Qaps Technical Specification 5.6.8 Palo Verde Nuclear Generating Station 5801 S. Wintersburg Road Tonopah, AZ 85354 102-07819-MDD/MSC November 2, 2018 ATTN: Document Control Desk U. S. Nuclear Regulatory Commission Washington, DC 20555-0001
Subject:
Palo Verde Nuclear Generating Station (PVNGS) Unit 3 Docket No. STN 50-530 License No. NPF-74 Steam Generator Tube Inspection Report Attached please find the PVNGS Unit 3 Steam Generator Tube Inspection Report prepared and submitted by Arizona Public Service Company (APS) pursuant to Technical Specification (TS) Reporting Requirement 5.6.8. This report describes steam generator tube inspection and plugging results from the Unit 3 twentieth refueling outage.
By copy of this letter, this submittal is being provided to the NRC Region IV Administrator and the PVNGS Senior Resident Inspector. No commitments are being made to the NRC by this letter.
Should you need further information regarding this submittal, please contact Matthew S. Cox, Licensing Section Leader, at (623) 393-5753.
Sincerely, Michael D. Dilorenzo Nuclear Regulatory Affairs Department Leader MDD/MSC/CJS/sma Attachment cc:
(with attachment)
K. M. Kennedy C. A. Peabody NRC Region IV Regional Administrator NRC Senior Resident Inspector for PVNGS A member of the STARS Alliance, LLC Callaway
- Diablo Canyon
- Palo Verde
- Wolf Creek
Attachment Unit 3 - 20* Refueling Outage Steam Generator Tube Inspection Report
PaloVerde GENERATING STATION UNrrs U3R20 ARIZONA PUBLIC SERVICE P. O. BOX 52034 PHOENIX, AZ 85072 Prepared by: Douglas Hansen 4-26-18 Leaverton DN: cn*teav#rton, Warren
, Warren UV59783)
Reviewed by:
Approved by:
Commercial Service Date: 1-8-88 document Dele: 2018.10.23 07:S&53
.07W Digitally signed by Gil, Katherine J(Z05492)
DN: cn=Gil, Katherine J{Z05492)
Date: 2018.10.29 11:07:56 -07'00'
Table of Contents 1.0
SUMMARY
2.0 SCOPE OF EXAMINATIONS PERFORMED 3.0 ACTIVE DEGRADATION MECHANISMS 4.0 NDE TECHNIQUES UTILIZED 5.0 INDICATION
SUMMARY
6.0 TUBES PLUGGED 7.0 PLUG HISTORY 8.0 CONDITION MONITORING APPENDIX A - TUBE SUPPORT DIAGRAM, LEGEND, and ANALYSIS CODES APPENDIX B - SG 31
SUMMARY
DATA SHEETS APPENDIX C - SG 32
SUMMARY
DATA SHEETS APPENDIX D - PLI and PLP DATA SHEETS APPENDIX E - PLUG MAPS
UNIT 3 STEAM GENERATOR EDDY CURRENT U3 R20 Refueling Outage 1.0 Summary This report is intended to satisfy the requirements of PVNGS Technical Specifications 5.6.8 for the submittal of a Steam Generator Tube Inspection Report. The steam generator (SG) eddy current examination for the 20th refueling outage in Unit 3 (U3R20) was conducted during April 2018.
Mode 4 entry was on May 2, 2018. The initial examination plan for both steam generators is listed in Table 1. This table summarizes the examinations performed for each of the various categories, examination types, extents, and the number of tubes or tube locations completed. This examination was a 100% full length tubing inspection.
The examinations resulted in a total of 31 tubes being plugged in SG 31, and 19 tubes being plugged in SG 32. A description of the previous plugging history for these replacement steam generators is contained in Appendix E.
2.0 Scope of Examinations Performed The original examination plan was developed based on the PVNGS U3R20 Steam Generator Degradation Assessment (Westinghouse document SG-SGMP-18-03-NP, dated April 5, 2018) developed per PVNGS Procedure 81DP-9RC01 as required by NEI 97-06. In addition, possible damage mechanisms were reviewed along with the specific requirements set forth in Procedure 73TI-9RC01 and the PVNGS Technical Specifications.
This original plan, along with the examinations performed as a result of bobbin indications noted, is summarized in Table 1 of this report.
3.0 Active Degradation Mechanisms The only degradation noted during the examinations was determined to be wear. Section 8.0 contains further discussions relating to this mechanism. Table 2 summarizes the results into categories and sections B and C itemizes all indications reported.
4.0 NDE Techniques Utilized The following table documents the site validated and qualified techniques utilized during this outage:
BOBBIN Examinations Damage Mechanism Location ETSS NO QUAL STATUS Extended Applicability BC DET BC SIZE TECH Comment Wear BWs, VSs, ECs (not dented) 96004.1 R13 SITE VALIDATED Tube Proximity Y
Y Volt DIFF Note Wear Loose Part 27091.2 R2 QUALIFIED Tubesheet Transition Y
N Volt DIFF Note ARRAY Examinations Damage Mechanism Location ETSS NO QUAL STATUS Extended Applicability DET SIZE TECH Comment Wear BWs, ECs, VSs 11956.3 R2 11956.4 R2 SITE VALIDATED Wear at Dented Supports Y
Y X-Probe Note The U3R20 Degradation Assessment and associated site validation provides details for the qualification and use of the above techniques The eddy current examinations were performed by Westinghouse Electric Company using the Core Star OMNI 200 eddy current instrument. Westinghouse Anser software was utilized to acquire the data along with the Pegasys robotic manipulator. This robot was configured with a dual guide tube in each of the hot and cold legs.
The tubing was examined with Core Star manufactured bobbin coil probes and Zetec array style probes. Probe diameters were 0.590 to 0.610. Array probes were used for the characterization of non-quantifiable or distorted bobbin indications.
Fiber optic cable was used from containment to the data acquisition room located at the PVNGS North Annex. Primary and secondary analysis was all performed on site. The Primary and Secondary Resolution Analysts, Independent Review Analysts, and data management were also located at PVNGS in the North Annex. Westinghouse provided the data acquisition and primary data analysis. Areva provided the secondary data analysis.
Each individual from Westinghouse and Framatome who performed data analysis was required to complete and pass a PVNGS site specific Eddy Current Data Analysis Course as well as an associated performance and written examination. All individuals performing data analysis were also
required to have Qualified Data Analyst (QDA) certification. Per 73TI-9RC01, all certification records are maintained in the Nuclear Information Records Management System.
