Clinton Power Station Regulatory Conference Division 2 Diesel Generator Air Start Isolation Event November 30, 2018

Agenda

  • Introduction.................................... Brad Fewell
  • Finding Cause and Corrective Actions............... Brad Kapellas
  • Key Differences................................. Gene Kelly/Johnny Weissinger
  • Initial Conditions for Postulated Event, Recovery and Mitigation Actions........................... Johnny Weissinger/Gene Kelly
  • Risk Significance................................ Gene Kelly
  • Conclusion..................................... Ted Stoner 1

Clinton Power Station Regulatory Conference Introduction Brad Fewell Senior Vice President, Regulatory Affairs and General Counsel

Introduction

  • We agree with the Finding and violation
  • We recognize our failure to maintain the configuration of an important safety system
  • We have taken timely, comprehensive, and broad responsive actions
  • We disagree with the Findings preliminary significance of White

- Commission Policy and NRC guidance drive risk evaluations to be realistic and based on best available information

- NRC risk evaluation does not reflect the as-built, as-operated plant response

  • NRCs risk evaluation assumptions do not reflect how CPS would respond to DG recovery, SBO, FLEX, and ELAP by not appropriately crediting:

- Operators extensive knowledge, training, and experience

- Available time to take recovery actions

- Procedures that control the event and drive successful resolution PRA evaluations should be realistic and based on best available information 3

Introduction (cont.)

  • We will show that using realistic and best-available information:

- Division 2 DG would have been restored and injection available within one hour

- Expansive time was available to recover AC power and prevent core uncovery

- Procedurally directed alternative power recovery actions would have been pursued in parallel

- Objective data to support different performance shaping factor (PSF) multipliers

  • We will provide information that the NRC did not previously review and new information that we have recently developed
  • We had the knowledge, time, and resources to restore AC power and injection Finding should be characterized as Green 4

Clinton Power Station Regulatory Conference Finding Cause and Corrective Actions Brad Kapellas Plant Manager

Station Event Response

  • Root Cause

- Contrary to Exelon fleet governance for plant status control, operator logs were utilized as the sole means to track plant configuration

  • Corrective Action to Prevent Reoccurrence

- Identify and eliminate legacy site-specific administrative procedures/guidance that allow operator logs as a sole method for plant status control

  • Continuous Procedure Use

- Cause of the event was not an operating procedure execution issue

- Procedure directed operator component manipulation error rate is very low (estimated less than two per million manipulations)

  • Corrective Actions

- Implemented I know because I looked initiative station wide to improve administrative procedure knowledge and compliance

- Reinforced accountability for equipment status control throughout operations

- Revision to safety related operator rounds points

- Three day station wide campaign for change 6

Event taken seriously and being used as burning platform to move culture to sustained levels of high Operational Excellence

Clinton Power Station Regulatory Conference Key Differences Gene Kelly Sr. Manager, Risk Management Johnny Weissinger Director, Operations

Exelon and NRC Risk Results - Differences

  • Large difference in our results, a factor of almost 400
  • The difference is not in PRA methods both use similar approaches from a PRA standpoint
  • Key differences:

- Actual site response in SBO conditions

- Available time to recover power and injection

- Operator experience and training applied to recovery actions

- Complexity associated with power recovery actions 8

Exelon change in CDF NRC change in CDF 1E-8/year 3.8E-6/year Risk analysis should reflect manner in which plant is operated

Key Choice Letter Disagreements NRC Position Exelon Position Assumption 12 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br /> available to recover AC power to Division 2 by recovering DG; ELAP declared at 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br /> and FLEX power to Division 2 would commence DG recovery complicated by SBO load shedding that removes all DC control power from DG FLEX electrical lineup impacts DG components Air start valves found isolated within 29 minutes; ELAP not declared Load shed recovery proceduralized and does not complicate DG recovery ELAP not declared/FLEX staging only Assumption 13 Experience/training considered Low for DG recovery diagnosis Operators have not trained on, experienced, or been exposed to failed DG DG air start valve position easily identified in knowledge-based or procedure-based mode Operators extensively trained on DG malfunctions 9

Key Choice Letter Disagreements (cont.)

