventilation SR 3.3.6.1.6 Differential Temperature - High
- f.
Pump Room Area 1, 2, 3 1 per room F
- s: 180°F Temperature - High SR 3.3.6.1.4 SR 3.3.6.1.6
- g.
Pump Room Area 1, 2, 3 1 per room F
- s: 100°F Ventilation SR 3.3.6.1.4 Differential SR 3.3.6.1.6 Temperature - High
- h.
RWCU/RCIC Line 1, 2, 3 1
- s: 180°F Routing Area SR 3.3.6.1.4 Temperature - High SR 3.3.6.1.6
- i.
RWCU Line Routing 1, 2, 3 1 per room F
SR 3.3.6.1.3 Area Temperature -
SR 3.3.6.1.4 High SR 3.3.6.1.6 Room 409, 509
- s: 175°F Areas Room 408, 511
- s: 180°F Areas
- j.
Reactor Vessel 1, 2, 3 2
~ -58 inches Water Level - Low SR 3.3.6.1.4 Low, Level 2 SR 3.3.6.1.6
- k.
Standby Liquid 1, 2, 3 2(c)
SR 3.3.6.1.6 NA Control (SLC)
System Initiation I.
Manual Initiation 1,2, 3 2
G SR 3.3.6.1.6 NA (c)
SLC System Initiation only inputs into one of the two trip systems.
Columbia Generating Station 3.3.6.1-8 Amendment No. ~.49-9 22a 253
Primary Containment Isolation Instrumentation 3.3.6.1 Table 3.3.6.1-1 (page 5 of 6)
Primary Containment Isolation Instrumentation APPLICABLE CONDITIONS MODES OR REQUIRED REFERENCED OTHER CHANNELS FROM SPECIFIED PER TRIP REQUIRED SURVEILLANCE ALLOWABLE FUNCTION CONDITIONS SYSTEM ACTION C.1 REQUIREMENTS VALUE
- 5.
Residual Heat Removal (RHR) Shutdown Cooling (SDC) System Isolation
- a.
Pump Room Area 3
1 per room F
SR 3.3.6.1.3 s 150°F Temperature - High SR 3.3.6.1.4 SR 3.3.6.1.6
- b.
Pump Room Area 3
1 per room F
SR 3.3.6.1.3 s 70°F Ventilation SR 3.3.6.1.4 Differential SR 3.3.6.1.6 Temperature - High C.
Heat Exchanger 3
1 per room F
SR 3.3.6.1.3 Area Temperature -
SR 3.3.6.1.4 High SR 3.3.6.1.6 Room 505 Area s 140°F Room 507 Area s 160°F Room 605 Area s 150°F Room 606 Area s 140°F
- d.
Reactor Vessel 3
2 J
~ 9.5 inches Water Level - Low, SR 3.3.6. 1.2 Level3 SR 3.3.6. 1.4 SR 3.3.6. 1.6
- e.
Reactor Vessel 1, 2, 3 1
F SR 3.3.6. 1.2 s 135 psig Pressure - High SR 3.3.6.1.4 SR 3.3.6. 1.6
- f.
Manual Initiation 1, 2, 3 2
G SR 3.3.6.1.6 NA (d)
Deleted Columbia Generating Station 3.3.6.1-9 Amendment No. 4e4,4e9 ~
~
253
SURVEILLANCE REQUIREMENTS SURVEILLANCE SR 3.3.8.1.2 Perform CHANNEL CALIBRATION.
SR 3.3.8.1.3 Perform CHANNEL CALIBRATION.
SR 3.3.8.1.4 Perform LOGIC SYSTEM FUNCTIONAL TEST.
LOP Instrumentation 3.3.8.1 FREQUENCY In accordance with the Surveillance Frequency Control Program In accordance with the Surveillance Frequency Control Program In accordance with the Surveillance Frequency Control Program Columbia Generating Station 3.3.8.1-3 Amendment No. 449,469 ~
~
253
Recirculation Loops Operating 3.4.1 3.4 REACTOR COOLANT SYSTEM (RCS) 3.4.1 Recirculation Loops Operating LCO 3.4.1 Two recirculation loops with matched flows shall be in operation.
OR One recirculation loop shall be in operation provided that the following limits are applied when the associated LCO is applicable:
- a.