5.0 Indication Summary A detailed listing of the location and measured sizes of all service induced indications recorded is included in Appendix B and C. A summary of these indication results is located in Table 2. In addition, Appendix A contains a reference drawing of steam generator support locations and report legend.
Appendix D contains a listing of the possible loose part (PLP) indications that were confirmed with rotating coil examinations. Note Section 8.0 for further discussion on the PLPs.
There were no indications that were identified as linear during this outage.
6.0 Tubes Plugged A summary of the tubes plugged is located in Table 2. Appendix E contains a map that details the plugged tube location along with the previously plugged tubes.
7.0 Plug History A summary of the number and percentage of tubes plugged is also located in Table 2.
8.0 Condition Monitoring Tube Inspection Summary Per the Steam Generator Program, as defined in PVNGS Procedure 81DP-9RC01, a condition monitoring evaluation was conducted by PVNGS Engineering. The results of the eddy current examinations are provided in Section 5.0. An engineering evaluation of the as-found condition of inservice tubes did not reveal any degradation exceeding the threshold values for structural and leakage integrity. As such, all steam generator performance criteria were satisfied for Unit 3 Cycles 19 and 20. No tube pulls or in-situ pressure testing were required based on the results of the examinations.
Foreign Object Search and Retrieval (FOSAR)
FOSAR was performed at the tubesheet elevation in the annulus region and the blowdown lane. The applicable requirements of Revision 4 of the EPRI Steam Generator Integrity Assessment Guidelines Section 10.3, Foreign Object Search and Retrieval, were applied for the FOSAR inspections.
An evaluation was performed to determine if Flow Distribution Plate (FDP) area FOSAR should continue to be performed with the FDP robot (or guide tubes) or if reliance on ECT in the area is considered adequate to find foreign objects in the area. It was concluded that the ECT method is acceptable. This approach has been used several times in previous inspections. ECT monitoring of the FDP area in SG31 and SG32 during U3R20 did not identify any foreign objects or foreign object wear, so further testing of the area from the secondary side was not performed.
No foreign object wear was found in either steam generator 31 or 32. Following is a summary of the foreign objects that were identified in each SG. Sludge rocks, scale and graphite are not discussed, since they are not considered as a threat to tube integrity.
SG 31 -Foreign object Summary There was one non-sludge/scale object found during FOSAR in SG 31 (flex gasket material). The object was retrieved from the cold leg tubesheet by tube R110C27. The gasket material was approximately 1.0 long. There was no wear identified by bobbin or special interest testing.
SG 32 -Foreign object Summary There was one non-sludge/scale object found during FOSAR in SG 32 (flex gasket material). The object was retrieved from the cold leg tubesheet by tube R165C78. The gasket material was approximately 2.5 long. There was no wear identified by bobbin or special interest testing.
Blowdown Patch Plate Weld Inspection Summary Also included in the scope of the FOSAR effort was an inspection of the blowdown patch plate welds In SG31 and SG32 that were found to be cracked in Unit 3 during 3R15. Inspections confirmed that the weld material in the vicinity of the cracked weld on all 4 patch plates (2 per SG) is intact, and a loose parts concern is not being created. A previous evaluation concluded that, with the presence of the cracked welds, the patch plates in the Unit 2 SGs will continue to perform their design function and that the probability of loose parts being formed is remote. This evaluation also applies to Unit 3. Thus, there is a very low risk that the cracked welds will affect the structural or leakage integrity of tubes in these steam generators.
Plug Inspections Summary The EPRI PWR Steam Generator Examination Guidelines require that a visual inspection of the previously installed steam generator plugs be performed to assess plug integrity. Additionally, the Examination Guidelines require a verification of the location and presence of existing in-service plugs. The conduct of the plug location and integrity verification was performed in 3R20 per the applicable procedure. A review of the inspection results indicated that all plugs were accounted for and no evidence of potential plug leakage was identified.
Channel Head Inspection Summary A channel head inspection was also performed in response to Westinghouse Engineering Nuclear Safety Advisory Letter (NSAL) 12-1, dated January 5, 2012. The inspection identified no degradation.
TABLE 1 EXAMINATION
SUMMARY
SCOPE DESCRIPTION SG 31 SG 32 Exam Description Extents Scope Scope FULL LENGTH BOBBIN TEC-TEH 12503 12479 HOT LEG ARRAY VARIOUS 262 194 COLD LEG ARRAY VARIOUS 164 65 Notes:
ARRAY probe technology utilized the X-Probe
TABLE 2 INDICATION
SUMMARY
DAMAGE MECHANISM STEAM GENERATOR 31 STEAM GENERATOR 32 Tubes Indications BW VS EC Tubes Indications BW VS EC WEAR 1% - 19%
20% - 29%
30% - 39%
> 40%
PLUGGED 896 98 11 7
(31) 1012 106 11 8
312 49 8
7 508 54 3
1 192 3
0 0
1020 84 10 0
(19) 1142 89 12 0
264 38 10 0
690 35 2
0 198 16 0
0 Possible Loose Parts (Array Probe)
PLI PLP PLUGGED 0
5 (0) 0 0
(0)
PREVENTATIVE (0)
(0)
PLUGGED
( 31)
( 19)
TOTAL PLUGGED /
( 108 / 0.8% )
( 120 / 0.9% )
NOTES:
- 1. Numbers in (X) are tubes numbers plugged in each category
- 2. The Tubes column above represents Bobbin Coil results for the number of tubes; using the largest wear indication
- 3. The Indications column above represents Bobbin Coil results for the number of wear indications LEGEND:
BW - batwing VS - vertical strap EC - eggcrate
APPENDIX A TUBE SUPPORT DIAGRAM, LEGEND, and ANALYSIS CODES
PVNGS Steam Generator REPLACEMENTS VS1 VS3 VS4 VS2 VS5 07H 06H 05H 04H 03H 02H 01H Inlet Outlet 09C 07C 06C 05C 04C 03C 02C FDP 20 36.33 36.33 36.34 35.95 35.95 35.95 16.5 24 28.125 32.25 26 Typical Spacing Center of 08H to 08C Row 1 - 17.415 Row 2 - 19.736 Row 3 - 22.056 Row 4 - 24.377 Row 5 - 26.698 Row 6 - 29.019 28.125 01C 08H 08C 35.95 36.75 09H 36.75 10C 36.75 11C BW2 BW1 11H 10H 25 + 0.25 clad
LEGEND ROW:
Indicates the row number of a given tube.