NRC Position Exelon Position Assumption 2 Time to TAF does not appear to credit shutdown cooling isolation Operators will close one shutdown cooling valve per procedure to extend time to TAF from 10.8 hours9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br /> to about 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> Assumptions 14, 23, 24 FLEX implementation success credited as Low FLEX lineup experience/training considered Low FLEX ergonomics considered Poor NRC inspections confirm that FLEX strategy meets regulatory requirements FLEX trained in accordance with Systematic Approach to Training FLEX tasks similar to normal EO tasks &

performed in non-adverse conditions Assumption 15 Div 3 to Div 2 AC power cross-tie is Complex Time required to complete cross-tie is 5-6 hours Procedure is straightforward and not complex Time-validated at 1.5 hours5.787037e-5 days <br />0.00139 hours <br />8.267196e-6 weeks <br />1.9025e-6 months <br /> 10

Clinton Power Station Regulatory Conference Initial Conditions for Postulated Event, Recovery and Mitigation Actions Johnny Weissinger Director, Operations Gene Kelly Sr. Manager, Risk Management

Success Criteria Injection Established Before RPV Water Level Reaches the Top of Active Fuel Division 2 DG is completely recoverable (no equipment malfunction) and operations response would not complicate recovery NRC did not model or credit Division 2 DG after one hour One action to close a shutdown cooling valve (1E12-F008), as directed by procedure, extends the time to TAF to about 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> Does not appear to be modeled in NRCs analysis DC batteries provide ability to control RPV pressure using SRVs permitting use of low or high pressure injection sources Does not appear to be modeled in NRCs analysis 12

Exelon Perspective

  • RPV injection will be restored prior to reactor water level lowering below TAF through multiple, independent, and diverse means

- Rule-based procedural guidance to restore the DG

- Knowledge-based identification of the DG air start valves

- Cross-tie of the Division 3 DG to the Division 2 bus

- Use of FLEX

  • Identifying the closed air start valves, reopening them, and restarting the DG per procedure terminates the postulated event

- Significant time available before deterioration of plant conditions

- Operators are extremely knowledgeable and experienced with DG operation

- All actions to identify the valves and restart DG are proceduralized

- Air start valves are readily identifiable and accessible

- Reopening a manual ball valve is a simple task

- Emergency battery lighting and portable flashlights available

- Significant resources onsite to support 13

Bus Alignment During Div 1 & 2 DG Unavailability 14 Division 1 4160V Division 2 4160V Division 3 4160V 138 kV Switchyard RAT-B XFMR ERAT XFMR Div 1 DG Div 2 DG Div 3 DG System Outage Window Unplanned out-of-service Division 1 Division 2 Division 3 AC Distribution X AC Distribution O AC Distribution O

Diesel Generator X Diesel Generator X Diesel Generator O

RHR-A / SDC X RHR-B / SDC O HPCS X

LPCS X RHR-C O

DC Batteries O DC Batteries O DC Batteries O

Plant is in Mode 4 - Cold Shutdown RPV Water Level 235 to 250 above TAF Time To Boil ~4 hours 345 kV Switchyard

Overview of Station Response to a SBO LOOP/Station Blackout Time Extension Operations Response Shutdown Cooling Isolation (extends time to TAF from 10.8 hrs to ~24 hrs)

DC Battery Load Shedding (extends battery life from 2.3 hrs to 24 hrs)

Control RPV Pressure for Low Pressure Injection Power Recovery Align Div 2 DG to start FLEX Div 3 DG cross-tie to Div 2 bus Restore Offsite Power Emergency Response Declare ALERT Activate ERO 15

Loss of AC Power Procedure 4200.01 16 SBO is not a beyond design basis external event

  • Definitions are in accordance with CPS licensing basis

LOOP Procedure Direction for ELAP Declaration 17 HIGH ASSURANCE that power will be recovered within 4 hours4.62963e-5 days <br />0.00111 hours <br />6.613757e-6 weeks <br />1.522e-6 months <br /> includes:

Division 2 DG air start valves identified out of position No maintenance performed on Division 2 DG during outage No degraded conditions for the Division 2 DG existed Shift Manager has High Assurance ELAP does not exist