LCO 3.2.1, "AVERAGE PLANAR LINEAR HEAT GENERATION RATE (APLHGR)," single loop operation limits specified in the COLR;
- b.
LCO 3.2.2, "MINIMUM CRITICAL POWER RATIO (MCPR)," single loop operation limits specified in the COLR; and
- c.
LCO 3.3.1.1, "Reactor Protection System (RPS) Instrumentation,"
Function 2.b (Average Power Range Monitors, Simulated Thermal Power - High), Allowable Value of Table 3.3.1.1-1 is reset for single loop operation.
APPLICABILITY:
MODES 1 and 2 ACTIONS CONDITION REQUIRED ACTION COMPLETION TIME A. Recirculation loop flow A.1 Declare the recirculation 2 hours2.314815e-5 days <br />5.555556e-4 hours <br />3.306878e-6 weeks <br />7.61e-7 months <br /> mismatch not within loop with lower flow to be limits.
"not in operation."
B. Requirements of the B.1 Satisfy the requirements of 4 hours4.62963e-5 days <br />0.00111 hours <br />6.613757e-6 weeks <br />1.522e-6 months <br /> LCO not met for reasons the LCO.
other than Condition A.
Columbia Generating Station 3.4.1-1 Amendment No. ~
~
229 253
Recirculation Loops Operating 3.4.1 ACTIONS CONDITION REQUIRED ACTION C. Required Action and C.1 Be in MODE 3.
associated Completion Time of Condition A or B not met.
OR No recirculation loops in operation.
SURVEILLANCE REQUIREMENTS SR 3.4.1.1 SURVEILLANCE
~----~--~~-------~--NOTE---~---~~----~-~---------
Not required to be performed until 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> after both recirculation loops are in operation.
Verify recirculation loop drive flow mismatch with both recirculation loops in operation is:
- a.
~ 10% of rated recirculation loop drive flow when operating at < 70% of rated core flow; and
- b.
~ 5% of rated recirculation loop drive flow when operating at 2 70% of rated core flow.
COMPLETION TIME 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> FREQUENCY In accordance with the Surveillance Frequency Control Program Columbia Generating Station 3.4.1-2 Amendment No. 4-74 ~
22e 253
ECCS - Operating 3.5.1 3.5 EMERGENCY CORE COOLING SYSTEMS (ECCS), RPV WATER INVENTORY CONTROL, AND REACTOR CORE !SOLA TION COOLING (RCIC) SYSTEM 3.5.1 ECCS - Operating LCO 3.5.1 Each ECCS injection/spray subsystem and the Automatic Depressurization System (ADS) function of six safety/relief valves shall be OPERABLE.
APPLICABILITY:
MODE 1, MODES 2 and 3, except ADS valves are not required to be OPERABLE with reactor steam dome pressure ~ 150 psig.
ACTIONS
---~~-~--~-----~--------~--~--~-~--~---~----~---NOTE-~---~----~~-~-~-------~-~-~-~----~~-~-----
LCO 3.0.4.b is not applicable to High Pressure Core Spray (HPCS).
CONDITION REQUIRED ACTION COMPLETION TIME A One low pressure ECCS A.1 Restore low pressure 7 days<1>
injection/spray ECCS injection/spray subsystem inoperable.
subsystem to OPERABLE status.
B High Pressure Core B.1 Verify by administrative Immediately Spray (HPCS) System means RCIC System is inoperable.
OPERABLE when RCIC System is required to be OPERABLE.
AND B.2 Restore HPCS System to 14 days OPERABLE status.
<1> The Completion Time that one train of RHR (RHR-A) can be inoperable as specified by Required Action A.1 may be extended beyond the 7 day completion time up to 7 days to support restoration of RHR-A following pump and motor replacement. This footnote will expire at 23:59 PST February 28, 2019.
Columbia Generating Station 3.5.1-1 Amendment No. 437 ~
~
~
2§4 253
SOM Test-Refueling 3.10.8 3.10 SPECIAL OPERATIONS 3.10.8 SHUTDOWN MARGIN (SOM) Test - Refueling LCO 3.10.8 APPLICABILITY:
The reactor mode switch position specified in Table 1.1-1 for MODE 5 may be changed to include the startup/hot standby position, and operation considered not to be in MODE 2, to allow SOM testing, provided the following requirements are met:
- a.