COL:
Indicates the column number of a given tube.
VOLTS:
Indicates the peak-to-peak voltage of a given indication response.
DEG:
The measured phase angle of a given indication response.
IND:
Indicates the analysis code or PCT for percent PER or PCT:
The percent through the tube wall of a given indication CHN:
Indicates the channel used to make the call LOCN:
Gives indication location at INCH1 to INCH2 relative to known landmarks such as supports, vertical straps, and batwings. Typical location codes are as follows:
- 1 Vertical Strap................................VS1
- 1 Batwing.........................................BW1
- 1 Support Plate in Hot Leg..............01H
- 7 Support Plate in Cold Leg.............07C Top Tube Sheet Cold Leg..................TSC Tube End Hot Leg..............................TEH Tube End Cold Leg............................TEC CRLEN:
Indicates the flaw length, used to identify the length of a wear indication CRWID:
Indicates the flaw width, typically used for cracks only CEG:
Indicates the flaw length, typically used for cracks only BEGT and ENDT:
Indicates the beginning and of the test; together they document the examination extent PDIA:
Documents the probe diameter PTYPE:
Documents the probe type CAL:
Indicates calibration number L:
Indicates the leg the examination was conducted from COM:
This comment field is utilized to document comments
Analysis CODES:
Absolute Drift.................................................................... ADI Bulge.................................................................................. BLG Dented Buff Mark.............................................................. DBM Deposit............................................................................... DEP Dent.................................................................................... DNT Data Quality Acceptance.................................................... DQA Distorted Support Signal With Indication.......................... DSI Distorted Top of Tubesheet With Indication..................... DTI Geometric Indication.......................................................... GEO ID Chatter........................................................................... IDC Indication Not Found......................................................... INF Indication Not Reportable.................................................. INR Multiple Axial Indication................................................... MAI Manufacturer Burnishing Mark.......................................... MBM Mixed Mode Indication...................................................... MMI Multiple Circumferential Indication................................... MCI Multiple Volumetric Indication.......................................... MVI No Detectable Defect......................................................... NDD No Discontinuity Found..................................................... NDF Non-Quantifiable Indication.............................................. NQI No Tube Sheet Expansion.................................................. NTE Obstructed.......................................................................... OBS Over Expanded................................................................... OXP Previous Bobbin Call......................................................... PBC Possible Deposit................................................................. PDP Positive Identification........................................................ PID Positive Identification Verified.......................................... PIV Possible Loose Part with Indication................................... PLI Possible Loose Part............................................................ PLP Previous RC Call................................................................ PRC Possible Support Anomaly................................................. PSA Possible Support Indication............................................... PSI Permeability Variation Noise............................................. PVN Retest Bad Data.................................................................. RBD Retest Identification Check................................................ RIC Retest with Magnetic Bias RC Probe................................. RMB Single Axial Indication...................................................... SAI Single Circumferential Indication...................................... SCI Single Volumetric Indication............................................. SVI Senior (Lead) Analysis Review......................................... SR Sludge................................................................................ SLG To Be Plugged.................................................................... TBP Volumetric Indication........................................................ VOL
APPENDIX B STEAM GENERATOR 31
SUMMARY
DATA SHEETS
SG - 31 Calls of Interest Palo Verde 3 U3R20 PVNGS3 20180401 04/20/2018 13:40:22
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
l ROW COL VOLTS DEG IND PER CRLEN CHN LOCN INCH1 INCH2 BEGT ENDT PDIA PTYPE CAL L IDX UTIL1 UTIL2l
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
l 54 11.32 109 PCT 12 P2 09H.83 TEH TEC.610 SBAY2 17 C 48 l l l l 19 14.30 97 PCT 11 P2 VS3.06 TEH TEC.610 SBAY2 3 C 126 l l l l 58 15.31 125 PCT 11 P2 09H.87 TEH TEC.610 SBAY2 17 C 13 l l l l 83 16.34 68 PCT 10 P2 VS2 -.67 TEH TEC.610 SBAY2 18 C 47 l l 83 16.53 63 PCT 14 P2 VS4.89 TEH TEC.610 SBAY2 18 C 47 l l l l 76 17.38 118 PCT 11 P2 VS2.73 TEH TEC.610 SBAY2 18 C 24 l l l l 75 18.46 104 PCT 15 P2 VS2 -.84 TEH TEC.610 SBAY2 15 C 146 l l l l 80 19.55 106 PCT 17 P2 VS2.81 TEH TEC.610 SBAY2 15 C 124 l l l l 90 19.41 101 PCT 14 P2 VS4 -.79 TEH TEC.610 SBAY2 15 C 131 l l l l 85 20.41 40 PCT 12 P2 VS4 1.06 TEH TEC.610 SBAY2 16 C 134 l l l l 96 21.37 76 PCT 11 P2 VS2 -.85 TEH TEC.610 SBAY2 16 C 123 l l l l 83 22.35 124 PCT 12 P2 VS4 -.53 TEH TEC.610 SBAY2 15 C 82 l l l l 87 22.28 98 PCT 11 P2 VS2 -.83 TEH TEC.610 SBAY2 15 C 80 l l l l 89 22.27 99 PCT 10 P2 VS2 -.65 TEH TEC.610 SBAY2 15 C 79 l l l l 101 22.23 81 PCT 10 P2 VS2 -.72 TEH TEC.610 SBAY2 13 C 44 l l l l 92 23.19 120 PCT 8 P2 VS2 -.89 TEH TEC.610 SBAY2 13 C 7 l l l l 87 24.55 125 PCT 17 P2 VS2 -.86 TEC TEH.610 SBAY2 27 H 126 l l 87 24 NDF P20 TEH 21.01 01H TEH.610 ZYAX2 34 H 40 l l l l 89 24 1.06 99 PCT 23 P2 VS2 -.90 TEH TEC.610 SBAY2 16 C 72 l l 89 24 2.03 284 WAR.29 P6 VS2 -.65 VS3 TEH.610 ZYAX2 34 H 41 l l l l 93 24.33 78 PCT 10 P2 VS2 -.72 TEH TEC.610 SBAY2 14 C 6 l l l l 99 24.41 34 PCT 12 P2 BW2.82 TEH TEC.610 SBAY2 14 C 42 l l l l 107 24.44 46 PCT 13 P2 BW1 1.08 TEH TEC.610 SBAY2 14 C 46 l l l l 109 24 1.31 100 PCT 28 P2 VS3 -1.03 TEH TEC.610 SBAY2 13 C 60 l
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
l ROW COL VOLTS DEG IND PER CRLEN CHN LOCN INCH1 INCH2 BEGT ENDT PDIA PTYPE CAL L IDX UTIL1 UTIL2l
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
1 ST Max
SG - 31 Calls of Interest Palo Verde 3 U3R20 PVNGS3 20180401 04/20/2018 13:40:22
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
l ROW COL VOLTS DEG IND PER CRLEN CHN LOCN INCH1 INCH2 BEGT ENDT PDIA PTYPE CAL L IDX UTIL1 UTIL2l
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
l 109 24 1.32 271 WAR.19 P7 VS3 -.60 VS3 TEH.610 ZYAX2 34 H 43 l l l l 90 25.31 113 PCT 10 P2 10C -1.18 TEH TEC.610 SBAY2 14 C 9 l l l l 81 26.36 80 PCT 13 P2 VS4 -.72 TEH TEC.610 SBAY2 11 C 299 l l l l 111 26.34 147 PCT 12 P2 10H.72 TEH TEC.610 SBAY2 13 C 58 l l l l 82 27.67 97 PCT 19 P2 VS2.80 TEH TEC.610 SBAY2 11 C 265 l l l l 98 27.28 151 PCT 9 P2 10H.71 TEH TEC.610 SBAY2 13 C 70 l l l l 35 28.24 114 PCT 10 P2 BW1.98 TEH TEC.610 SBAY2 9 C 53 l l l l 85 28.57 85 PCT 16 P2 VS3.89 TEH TEC.610 SBAY2 12 C 305 l l l l 89 28.48 63 PCT 14 P2 VS4.98 TEH TEC.610 SBAY2 12 C 307 l l l l 110 29.72 92 PCT 18 P2 VS4 -.67 TEH TEC.610 SBAY2 14 C 66 l l l l 85 30.73 107 PCT 20 P2 VS2 -.80 TEH TEC.610 SBAY2 11 C 255 l l 85 30 1.71 285 WAR.51 P5 VS2 -.95 VS3 TEH.610 ZYAX2 34 H 42 l l l l 87 30.24 105 PCT 10 P2 VS3 -.81 TEH TEC.610 SBAY2 11 C 256 l l 87 30.45 96 PCT 15 P2 VS4 1.08 TEH TEC.610 SBAY2 11 C 256 l l l l 115 30.30 101 PCT 11 P2 BW1.84 TEH TEC.610 SBAY2 13 C 83 l l l l 98 31.24 87 PCT 10 P2 VS2.73 TEH TEC.610 SBAY2 13 C 104 l l l l 110 31.31 118 PCT 12 P2 VS4 -.79 TEH TEC.610 SBAY2 13 C 98 l l l l 120 33 1.36 79 PCT 27 P2 VS4.90 TEH TEC.610 SBAY2 14 C 87 l l 120 33 2.21 123 WAR.35 P9 VS4.66 VS3 TEC.610 ZYAX2 32 C 59 l l l l 5 34.31 112 PCT 10 P2 VS3.88 TEH TEC.610 SBAY2 26 C 101 l l l l 125 34.23 129 PCT 10 P2 BW1 -.13 TEH TEC.610 SBAY2 13 C 121 l l l l 90 35.25 97 PCT 10 P2 10C -1.69 TEH TEC.610 SBAY2 11 C 217 l l l l 94 35.35 90 PCT 13 P2 VS2.72 TEH TEC.610 SBAY2 11 C 215 l l l l 100 35.42 96 PCT 15 P2 VS4.33 TEH TEC.610 SBAY2 13 C 136 l