Entry into ELAP

  • Operators are exhaustively trained on the DGs and Loss of AC Power due to high risk significance

- Five simulator scenarios, 26 exam questions, biennial training in last two years

- Operator JPMs for DGs include resetting trips/lockouts and manually bypassing the air start system to manually start the engine with 100% pass rates administered a total of 50 times in the last two years

  • ERO is trained on LOOP/FLEX

- ERO drills include simulated loss of power and/or loss of DG

- TSC personnel experienced in plant restoration

- Restoration of power is high priority

  • Six CPS Shift Managers were surveyed for four potential ELAP scenarios

- All surveyed Shift Managers stated they would not declare an ELAP during scenarios where action was taken to recover power within the 4-hour SBO coping period

- All Shift Managers stated they would not enter ELAP/FLEX procedures once the DG air start valves are identified out of position

- All Shift Managers surveyed stated they would pre-stage FLEX equipment to improve plant risk

  • 28 SROs from other stations (including non-Exelon) were given CPS procedures and scenarios that recreated the postulated scenario

- All SROs stated that they remain in the LOOP procedure and NOT enter ELAP 18 No ELAP entry conditions

Recovery Pathway #1: Division 2 DG Restoration

  • Time validation for a CPS EO to walkdown and identify the out of position air start valves using only system knowledge was 11 minutes
  • Time validation for a CPS EO to identify and correct the out of position air start valves per procedure was 29 minutes

- DG full lineup completed within 40 minutes and in service within 50 minutes

  • JPM performed by non-CPS EOs to identify out of position air start valves

- All six EOs identified closed air start valves using procedure within 32 minutes

- DG full lineup completed within 37 minutes

  • Multiple operators, engineers, and technicians would respond, improving DG recovery time 19 Division 2 DG will be recovered in < 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br />

Rule-Based Operator Response to Division 2 DG Failure to Start 20 Knowledge / Training-Based Response EOs are trained to check the air start system after any DG start. The EO is also cued by the alarm card.

The out of position air start valves will be identified during this walkdown.

Procedure / Rule-Based Response A supervisor and additional EOs arrive to support with the procedure in hand.

The out of position air start valves are identified by procedure.

EO resets DG lockouts and Engine Start (bus energized)

EO commences DG lineup and restores valves per procedure EO requests DG standby procedure.

Walks down DG.

Dedicated Safe Shutdown EO arrives and reports Failure to Start alarm and no visible equipment damage Multiple means to identify out of position air start valves DG is recovered.

Air start valves are restored by procedure.

The Div 2 DG starts and restores power.

Identification of closed air start valves and no visible damage provides Shift Manager High Assurance of Division 2 power recovery LOOP/SBO Entered

Operator Response to Division 2 DG Failure to Start (Rule-Based) 21

22 Dedicated EO requests a copy of the DG procedures from the Control Room Operator Alarm Response (Rule-Based)

Operator Alarm Response (Rule-Based) 23 DG recovered completely by procedures On Page 6 of DG operating procedure Opening of the air start valves is procedurally governed Restoration of DC control power following load shed is procedurally governed and does not complicate DG recovery Load shed circuits are recovered per Loss of AC Power procedure

Operator Response to Division 2 DG Failure to Start (Knowledge-Based) 24 Starting air receiver pressure is 225-250 psig and did not lower as expected following DG start signal

Operator Validates DG Starting Air Parameters 25 EO identifies closed air start valves based on alarms and local indications Division 2 DG Local Air Start Pressure Located on gauge board, as found during the event Division 2 DG Air Receiver Pressure Tech Spec LCO 3.8.3 Not on operator rounds prior to event 0 psig Required to log on operator rounds Normal pressure is 225-250 psig

Operator Response to Division 2 DG Failure to Start 26 This flow path was most recently trained in 2017 Air start path can be easily traced back to the receivers EO JPM to start the DG by overriding the air start system solenoids/lineup; 100% pass rate across 27 Operators in 2017