LCO 3.3.1.1, "Reactor Protection System (RPS) Instrumentation,"
MODE 2 requirements for Functions 2.a, 2.d, and 2.e of Table 3.3.1.1-1;
- b.
- 1.
LCO 3.3.2.1, "Control Rod Block Instrumentation," MODE 2 requirements for Function 2 of Table 3.3.2.1-1, with banked position withdrawal sequence requirements of SR 3.3.2.1.8 changed to require the control rod sequence to conform to the SOM test sequence,
- 2.
Conformance to the approved control rod sequence for the SOM test is verified by a second licensed operator or other qualified member of the technical staff;
- c.
Each withdrawn control rod shall be coupled to the associated control rod drive (CRD);
- d.
All control rod withdrawals during out of sequence control rod moves shall be made in notch out mode;
- e.
No other CORE AL TERA TIONS are in progress; and
- f.
CRD charging water header pressure ~ 940 psig.
MODE 5 with the reactor mode switch in startup/hot standby position.
Columbia Generating Station 3.10.8-1 Amendment No. 4-eS ~
~
253
ACTIONS CONDITION REQUIRED ACTION A -----------NOTE----------
NOTE------------
Separate Condition entry Rod worth minimizer may be is allowed for each bypassed as allowed by control rod.
LCO 3.3.2.1, "Control Rod Block Instrumentation," if required, to allow insertion of inoperable control One or more control rod and continued operation.
rods not coupled to its associated CRD.
A.1 Fully insert inoperable control rod.
AND A.2 Disarm the associated CRD.
B. One or more of the B.1 Place the reactor mode above requirements not switch in the shutdown or met for reasons other refuel position.
than Condition A.
SURVEILLANCE REQUIREMENTS SR 3.10.8.1 SURVEILLANCE Perform the MODE 2 applicable SRs for LCO 3.3.1.1, Functions 2.a, 2.d, and 2.e of Table 3.3.1.1-1.
SOM Test-Refueling 3.10.8 COMPLETION TIME 3 hours3.472222e-5 days <br />8.333333e-4 hours <br />4.960317e-6 weeks <br />1.1415e-6 months <br /> 4 hours Immediately FREQUENCY According to the applicable SRs SR 3.10.8.2
NO TE---------------------------
Not required to be met if SR 3.10.8.3 satisfied.
Perform the MODE 2 applicable SRs for LCO 3.3.2.1, Function 2 of Table 3.3.2.1-1.
According to the applicable SRs Columbia Generating Station 3.10.8-2 Amendment No. 4-88 ~
~
253
SURVEILLANCE REQUIREMENTS SR 3.10.8.3 SR 3.10.8.4 SR 3.10.8.5 SR 3.10.8.6 SURVEILLANCE
~-~-~~----~----~-~-~-N()TE-~---~~~-~---~~---~-~
Not required to be met if SR 3.10.8.2 satisfied.
Verify movement of control rods is in compliance with the approved control rod sequence for the SOM test by a second licensed operator or other qualified member of the technical staff.
Verify no other C()RE AL TERA Tl()NS are in progress.
Verify each withdrawn control rod does not go to the withdrawn overtravel position.
Verify CRD charging water header pressure
- 940 psig.
SOM Test-Refueling 3.10.8 FREQUENCY During control rod movement In accordance with the Surveillance Frequency Control Program Each time the control rod is withdrawn to "full out" position Prior to satisfying LC() 3.10.8.c requirement after work on control rod or CRD System that could affect coupling In accordance with the Surveillance Frequency Control Program Columbia Generating Station 3.10.8-3 Amendment No. 4eQ. ~
229 253
5.5 Programs and Manuals 5.5.4 Radioactive Effluent Controls Program (continued)
Programs and Manuals 5.5
- e.
Determination of cumulative and projected dose contributions from radioactive effluents for the current calendar quarter and current calendar year in accordance with the methodology and parameters in the ODCM at least every 31 days;
- f.
Limitations on the functional capability and use of the liquid and gaseous effluent treatment systems to ensure that appropriate portions of these systems are used to reduce releases of radioactivity when the projected doses in a period of 31 days would exceed 2% of the guidelines for the annual dose or dose commitment, conforming to 10 CFR 50, Appendix I;
- g.
Limitations on the dose rate resulting from radioactive material released in gaseous effluents from the site to areas at or beyond the site boundary shall be limited to the following:
- 1.