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
l ROW COL VOLTS DEG IND PER CRLEN CHN LOCN INCH1 INCH2 BEGT ENDT PDIA PTYPE CAL L IDX UTIL1 UTIL2l
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
2 ST Max
SG - 31 Calls of Interest Palo Verde 3 U3R20 PVNGS3 20180401 04/20/2018 13:40:22
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
l ROW COL VOLTS DEG IND PER CRLEN CHN LOCN INCH1 INCH2 BEGT ENDT PDIA PTYPE CAL L IDX UTIL1 UTIL2l
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
l l l 122 35.42 133 PCT 15 P2 VS1.78 TEH TEC.610 SBAY2 13 C 125 l l l l 69 36.28 100 PCT 11 P2 VS3 1.01 TEH TEC.610 SBAY2 11 C 199 l l l l 115 36.36 27 PCT 11 P2 VS3 -1.10 TEH TEC.610 SBAY2 14 C 108 l l l l 127 36.31 127 PCT 12 P2 VS2 -.86 TEH TEC.610 SBAY2 13 C 157 l l l l 102 37 1.03 98 PCT 23 P2 VS3 -.72 TEH TEC.610 SBAY2 14 C 128 l l 102 37 1.95 288 WAR.48 P7 VS3 -.60 VS3 TEH.610 ZYAX2 34 H 44 l l l l 128 37.21 116 PCT 9 P2 VS3 -.63 TEH TEC.610 SBAY2 13 C 158 l l l l 130 37.33 127 PCT 12 P2 VS1 -.77 TEH TEC.610 SBAY2 13 C 155 l l l l 132 39.36 119 PCT 13 P2 11C -1.02 TEH TEC.610 SBAY2 13 C 164 l l l l 134 39.12 114 PCT 8 P2 05H -.20 TEH TEC.610 SBAY2 13 C 163 l l l l 89 40.41 75 PCT 14 P2 VS2.64 TEH TEC.610 SBAY2 11 C 155 l l l l 127 40.34 134 PCT 10 P2 VS1.52 TEH TEC.610 SBAY2 14 C 149 l l l l 133 40.25 147 PCT 10 P2 BW1.70 TEH TEC.610 SBAY2 13 C 161 l l l l 135 40.24 137 PCT 10 P2 07H -.30 TEH TEC.610 SBAY2 13 C 162 l l l l 118 41 2.36 100 PCT 37 P2 VS3 1.03 TEH TEC.610 SBAY2 14 C 158 l l 118 41 TBP P1 VS3 1.03 TEC TEH.610 SBAY2 29 H 49 l l 118 41 4.55 105 WAR.72 P31 VS3 1.03 VS3 TEH.610 ZYAX2 34 H 49 l l l l 122 41.40 93 PCT 12 P2 VS1.91 TEH TEC.610 SBAY2 14 C 156 l l l l 136 41.29 133 PCT 11 P2 BW2 -1.05 TEH TEC.610 SBAY2 13 C 201 l l l l 133 42.46 93 PCT 16 P2 VS1.79 TEH TEC.610 SBAY2 13 C 198 l l l l 76 43.47 114 PCT 14 P2 09H.86 TEH TEC.610 SBAY2 12 C 98 l l l l 124 43.24 87 PCT 10 P2 VS1.88 TEH TEC.610 SBAY2 13 C 210 l l 124 43.44 111 PCT 15 P2 VS3 -.93 TEH TEC.610 SBAY2 13 C 210 l l 124 43.83 111 PCT 22 P2 VS3 1.02 TEH TEC.610 SBAY2 13 C 210 l l 124 43.88 100 PCT 23 P2 VS4 -.74 TEH TEC.610 SBAY2 13 C 210 l
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
l ROW COL VOLTS DEG IND PER CRLEN CHN LOCN INCH1 INCH2 BEGT ENDT PDIA PTYPE CAL L IDX UTIL1 UTIL2l
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
3 ST Max
SG - 31 Calls of Interest Palo Verde 3 U3R20 PVNGS3 20180401 04/20/2018 13:40:22
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
l ROW COL VOLTS DEG IND PER CRLEN CHN LOCN INCH1 INCH2 BEGT ENDT PDIA PTYPE CAL L IDX UTIL1 UTIL2l
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
l 124 43.34 122 PCT 13 P2 VS5 -.63 TEH TEC.610 SBAY2 13 C 210 l l 124 43 1.22 103 WAR.20 P15 VS3.68 VS3 TEC.610 ZYAX2 32 C 58 l l 124 43 1.72 102 WAR.57 P17 VS4 -.88 VS3 TEC.610 ZYAX2 32 C 58 l l 124 43.91 115 WAR.31 P7 VS3 -.96 VS3 TEH.610 ZYAX2 34 H 52 l l 124 43 1.33 118 WAR.28 P31 VS3.91 VS3 TEH.610 ZYAX2 34 H 52 l l l l 126 43.26 101 PCT 11 P2 VS3 -.85 TEH TEC.610 SBAY2 13 C 209 l l l l 127 44.40 80 PCT 12 P2 VS4 -.26 TEH TEC.610 SBAY2 14 C 186 l l l l 66 45.28 77 PCT 11 P2 VS3 -.86 TEH TEC.610 SBAY2 11 C 94 l l l l 90 45.45 114 PCT 15 P2 VS3 1.16 TEH TEC.610 SBAY2 11 C 106 l l l l 116 45 4.47 93 PCT 50 P2 VS3.95 TEH TEC.610 SBAY2 14 C 201 l l 116 45 TBP P2 VS3.95 TEC TEH.610 SBAY2 29 H 48 l l 116 45 3.59 98 PCT 47 P10 VS3.77 TEC TEH.610 SBAY2 31 H 12 l l 116 45 3.59 98 PCT 46 P9 VS3.86 TEC TEH.610 SBAY2 31 H 12 l l 116 45 7.07 103 WAR.75 P30 VS3.96 VS3 TEH.610 ZYAX2 34 H 74 l l l l 126 45.43 108 PCT 12 P2 VS2 -.59 TEH TEC.610 SBAY2 14 C 196 l l 126 45.34 91 PCT 10 P2 VS3 -.60 TEH TEC.610 SBAY2 14 C 196 l l l l 113 46.20 130 NQI 3 10H 19.95 TEH TEC.610 SBAY2 15 C 6 l l 113 46 NDF P15 10H 19.95 