Operator Validates Air Start System Did Not Actuate Through Equipment Checks 27 If the DG received starting air, an oil spray/mist would be visible below the exhaust of the six air start motors

Operator Response to Division 2 DG Failure to Start 28 Walking down the air start system is trained and performed with the monthly DG runs EOs trained to check air start system response after DG start

Operator Identifies Out Of Position Air Start Valves 29 Tags Plus straps left on air start valves Left over tie wraps from clearance order tags as found on 5/17/18 Division 2 DG air start valve in the normal Locked Open position

Operator Response to Division 2 DG Failure to Start 30 Video

DG Restoration Summary

  • Identification of the out of position air start valves will occur in either knowledge or rule-based space
  • Air start valves are time validated to be identified by knowledge in 11 minutes and procedure in 29 minutes
  • DG recovery is simple task (open air start valves) using regularly executed DG lineup procedure
  • Identification of closed air start valves and no visible damage provides Shift Manager High Assurance of Division 2 power recovery

- An ELAP will not be declared

  • OCC/ERO technical support and large number of resources 31 We had knowledge, time, and resources to restore Division 2 DG

Impact of Actual Response: Div 2 DG Recovery

  • Realistic modeling of Division 2 DG recovery, by itself, leads to GREEN significance

- NRCs sensitivity case #3 (using Exelons HEP) shows Green 32 Exelons DG HEP NRCs DG HEP 0.005 (99.5% success) 0.2 (80% success)

Considerable available time, and operator experience and training assure high success PSF NRC Diagnosis Setting Exelon Position SPAR-H HEP Reduction Factor Impact on Finding Available Time (required time <1 hr)

Nominal 1 hr Expansive only need 2 hrs, but 24 hrs available

~50 GREEN Experience/Training Low Nominal

~10 GREEN

Minimum Shift Staffing 33 Shift Manager (SRO) 2 Senior Reactor Operators 3 Reactor Operators Control Room Team 6 Equipment Operators Dedicated On Duty Security Force Members 2 RP Technicians Chemistry Technician 1 IM/EM ERO

Outage Response Staffing

  • 137 - Minimum craft staffing on any shift during the affected window of C1R18 34 Control Room Team 6 Senior Reactor Operators 5 Reactor Operators 27 Equipment Operators 30 Mechanics 44 Instrument Maintenance Technicians 16 Electricians 11 Radiation Protection Technicians 4 Chemistry Technicians Shift Manager (SRO)

Event Recovery Timeline Activities in Series 35 Start 2 hours2.314815e-5 days <br />5.555556e-4 hours <br />3.306878e-6 weeks <br />7.61e-7 months <br /> 4 hours 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> 8 hours 10 hours1.157407e-4 days <br />0.00278 hours <br />1.653439e-5 weeks <br />3.805e-6 months <br /> 12 hours Restore Div 2 DG to Service (50 min)

Complete DC Load Shed (1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br />)

Commence FLEX Pre-Staging (1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br />)

ERO Is Staffed (Alert) (1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br />)

Complete Div 3 to Div 2 X-Tie (1.5 hours5.787037e-5 days <br />0.00139 hours <br />8.267196e-6 weeks <br />1.9025e-6 months <br />)

End of SBO. Commence FLEX (4 hours4.62963e-5 days <br />0.00111 hours <br />6.613757e-6 weeks <br />1.522e-6 months <br />)

FLEX is ready for RPV injection (5 hour5.787037e-5 days <br />0.00139 hours <br />8.267196e-6 weeks <br />1.9025e-6 months <br />s*)

RCS Boiling Begins (4 hours4.62963e-5 days <br />0.00111 hours <br />6.613757e-6 weeks <br />1.522e-6 months <br />)

Shutdown Cooling Isolated within 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> Time to TAF (No Operator Actions) (10.8 hours9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br />)

Time to TAF (SDC isolated or RPV pressure controlled low with Batteries) (~24 hours)

Substantial time available for mitigation actions even if performed in series 5 hours5.787037e-5 days <br />0.00139 hours <br />8.267196e-6 weeks <br />1.9025e-6 months <br /> is the worst case for FLEX RPV injection and 8 hours9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br /> is the worst case FLEX heat removal and suppression pool makeup. RPV injection commences before TAF in all cases.