For noble gases: less than or equal to a dose rate of 500 mrems/yr to the whole body and less than or equal to a dose rate of 3000 mrems/yr to the skin, and
- 2.
For iodine-131, iodine-133, tritium, and for all radionuclides in particulate form with half lives > 8 days: less than or equal to a dose rate of 1500 mrems/yr to any organ;
- h.
Limitations on the annual and quarterly air doses resulting from noble gases released in gaseous effluents from each unit to areas beyond the site boundary, conforming to 10 CFR 50, Appendix I;
- i.
Limitations on the annual and quarterly doses to a member of the public from iodine-131, iodine-133, tritium, and all radionuclides in particulate form with half lives > 8 days in gaseous effluents released from each unit to areas beyond the site boundary, conforming to 10 CFR 50, Appendix I;
- j.
Limitations on the annual dose or dose commitment to any member of the public, beyond the site boundary, due to releases of radioactivity and to radiation from uranium fuel cycle sources, conforming to 40 CFR 190;
- k.
Limitations on venting and purging of the primary containment through the Standby Gas Treatment System to maintain releases as low as reasonably achievable; and I.
The provisions of SR 3.0.2 and SR 3.0.3 are applicable to the Radioactive Effluent Controls Program surveillance frequency.
Columbia Generating Station 5.5-3 Amendment ~.482 ~
253
Reporting Requirements 5.6 5.6 Reporting Requirements 5.6.3 CORE OPERATING LIMITS REPORT (COLR)
- a.
Core operating limits shall be established prior to each reload cycle, or prior to any remaining portion of a reload cycle, and shall be documented in the COLR for the following:
- 1.
The APLHGR for Specification 3.2.1;
- 2.
The MCPR for Specification 3.2.2;
- 3.
The LHGR for Specification 3.2.3;
- 4.
Deleted;
- 5.
The Oscillation Power Range Monitor (OPRM) Instrumentation for Specification 3.3.1.1; and
- 6.
The Rod Block Monitor Instrumentation for Specification 3.3.2.1.
- b.
The analytical methods used to determine the core operating limits shall be those previously reviewed and approved by the NRC, specifically those described in the following documents:
- 1.
XN-NF-81-58(P)(A), "RODEX2 Fuel Rod Thermal-Mechanical Response Evaluation Model," Exxon Nuclear Company
- 2.
XN-NF-85-67(P)(A), "Generic Mechanical Design for Exxon Nuclear Jet Pump BWR Reload Fuel," Exxon Nuclear Company
- 3.
EMF-85-74(P) Supplement 1(P)(A) and Supplement 2(P)(A),
"RODEX2A (BWR) Fuel Rod Thermal-Mechanical Evaluation Model,"
Siemens Power Corporation
- 4.
ANF-89-98(P)(A), "Generic Mechanical Design Criteria for BWR Fuel Designs," Advanced Nuclear Fuels Corporation
- 5.
XN-NF-80-19(P)(A) Volume 1, "Exxon Nuclear Methodology for Boiling Water Reactors - Neutronic Methods for Design and Analysis,"
Exxon Nuclear Company
- 6.
XN-NF-80-19(P)(A) Volume 4, "Exxon Nuclear Methodology for Boiling Water Reactors: Application of the ENC Methodology to BWR Reloads," Exxon Nuclear Company Columbia Generating Station 5.6-2 Amendment No. 4W ~
22e 253
WASHINGTON, D.C. 20555-0001 SAFETY EVALUATION BY THE OFFICE OF NUCLEAR REACTOR REGULATION RELATED TO AMENDMENT NO. 253 TO RENEWED FACILITY OPERATING LICENSE NO. NPF-21 ENERGY NORTHWEST COLUMBIA GENERA TING STATION DOCKET NO. 50-397
1.0 INTRODUCTION
By application dated June 12, 2018 (Agencywide Documents Access and Management System (ADAMS) Accession No. ML18163A351 ), as supplemented by letter dated August 7, 2018 (ADAMS Accession No. ML18219C797), Energy Northwest (the licensee) requested changes to the Technical Specifications (TSs) for Columbia Generating Station (Columbia).
The proposed changes to the renewed facility operating license (RFOL) and TSs are administrative and editorial and will not result in any change to the technical or operating requirements at Columbia.