VS3 TEH.610 ZYAX2 34 H 75 l l l l 121 46.44 113 PCT 14 P2 VS3 -.87 TEH TEC.610 SBAY2 15 C 10 l l l l 88 47.38 113 PCT 12 P2 VS2 -.79 TEH TEC.610 SBAY2 12 C 60 l l l l 122 47.30 91 PCT 11 P2 VS3.84 TEH TEC.610 SBAY2 15 C 38 l l l l 144 47.25 124 PCT 10 P2 11H.69 TEH TEC.610 SBAY2 15 C 27 l l 144 47 NDF P11 TSH 1.02 01H TEH.610 ZYAX2 32 H 11 l l l l 113 48.35 42 PCT 11 P2 BW1.96 TEH TEC.610 SBAY2 16 C 7 l l l l 115 48.33 94 PCT 10 P2 VS3 -.74 TEH TEC.610 SBAY2 16 C 8 l l l l 117 48.37 119 PCT 11 P2 VS3 -1.17 TEH TEC.610 SBAY2 16 C 9 l l l l 143 48.34 139 PCT 12 P2 11H.77 TEH TEC.610 SBAY2 15 C 77 l l l l 90 49.41 102 PCT 14 P2 10C -1.24 TEH TEC.610 SBAY2 11 C 62 l
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
l ROW COL VOLTS DEG IND PER CRLEN CHN LOCN INCH1 INCH2 BEGT ENDT PDIA PTYPE CAL L IDX UTIL1 UTIL2l
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
4 ST Max
SG - 31 Calls of Interest Palo Verde 3 U3R20 PVNGS3 20180401 04/20/2018 13:40:22
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
l ROW COL VOLTS DEG IND PER CRLEN CHN LOCN INCH1 INCH2 BEGT ENDT PDIA PTYPE CAL L IDX UTIL1 UTIL2l
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
l l l 114 49.40 64 PCT 12 P2 VS1.95 TEH TEC.610 SBAY2 16 C 35 l l l l 118 49.34 28 PCT 10 P2 VS4 -.72 TEH TEC.610 SBAY2 16 C 33 l l l l 95 50.41 117 PCT 12 P2 10H.75 TEH TEC.610 SBAY2 12 C 23 l l l l 105 50.31 119 PCT 11 P2 10H.74 TEH TEC.610 SBAY2 15 C 54 l l l l 125 50.26 68 PCT 10 P2 VS3 -.94 TEH TEC.610 SBAY2 15 C 64 l l l l 134 51.27 116 PCT 10 P2 VS1.90 TEH TEC.610 SBAY2 17 C 126 l l l l 144 51.26 66 PCT 10 P2 VS2 -.94 TEH TEC.610 SBAY2 17 C 131 l l 144 51.39 127 PCT 13 P2 VS2 1.15 TEH TEC.610 SBAY2 17 C 131 l l l l 97 52.41 127 PCT 12 P2 10H.89 TEH TEC.610 SBAY2 16 C 47 l l l l 125 52.39 89 PCT 11 P2 VS3 -.97 TEH TEC.610 SBAY2 16 C 61 l l l l 127 52.38 104 PCT 11 P2 VS1 -.69 TEH TEC.610 SBAY2 16 C 62 l l l l 131 52.96 82 PCT 22 P2 VS2 -.59 TEH TEC.610 SBAY2 16 C 64 l l 131 52.80 93 PCT 19 P2 VS3 -.88 TEH TEC.610 SBAY2 16 C 64 l l 131 52.70 73 PCT 18 P2 VS4 -.81 TEH TEC.610 SBAY2 16 C 64 l l 131 52.51 67 PCT 14 P2 VS5 -.70 TEH TEC.610 SBAY2 16 C 64 l l 131 52 2.12 301 WAR.69 P30 VS2 -.80 VS3 TEH.610 ZYAX2 34 H 70 l l 131 52 2.24 302 WAR.66 P30 VS3 -1.18 VS3 TEH.610 ZYAX2 34 H 70 l l l l 130 53.48 105 PCT 13 P2 VS2 -.80 TEH TEC.610 SBAY2 18 C 100 l l l l 134 53.46 107 PCT 12 P2 VS1 -.72 TEH TEC.610 SBAY2 18 C 102 l l l l 97 54.31 113 PCT 12 P2 10H.75 TEH TEC.610 SBAY2 19 C 54 l l l l 121 54.40 122 PCT 14 P2 VS2 -.82 TEH TEC.610 SBAY2 19 C 66 l l l l 125 54.56 100 PCT 17 P2 VS3 -.93 TEH TEC.610 SBAY2 19 C 68 l l l l 127 54.38 76 PCT 13 P2 VS4 -.25 TEH TEC.610 SBAY2 19 C 69 l l l l 56 55.55 62 PCT 15 P2 BW1 -1.70 TEH TEC.610 SBAY2 10 C 246 l l l l 98 55.38 107 PCT 13 P2 10H.80 TEH TEC.610 SBAY2 19 C 73 l
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
l ROW COL VOLTS DEG IND PER CRLEN CHN LOCN INCH1 INCH2 BEGT ENDT PDIA PTYPE CAL L IDX UTIL1 UTIL2l
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
5 ST Max
SG - 31 Calls of Interest Palo Verde 3 U3R20 PVNGS3 20180401 04/20/2018 13:40:22
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
l ROW COL VOLTS DEG IND PER CRLEN CHN LOCN INCH1 INCH2 BEGT ENDT PDIA PTYPE CAL L IDX UTIL1 UTIL2l
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
l l l 116 55.29 132 PCT 11 P2 VS2 -.71 TEH TEC.610 SBAY2 19 C 82 l l l l 118 55.33 75 PCT 12 P2 VS2 -.77 TEH TEC.610 SBAY2 19 C 83 l l l l 126 55.24 143 PCT 10 P2 VS1.47 TEH TEC.610 SBAY2 19 C 145 l l 126 55.35 119 PCT 13 P2 VS2 -.91 TEH TEC.610 SBAY2 19 C 145 l l 126 55.67 125 PCT 19 P2 VS3 1.11 TEH TEC.610 SBAY2 19 C 145 l l 126 55 1.28 113 PCT 28 P2 VS3 1.33 TEH TEC.610 SBAY2 19 C 145 l l 126 55.87 115 PCT 23 P2 VS4 -1.02 TEH TEC.610 SBAY2 19 C 145 l l 126 55 1.64 80 WAR.38 P16 VS3.83 VS3 TEC.610 ZYAX2 32 C 57 l l 126 55 1.87 101 WAR.37 P17 VS4 -1.09 VS3 TEC.610 ZYAX2 32 C 57 l l 126 55 1.99 111 WAR.55 P30 VS3 1.10 VS3 TEH.610 ZYAX2 34 H 65 l l l l 47 56.31 101 PCT 11 P2 VS3.82 TEH TEC.610 SBAY2 7 C 59 l l l l 82 57.32 79 PCT 12 P2 VS2.81 TEH TEC.610 SBAY2 9 C 245 l l l l 94 57.28 124 PCT 11 P2 10H.75 TEH TEC.610 SBAY2 9 C 250 l l l l 142 57.48 106 PCT 14 P2 VS1.89 TEH TEC.610 