  • 1 hour subtracted from FLEX times because they overlap with the first hour of SBO actions.

Recovery Pathway #2:

Cross-Tie Div 3 DG to Div 2 Bus 36

- Bus cross-tie completion validated to complete in 1.5 hours5.787037e-5 days <br />0.00139 hours <br />8.267196e-6 weeks <br />1.9025e-6 months <br />

- Open one in-plant disconnect

- Open four relay test switches

- Remove one relay control power fuse

- Control Room performs breaker alignments

- Tools pre-staged in operations locked cages and all manipulations in general plant areas

- Switchgear breaker and disconnect training occurs every two years

- Four page procedure with pictures, locations, and diagrams simplify execution

Cross-Tie Div 3 DG to Div 2 Bus During SBO 37 Division 1 4160V Division 2 4160V Division 3 4160V 345kV Switchyard 138 kV Switchyard RAT-B XFMR ERAT XFMR Div 1 DG Div 2 DG Div 3 DG System Outage Window Unplanned Out of service Division 1 Division 2 Division 3 AC Distribution X AC Distribution O AC Distribution O

Diesel Generator X Diesel Generator X Diesel Generator O

RHR-A / SDC X RHR-B / SDC O HPCS X

LPCS X RHR-C O

DC Batteries O DC Batteries O DC Batteries O

Impact of Actual Response: Div 3 to Div 2 Cross-Tie 38 Exelons Cross-Tie HEP NRCs Cross-Tie HEP 0.096 (90.4% success) 0.27 (73% success)

PSF NRC Action Setting Exelon Position SPAR-H HEP Reduction Factor Impact on Finding Available Time (required time ~1.5 hr)

Nominal (13 hours1.50463e-4 days <br />0.00361 hours <br />2.149471e-5 weeks <br />4.9465e-6 months <br />)

Extra (24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br />)

~7 GREEN Experience/Training Low Nominal Ergonomics Poor Nominal Complexity High Moderate Realistic modeling of Division 3 cross-tie, coupled with higher likelihood of offsite power recovery within 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br />, leads to Green

Recovery Pathway #3:

FLEX Implementation and Timeline 39 FLEX equipment pre-staged in parallel until implementation required

FLEX Implementation and Timeline

  • By 2 hour2.314815e-5 days <br />5.555556e-4 hours <br />3.306878e-6 weeks <br />7.61e-7 months <br />s: Briefs complete, teams ready to dispatch
  • By 4 hour4.62963e-5 days <br />0.00111 hours <br />6.613757e-6 weeks <br />1.522e-6 months <br />s: Pre-staging complete, hoses and cables run to location, FLEX generator running in standby; plant realignment occurs when directed by Control Room Supervisor
  • By 6 hour6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br />s: Battery charger in service powering Division 2 batteries, low pressure RPV makeup is available
  • By 8 hour9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br />s: Decay heat removal and suppression pool makeup available
  • Minimum Personnel: 6 Operators, 6 Security Force Members (for 3 hours3.472222e-5 days <br />8.333333e-4 hours <br />4.960317e-6 weeks <br />1.1415e-6 months <br />), 2 Radiation Protection Technicians, 1 Chemistry Technician
  • Outage Personnel: At least 15 Qualified Operators + Supervision, Electrical and Mechanical maintenance dispatched by the ERO to support as necessary 40

FLEX Training and Experience

  • Task specific procedures are located in field FLEX cabinets
  • Procedures are designed to be Grab and go and have prerequisite steps built into each section to ensure all required manipulations are completed
  • Most tasks are similar to normal EO tasks

- Racking breakers

- Starting FLEX generator (similar to TSC generator)

- Routing cable or hoses

  • Trained in accordance with the Systematic Approach to Training
  • From NRC Inspection Report TI-191: licensee has trained their staff to assure personnel proficiency in the mitigation of beyond DB events 41 EOs trained and proficient with FLEX equipment and procedures

Impacts of Actual Response: FLEX Alignment 42 Exelons FLEX HEP NRCs FLEX HEP 0.002 (99.8% success) 0.25 (75% success)