2.0 REGULATORY EVALUATION
2.1
System Description
The license amendment request proposes to remove the Table of Contents from the Columbia TSs and place it under licensee control, as well as a number of editorial changes to the RFOL and TSs, including removal of an obsolete operating license condition and operating license attachments, removal of obsolete TS information, and renumbering of TS pages. The licensee stated that neither the proposed administrative changes nor the proposed editorial changes result in changes to technical or operating requirements at Columbia.
2.2 Description of the Proposed Changes 2.2.1 Proposed TS Changes The specific changes the licensee proposed to the TSs are as follows:
- 1.
Remove the Table of Contents from the TSs and place it under the licensee's control;
- 2.
Remove TS 3.2.4, "Average Power Range Monitor (APRM) Gain and Setpoint," and TS 3.3.1.3, "Oscillation Power Range Monitor (OPRM) Instrumentation";
- 3.
Remove the definition "Maximum Fraction of Limiting Power Density (MFLPD)," from TS Section 1.1, "Definitions";
- 4.
Remove portions of TS 3.3.1.1 "Reactor Protection System (RPS) Instrumentation";
TS 3.3.2.1 "Control Rod Block Instrumentation"; TS 3.4.1 "Recirculation Loops Operating"; and TS 3.10.8, Shutdown Margin (SOM) Test - Refueling," containing the header, "Prior to implementation of PRNM [Power Range Neutron Monitor] Upgrade,"
which includes:
- a.
The removal of TS pages 3.3.1.1-1 through 3.3.1.1-8, 3.3.2.1-1 through 3.3.2.1-6, 3.4.1-1 through 3.4.1-2, and 3.10.8-1 through 3.10.8-4; and
- b.
The removal of the remaining TSs containing the header language, "After implementation of PRNM Upgrade," and the text "after implementation of Power Range Neutron Monitor (PRNM) upgrade," from the APPLICABILITY. The remaining TS pages would be renumbered to 3.3.1.1-1 through 3.3.1.1-10, 3.3.2.1-1 through 3.3.2.1-7, 3.4.1-1 through 3.4.1-2, and 3.10.8-1 through 3.10.8-3.
- c.
Correct two typographical errors in TS 3.3.1.1, as follows:
- 1)
In TS 3.3.1.1, Required Action 1.2, a period is missing after the word "OPERABLE"; and
- 2)
In TS Table 3.3.1.1-1, "Reactor Protection System Instrumentation" (page 2 of 4), remove extra hard returns after the 'SURVEILLANCE REQUIREMENTS" for Function 2.c., "Neutron Flux - High," and Function 2.d., "lnop."
- 5.
In TS 5.6.3, "Core Operating Limits Report (COLR)," remove TS 5.6.3a.4 and replaced with "Deleted"; and delete the language, "after implementation of the PRNM upgrade," in TSs 5.6.3a.5 and 5.6.3a.6.
- 6.
Typographical errors that would be corrected, as follows:
- a.
In TS 3.1.6, "Rod Pattern Control," a period would be added after the letter "B" in ACTIONS Table, Condition B of the continued page.
- b.
In TS Surveillance Requirement (SR) 3.3.6.1.5 and SR 3.3.8.1.3, a period would be added after the word "CALIBRATION" in the "Surveillance" column.
- c.
In TS Table 3.3.6.1-1, "Primary Containment Isolation Instrumentation" (TS pages 3, 4, and 5 of 6), the acronyms RWCU, SLC, and RHR SDC would be spelled out when they are first used within the Table as follows: Reactor Water Cleanup (RWCU), Standby Liquid Control (SLC), and Residual Heat Removal (RHR) Shutdown Cooling (SDC).
- d.
In the ACTIONS NOTE in TS 3.5.1, "ECCS - Operating," the acronym HPCS*
would be spelled out (High Pressure Core Spray (HPCS)), and
- e.
In TS 5.5.4, "Radioactive Effluent Controls Program," the "and" at the end of the sentence would be removed from TS 5.5.4j, and the period would be deleted and replaced with a semi-colon following the text "and" at the end of TS 5.5.4k.
2.2.2 Proposed Operating License Changes The licensee proposed the following changes to the RFOL:
- 1.
Remove License Condition 2.C.(33), "Control Room Envelope Habitability Program (CRE); and
- 2.
Remove Attachments 1 and 2, the contents of which were deleted previously in Amendment No. 223, dated March 30, 2012 (ADAMS Accession No. ML120800078).