SBAY2 22 C 14 l l l l 109 58.29 100 PCT 11 P2 BW1 -1.83 TEH TEC.610 SBAY2 19 C 92 l l l l 125 58.46 79 PCT 15 P2 VS3 -.92 TEH TEC.610 SBAY2 21 C 29 l l l l 8 59.36 24 PCT 11 P2 08C.67 TEH TEC.610 SBAY2 26 C 35 l l l l 66 59.30 102 PCT 10 P2 VS2 -.75 TEH TEC.610 SBAY2 10 C 207 l l l l 124 59 1.05 87 PCT 25 P2 VS4 -.83 TEH TEC.610 SBAY2 19 C 102 l l 124 59 1.20 111 WAR.33 P16 VS4 -.82 VS3 TEC.610 ZYAX2 32 C 55 l l l l 126 59.83 102 PCT 22 P2 VS4 -1.04 TEH TEC.610 SBAY2 21 C 30 l l 126 59 1.60 107 WAR.31 P17 VS4 -1.00 VS3 TEC.610 ZYAX2 32 C 56 l l l l 128 59.55 87 PCT 17 P2 VS2.82 TEH TEC.610 SBAY2 21 C 31 l l l l 144 59.35 132 PCT 13 P2 VS2 1.24 TEH TEC.610 SBAY2 21 C 39 l l 144 59.31 114 PCT 12 P2 VS3 -.70 TEH TEC.610 SBAY2 21 C 39 l l l l 154 59.38 109 PCT 14 P2 VS4.55 TEH TEC.610 SBAY2 19 C 13 l l l l 67 60.49 139 PCT 16 P2 VS2 -.86 TEH TEC.610 SBAY2 9 C 222 l
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
l ROW COL VOLTS DEG IND PER CRLEN CHN LOCN INCH1 INCH2 BEGT ENDT PDIA PTYPE CAL L IDX UTIL1 UTIL2l
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
6 ST Max
SG - 31 Calls of Interest Palo Verde 3 U3R20 PVNGS3 20180401 04/20/2018 13:40:22
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
l ROW COL VOLTS DEG IND PER CRLEN CHN LOCN INCH1 INCH2 BEGT ENDT PDIA PTYPE CAL L IDX UTIL1 UTIL2l
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
l l l 85 60.32 139 PCT 12 P2 BW1 1.17 TEH TEC.610 SBAY2 17 C 107 l l l l 123 60.36 84 PCT 11 P2 VS3 -1.19 TEH TEC.610 SBAY2 22 C 27 l l l l 145 60.41 83 PCT 12 P2 VS3.36 TEH TEC.610 SBAY2 22 C 16 l l l l 54 61.25 97 PCT 10 P2 BW1 -1.16 TEH TEC.610 SBAY2 9 C 181 l l l l 56 61.48 111 PCT 16 P2 BW1 -1.75 TEH TEC.610 SBAY2 9 C 182 l l l l 62 61.37 88 PCT 13 P2 VS2 -.70 TEH TEC.610 SBAY2 9 C 185 l l l l 66 61.36 45 PCT 13 P2 VS2 -.77 TEH TEC.610 SBAY2 9 C 187 l l l l 82 61.38 115 PCT 13 P2 VS4.41 TEH TEC.610 SBAY2 9 C 195 l l l l 88 61.50 116 PCT 16 P2 VS2.67 TEH TEC.610 SBAY2 9 C 198 l l l l 96 61.44 93 PCT 13 P2 10H.22 TEH TEC.610 SBAY2 20 C 121 l l l l 122 61.44 113 PCT 13 P2 VS3 1.19 TEH TEC.610 SBAY2 20 C 108 l l l l 126 61.39 98 PCT 12 P2 VS1.60 TEH TEC.610 SBAY2 22 C 29 l l l l 142 61.38 82 PCT 12 P2 VS3.81 TEH TEC.610 SBAY2 22 C 37 l l l l 144 61.79 89 PCT 20 P2 VS4 -.86 TEH TEC.610 SBAY2 22 C 38 l l 144 61 1.42 103 WAR.26 P24 VS4 -.74 VS3 TEC.610 ZYAX2 32 C 60 l l l l 47 62.29 91 PCT 9 P2 VS3.83 TEH TEC.610 SBAY2 6 C 133 l l l l 99 62.44 150 PCT 14 P2 10H.69 TEH TEC.610 SBAY2 19 C 117 l l l l 121 62.55 104 PCT 17 P2 VS2.82 TEH TEC.610 SBAY2 19 C 128 l l 121 62.46 119 PCT 15 P2 VS3.90 TEH TEC.610 SBAY2 19 C 128 l l l l 62 63.36 55 PCT 11 P2 VS2 -.92 TEH TEC.610 SBAY2 10 C 161 l l l l 94 63.55 122 PCT 15 P2 10H.66 TEH TEC.610 SBAY2 10 C 177 l l l l 128 63.21 99 PCT 9 P2 VS2.78 TEH TEC.610 SBAY2 21 C 56 l l l l 138 63.33 92 PCT 12 P2 VS1.97 TEH TEC.610 SBAY2 21 C 61 l
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
l ROW COL VOLTS DEG IND PER CRLEN CHN LOCN INCH1 INCH2 BEGT ENDT PDIA PTYPE CAL L IDX UTIL1 UTIL2l
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
7 ST Max
SG - 31 Calls of Interest Palo Verde 3 U3R20 PVNGS3 20180401 04/20/2018 13:40:22
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
l ROW COL VOLTS DEG IND PER CRLEN CHN LOCN INCH1 INCH2 BEGT ENDT PDIA PTYPE CAL L IDX UTIL1 UTIL2l
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
l l l 105 64.36 48 PCT 11 P2 VS2 -.71 TEH TEC.610 SBAY2 20 C 127 l l l l 107 64.51 75 PCT 15 P2 VS3 -1.03 TEH TEC.610 SBAY2 20 C 128 l l l l 109 64.39 53 PCT 12 P2 VS2 -.84 TEH TEC.610 SBAY2 20 C 129 l l l l 117 64.40 99 PCT 12 P2 VS3 -1.27 TEH TEC.610 SBAY2 20 C 133 l l l l 90 65.31 89 PCT 12 P2 BW1 -.83 TEH TEC.610 SBAY2 9 C 155 l l l l 124 65.47 115 PCT 14 P2 VS2.69 TEH TEC.610 SBAY2 22 C 55 l l 124 65.38 111 PCT 12 P2 VS3 -.77 TEH TEC.610 SBAY2 22 C 55 l l l l 126 65.72 99 PCT 19 P2 VS1.37 TEH TEC.610 SBAY2 22 C 56 l l 126 65.98 107 PCT 23 P2 VS3 -.82 TEH TEC.610 SBAY2 22 C 56 l l 126 65 1.18 102 PCT 26 P2 VS4 -1.11 TEH TEC.610 SBAY2 22 C 56 l l 126 65 1.79 107 WAR.32 P31 VS3 -.57 VS3 TEC.610 ZYAX2 32 C 54 l l 126 65 2.74 91 WAR.62 P17 VS4 -1.09 VS3 TEC.610 ZYAX2 32 C 54 l l l l 140 65.33 117 PCT 11 P2 VS1 -.61 TEH