PSF NRC Action Setting Exelon Position SPAR-H HEP Reduction Factor Impact on Finding Available Time (required time ~4 hr)

Nominal (13 hours1.50463e-4 days <br />0.00361 hours <br />2.149471e-5 weeks <br />4.9465e-6 months <br />)

Extra (24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br />)

~12 GREEN Experience/Training Low Nominal Ergonomics Poor Nominal Complexity High Nominal Realistic modeling of FLEX deployment, coupled with higher likelihood of offsite power recovery within 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br />, leads to Green

RPV Pressure Control

  • SRVs are available for pressure control for > 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br />

- Division 1 and 2 DC batteries analyzed with > 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> capacity with outage loads

- ADS accumulators and backup air bottles fully charged

  • Procedure guidance to stabilize pressure in multiple procedures

- Station Blackout, Loss of Shutdown Cooling, EOP-1, FLEX

  • Time to boil is 4 hours4.62963e-5 days <br />0.00111 hours <br />6.613757e-6 weeks <br />1.522e-6 months <br />, SRV usage not needed until at least 8 hours9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br /> 43 RPV pressure controlled to allow use of low pressure injection systems

Injection

  • Multiple diverse injection systems available after Division 2 AC power restored using proceduralized actions

- Within 1 minute, start Standby Liquid Control pump B from Control Room

  • 43 gpm (4000 gallon tank), injects at any pressure, no field actions required

- Within 1 minute, start RHR-B/C water leg pump from Control Room

  • 50 gpm with RPV depressurized, no field actions required

- Manually start RHR-C for Low Pressure Coolant Injection (LPCI)

- Align RHR-B from shutdown cooling to LPCI mode

  • Additional injection systems using proceduralized actions

- FLEX pump direct injection from Ultimate Heat Sink

- Suppression Pool Transfer Pump using FLEX generator power

- Fire pump injection (direct to RPV or using hoses) 44 Any one path restores RPV level

Impact of Actual Response - Pressure/Inventory Control 45 Exelon HEP NRC HEP SDC Isolation 0.022 (98% success)

Not modeled Realistic modeling of loss of shutdown cooling actions and RPV pressure control, coupled with multiple sources of injection, leads to Green Maintain RPV Pressure (Using Division 1 or 2 Batteries) 0.001 (99.9% success)

Not modeled

  • Both actions procedurally directed
  • Success of EITHER action extends time to TAF to about 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br />

- Increases Available Time for Diagnosis and Action to restore onsite equipment

- Increases likelihood of offsite power recovery

  • Division 1 and 2 batteries available for RPV pressure control (SRVs) for 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br />
  • RPV pressure control enhances ability for low or high pressure injection sources

Recovery and Mitigation Actions Summary

  • Identification of out of position air start valves will occur
  • DG recovery is simple task (open air start valves)
  • Shift Manager has High Assurance of Division 2 power recovery
  • Activities to restore power taken in parallel but controlled to minimize conflicts
  • Other defense-in-depth actions provide additional success paths within the available time 46 AC power and injection recovered quickly and successfully

Clinton Power Station Regulatory Conference Risk Significance Gene Kelly Sr. Manager, Risk Management

Risk Assessment for Safety Significance For White significance, NRC must conclude the SBO condition would not be successfully mitigated because:

- Division 2 DG not recovered within 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br /> and

- ELAP declared at 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br /> and

- Shutdown cooling valve not isolated and

- RPV pressure not controlled and

- Division 3 to Division 2 AC power cross-tie procedurally complex and

- FLEX strategy inadequate and not sufficiently trained White significance not based on realistic or best available information 48

Clinton Power Station Regulatory Conference Conclusion Ted Stoner Site Vice President

Conclusion

  • We had the knowledge, time, and resources to restore AC power
  • NRC policy and guidance dictate risk evaluations to be realistic and based on the best available information
  • Best available information includes:

- Reflecting a realistic response to the event

- Recognizing extensive operator training and experience

- Appropriately crediting FLEX

  • Using the best available information as presented today and applying the Commissions guiding policies and principles on risk results in:

50 Green significance