2.3 Regulatory Requirements Section 182a, "License Applications" of the Atomic Energy Act of 1954, as amended (the Act),
requires applicants for nuclear power plants to include an operating license and TSs as part of their application. The U.S. Nuclear Regulatory Commission (NRC or the Commission) regulatory requirements related to the content of the TSs are contained in Title 10 of the Code of Federal Regulations (1 O CFR) Section 50.36, "Technical specifications." Pursuant to 10 CFR 50.36, each operating license issued by the Commission includes TSs and includes items in the appropriate categories.
The regulations in 10 CFR 50.36 contain requirements for what is to be included in the licensee's TSs. The Table of Contents, which contains only administrative information, is not required by 10 CFR 50.36 to be in the TSs.
Section 187 of the Act, "Modification of License," states that the "terms and conditions of all licenses shall be subject to amendment, revision, or modification, by reason of amendments of this Act, or by reason of rules and regulations issued in accordance with the terms of this Act."
This provision authorizes the NRC to amend licenses.
The regulations in 10 CFR 50.50, "Issuance of licenses and construction permits," states, in part, that "the Commission will issue a license... in such form and containing such conditions and limitations including technical specifications, as it deems appropriate and necessary."
In accordance with 10 CFR 50.54, "Conditions of licenses," the operation of a nuclear power plant is authorized by the Commission subject to conditions of operation identified as a result of Commission's evaluation of applications for operating licenses.
Such conditions were placed on the operating license for Columbia, requiring the licensee to address outstanding licensing issues and facilitate issuance of the original operating license.
The original issuance of the Columbia operating license was subject to several additional requirements (license conditions). Additional requirements were incorporated in the license, as required, as a result of ongoing reviews via the license amendment process pursuant to 10 CFR 50.90, "Application for amendment of license, construction permit, or early site permit." In some cases, subsequent license amendments removed certain license conditions when they were no longer applicable. However, the majority of the license conditions have been left intact, including those that are no longer required.
The licensee is proposing administrative changes to the Columbia RFOL to remove or revise those license conditions that no longer apply or have been modified. This proposed RFOL "cleanup" license amendment request also includes minor editorial changes for consistency.
Revision of the RFOL is being proposed to retain only those license conditions that remain pertinent to current Columbia operations.
The NRC staff reviewed the licensee's application for changes to the TSs, Table of Contents, and license conditions. The staff's evaluations and conclusions are summarized below.
3.0 TECHNICAL EVALUATION
3.1 Proposed Table of Contents Change The licensee proposed to revise the Columbia TSs and remove the Table of Contents with the responsibility for maintenance and issuance of updates transferred from the NRC to Energy Northwest. The Table of Contents will no longer be included in the NRC-issued TSs and, as such, will no longer be part of the TSs, Appendix A, to the RFOL. The Table of Contents will be issued by Energy Northwest in conjunction with the implementation of future NRG-approved TS amendments.
The licensee stated that placing the Table of Contents under licensee control eliminates the regulatory burden of submitting Table of Contents pages for NRC review, and allows timely administrative corrections and improvements to the Table of Contents without NRC review and approval.
The NRC staff examined the licensee's proposal to remove the Table of Contents from its TSs and determined that the Table of Contents, per 10 CFR 50.36, is not required to be included within a plant's TSs. The licensee stated that the TS Table of Contents will be maintained, revised, and distributed in accordance with Columbia's administrative procedures and that holders of copies of the TSs, including the NRC, will continue to receive periodic updates of the Table of Contents pages. The NRC staff's review determined that the Table of Contents references the page number of each Specification in the TSs and does not contain any technical information required by 10 CFR 50.36. Because the Table of Contents does not include information required per 10 CFR 50.36, inclusion of a Table of Contents within the TSs is optional. Therefore, the NRC staff concludes that the removal of the Table of Contents from the Columbia TSs is an administrative change and, therefore, is acceptable.
3.2 Proposed TS Changes
3.2.1 TS Change Related to PRNM Upgrade The implementation of the PRNM upgrade was issued in Amendment No. 226, dated January 31, 2014 (ADAMS Accession No. ML13317B623). The amendment was not implemented until prior to plant startup following Refueling Outage 22. The refueling outage was scheduled to begin in the spring of 2015.
In support of the amendment, TSs 3.3.1.1, 3.3.1.3, 3.3.2.1, 3.2.4, 3.4.1, and 3.10.8 were modified to reflect the applicability of "prior to implementation of PRNM upgrade" or "after implementation of PRNM upgrade," as appropriate, and this related header was added to each specification that included the same modification.
The licensee stated that once the PRNM upgrade was installed in the plant, a TS change would be submitted to delete the obsolete TSs and portions thereof. Amendment No. 226 contained recognition that the following information below would be removed from Columbia's TSs after implementation.
- 1.
TSs 3.2.4 and 3.3.1.3 will be deleted as these specifications are obsolete with the implementation of the PRNM upgrade.
- 2.
The definition of MFLPD will be deleted in TS Section 1.1, along with its usage in TS 3.2.4, as this definition is no longer in use at Columbia.
- 3.
TSs 3.3.1.1, 3.3.2.1, 3.4.1, and 3.10.8 contain pages that are applicable "prior to implementation... " and "after implementation... ".
Each portion of these TSs containing the header "Prior to Implementation of PRNM Upgrade" will be deleted. TS pages 3.3.1.1-1 through 3.3.1.1-8, 3.3.2.1-1 through 3.3.2.1-6, 3.4.1-1 through 3.4.1-2, and 3.10.8-1 through 3.10.8-4 will be deleted.
Each of the remaining TSs containing the header language "After Implementation of PRNM Upgrade" will have this language deleted from the header. The language "after implementation of Power Range Neutron Monitor (PRNM) upgrade" would be deleted from the APPLICABILITY. The remaining TS pages will be renumbered to 3.3.1.1-1 through 3.3.1.1-10, 3.3.2.1-1 through 3.3.2.1-7, 3.4.1-1 through 3.4.1-2, and 3.10.8-1 through 3.10.8-3.
- 4.
TS 5.6.3a.4 in TS Section 5.6, "Reporting Requirements," will be deleted. The language "after the PRNM upgrade" will be deleted from TSs 5.6.3a.5 and 5.6.3a.6.
In the late spring of 2015, Columbia conducted Refueling Outage 22. During that outage, the PRNM upgrade was implemented. The licensee stated that since the PRNM upgrade has been implemented, the TS pages that refer to "prior to implementation... "
are obsolete and can be deleted.
Additionally, the licensee proposed to correct two typographical errors in TS 3.3.1.1.
These corrections are related to the implementation above and are, as follows:
In TS 3.3.1.1, Required Action 1.2, a period is missing after the word "OPERABLE."
In TS Table 3.3.1.1-1 (page 2 of 4), there are extra spaces between Function 2.c.,
"Neutron Flux - High," and Function 2.d., "lnop."
The NRC staff examined the licensee's proposal to delete the TS pages related to the PRNM upgrade and concludes that the deletion of pages that refer to "prior to implementation" is acceptable since the PRNM upgrade has been completed. The NRC staff also reviewed the licensee's correction of the two typographical errors related to the implementation of Amendment No. 226 and concludes that the correction is only administrative and, therefore, is acceptable.
3.2.2 Correction of Typographical Errors The licensee proposed the following corrections to the typographical errors in the TSs:
- 1.
In the continued page of the ACTIONS Table, Condition B, in TS 3.1.6, "Rod Pattern Control," the period is missing after "B."
- 2.
In TS SR 3.3.6.1.5 and TS SR 3.3.8.1.3, in the "SURVEILLANCE," the period is missing after the word "CALIBRATION."
- 3.
In TS Table 3.3.6.1-1, "Primary Containment Isolation" (pages 3, 4, and 5 of 6), the acronyms RWCU (Function 4), SLC (Function 4.k) and RHR SOC (Function 5) will be spelled out when they are first used within the table as Reactor Water Cleanup (RWCU),
Standby Liquid Control (SLC), and Residual Heat Removal (RHR) Shutdown Cooling (SDC).
- 4.
In TS 3.5.1, "ECCS - Operating," the ACTIONS NOTE, the acronym HPCS (High Pressure Core Spray) will be spelled out because it is the first use of this acronym within the TS.
- 5.
In TS 5.5.4, "Radioactive Effluent Controls Program," the "and" will be deleted from TS 5.5.4j. The period will be deleted in TS 5.5.4k and replaced with a semi-colon following the text "and" (; and) at the end of TS 5.5.4k.
The NRC staff further reviewed the licensee's correction of typographical errors and concludes that the corrections are administrative and are supported by the Technical Specifications Task Force (TSTF) guidance in TSTF-GG-05-01, "Writer's Guide for Plant-Specific Improved Technical Specifications," dated June 2005 (ADAMS Accession No. ML060720511) and, therefore, are acceptable.
3.3 Proposed Changes to the RFOL 3.3.1 Removal of License Condition 2.C.(33), "Control Room Envelope Habitability Program (CRE)"
The licensee stated that the first performances of the associated control room envelope habitability surveillance, assessment, and measurement are complete. Successive performances of the surveillances, assessments, and measurements will follow the respective frequencies identified in TS 5.5.14c and 5.5.14d. The licensee stated that with the first performances complete for Columbia, the operating license conditions are no longer required and can be removed.
The NRC staff reviewed the licensee's proposal to remove License Condition 2.C.(33). The licensee completed the license condition as follows:
License Condition Specification Completion Date 2.C.(33)(a) 5.5.14c(i) 11/17/2010 2.C.(33)(b) 5.5.14c(ii) 6/24/2010 2.C.(33)(c) 5.5.14d - System A 3/18/2010 2.C.(33)(c) 5.5.14d - System B 12/6/2011 Based on completion of the license condition, the NRC staff concludes that it is acceptable to remove it from the TSs.
3.3.2 Removal of Attachments 1 and 2 In Amendment No. 223 dated March 30, 2012, Columbia's operating license was modified to delete the contents of Attachments 1 and 2. However, the attachments themselves were retained. The licensee proposes to remove these attachment pages from the Columbia RFOL.
The NRC staff reviewed the licensee's proposal to remove Attachments 1 and 2 from Columbia's RFOL. The staff finds that the removal of these attachments is administrative since the license conditions related to these Attachments were deleted previously in Amendment No. 223. Therefore, the staff concludes that the removal of Attachments 1 and 2 is acceptable.
3.4 Summary Based on the licensee's license amendment request and its supplement for this amendment, the NRC staff finds that the licensee's proposed changes to the Columbia RFOL and TSs are administrative and editorial and delete obsolete information. Further, the licensee's proposed changes are consistent with the regulatory requirements and NRC guidance. Therefore, the staff concludes that the proposed changes to the Columbia RFOL and TSs are acceptable.
4.0 STATE CONSULTATION
In accordance with the Commission's regulations, the Washington State official was notified of the proposed issuance of the amendment on February 25, 2019. The State official had no comments.
5.0 ENVIRONMENTAL CONSIDERATION
The amendment changes a requirement with respect to the installation or use of a facility component located within the restricted area as defined in 10 CFR Part 20 and changes SRs.
The NRC staff has determined that the amendment involves no significant increase in the amounts, and no significant change in the types, of any effluents that may be released offsite, and that there is no significant increase in individual or cumulative occupational radiation exposure. The Commission has previously issued a proposed finding that the amendment involves no significant hazards consideration, published in the Federal Register on September 11, 2018 (83 FR 45984), and there has been no public comment on such finding.
The amendment also relates to changes in recordkeeping, reporting, or administrative procedures or requirements. Accordingly, the amendment meets the eligibility criteria for categorical exclusion set forth in 10 CFR 51.22(c)(9) and 10 CFR 51.22(c)(10). Pursuant to 10 CFR 51.22(b), no environmental impact statement or environmental assessment need be prepared in connection with the issuance of the amendment.
6.0 CONCLUSION
The Commission has concluded, based on the considerations discussed above, that: (1) there is reasonable assurance that the health and safety of the public will not be endangered by operation in the proposed manner, (2) there is reasonable assurance that such activities will be conducted in compliance with the Commission's regulations, and (3) the issuance of the amendment will not be inimical to the common defense and security or to the health and safety of the public.
Principal Contributor: A. Russell Date: June 20, 2019
ML19063A579 OFFICE NRR/DORL/LPL4/PM NRR/DORL/LPL4/LA NRR/DSS/STSB/BC NAME JKlos PBlechman VCusumano DATE 03/02/19 05/16/19 01/9/19 OFFICE OGC NRR/DORL/LPL4/BC NRR/DORL/LPL4/PM NAME CEngland RPascarelli JKlos DATE 05/20/19 06/19/19 06/20/19