TEC.610 SBAY2 22 C 67 l l l l 121 66.36 113 PCT 13 P2 VS4 -.67 TEH TEC.610 SBAY2 21 C 135 l l l l 46 67.38 99 PCT 12 P2 VS3.98 TEH TEC.610 SBAY2 6 C 85 l l l l 98 67.30 115 PCT 11 P2 VS2 -.78 TEH TEC.610 SBAY2 21 C 148 l l l l 118 67.27 119 PCT 10 P2 VS2.96 TEH TEC.610 SBAY2 21 C 158 l l 118 67.52 133 PCT 16 P2 VS3 -.30 TEH TEC.610 SBAY2 21 C 158 l l l l 126 67.42 106 PCT 14 P2 VS1.42 TEH TEC.610 SBAY2 21 C 162 l l 126 67.40 125 PCT 14 P2 VS3 -.70 TEH TEC.610 SBAY2 21 C 162 l l 126 67.86 117 PCT 22 P2 VS4 -.98 TEH TEC.610 SBAY2 21 C 162 l l 126 67 1.52 100 WAR.40 P16 VS4 -1.03 VS3 TEC.610 ZYAX2 32 C 51 l l l l 128 67.25 124 PCT 10 P2 VS1.64 TEH TEC.610 SBAY2 21 C 163 l l 128 67.95 105 PCT 24 P2 VS2.82 TEH TEC.610 SBAY2 21 C 163 l l 128 67.42 105 PCT 14 P2 VS3 -.64 TEH TEC.610 SBAY2 21 C 163 l l 128 67.91 104 PCT 23 P2 VS4 -.73 TEH TEC.610 SBAY2 21 C 163 l l 128 67 2.24 108 WAR.53 P17 VS4 -.91 VS3 TEC.610 ZYAX2 32 C 52 l l 128 67 2.48 300 WAR.64 P30 VS2.81 VS3 TEH.610 ZYAX2 34 H 63 l l l l 130 67.55 95 PCT 17 P2 VS2.86 TEH TEC.610 SBAY2 21 C 84 l
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
l ROW COL VOLTS DEG IND PER CRLEN CHN LOCN INCH1 INCH2 BEGT ENDT PDIA PTYPE CAL L IDX UTIL1 UTIL2l
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
8 ST Max
SG - 31 Calls of Interest Palo Verde 3 U3R20 PVNGS3 20180401 04/20/2018 13:40:22
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
l ROW COL VOLTS DEG IND PER CRLEN CHN LOCN INCH1 INCH2 BEGT ENDT PDIA PTYPE CAL L IDX UTIL1 UTIL2l
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
l 130 67.35 78 PCT 12 P2 VS3 -.78 TEH TEC.610 SBAY2 21 C 84 l l 130 67 1.27 103 PCT 27 P2 VS4 -.65 TEH TEC.610 SBAY2 21 C 84 l l 130 67 2.74 99 WAR.58 P17 VS4 -.74 VS3 TEC.610 ZYAX2 32 C 53 l l l l 158 67.29 75 PCT 11 P2 BW1 1.11 TEH TEC.610 SBAY2 19 C 43 l l l l 87 68.33 86 PCT 12 P2 VS2 -.87 TEH TEC.610 SBAY2 9 C 117 l l l l 89 68.36 81 PCT 13 P2 VS2 -.79 TEH TEC.610 SBAY2 9 C 116 l l l l 91 68.36 62 PCT 13 P2 BW2.94 TEH TEC.610 SBAY2 9 C 115 l l l l 97 68.30 89 PCT 10 P2 VS2 -.70 TEH TEC.610 SBAY2 22 C 156 l l l l 92 69.14 109 PCT 6 P2 09H.89 TEH TEC.610 SBAY2 9 C 112 l l 92 69.29 134 PCT 11 P2 10H.97 TEH TEC.610 SBAY2 9 C 112 l l l l 122 69.54 102 PCT 15 P2 VS1.90 TEH TEC.610 SBAY2 22 C 171 l l l l 128 69.36 110 PCT 11 P2 VS2 -.72 TEH TEC.610 SBAY2 22 C 88 l l 128 69.62 114 PCT 17 P2 VS3 -.55 TEH TEC.610 SBAY2 22 C 88 l l l l 162 69.34 103 PCT 12 P2 07H.83 TEH TEC.610 SBAY2 19 C 36 l l 162 69 NDF P26 TSH.79 01H TEH.610 ZYAX2 32 H 9 l l l l 113 70.53 82 PCT 17 P2 VS2 -.82 TEH TEC.610 SBAY2 21 C 172 l l l l 54 71.29 107 PCT 9 P2 09H -.75 TEH TEC.610 SBAY2 10 C 68 l l l l 72 71.30 80 PCT 10 P2 VS2 -.79 TEH TEC.610 SBAY2 10 C 77 l l l l 128 71.18 129 PCT 8 P2 VS1.78 TEH TEC.610 SBAY2 23 C 9 l l l l 121 72.38 85 PCT 12 P2 VS2 -.79 TEH TEC.610 SBAY2 22 C 177 l l l l 80 73.41 112 PCT 14 P2 VS3.90 TEH TEC.610 SBAY2 9 C 72 l l l l 114 73.38 94 PCT 12 P2 VS2.91 TEH TEC.610 SBAY2 22 C 199 l l l l 130 73.37 84 PCT 11 P2 VS3 -.74 TEH TEC.610 SBAY2 22 C 120 l l l l 47 74.35 82 PCT 12 P2 BW2.46 TEC TEH.610 SBAY2 7 H 122 l l 47 74 NDF P1 08H 19.78 26.38 VS3 TEH.610 ZYAX2 34 H 30 l l l
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
l ROW COL VOLTS DEG IND PER CRLEN CHN LOCN INCH1 INCH2 BEGT ENDT PDIA PTYPE CAL L IDX UTIL1 UTIL2l
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
9 ST Max
SG - 31 Calls of Interest Palo Verde 3 U3R20 PVNGS3 20180401 04/20/2018 13:40:22
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
l ROW COL VOLTS DEG IND PER CRLEN CHN LOCN INCH1 INCH2 BEGT ENDT PDIA PTYPE CAL L IDX UTIL1 UTIL2l
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
l 51 74.46 123 PCT 15 P2 VS3.75 TEC TEH.610 SBAY2 7 H 124 l l l l 125 74.23 116 PCT 10 P2 VS3 -.84 TEH TEC.610 SBAY2 23 C 16 l l l l 127 74.28 111 PCT 11 P2 VS3.40 TEH TEC.610 SBAY2 23 C 17 l l l l 157 74.27 127 PCT 11 P2 VS5 -.70 TEH TEC.610 SBAY2 23 C 32 l l l l 161 74.32 118 PCT 13 P2 VS5 -.83 TEH TEC.610 SBAY2 23 C 34 l l l l 165 74.31 59 PCT 12 P2 BW2 -.99 TEH TEC.610 SBAY2 19 C 44 l l l l 46 75.25 115 PCT 9 P2 BW2.88 TEC TEH.610 SBAY2 7 H 100 l l l l 86 75.29 132 PCT 10 P2 09H.36 TEC TEH.610 SBAY2 15 H 137 l l l l 140 75.35 49 PCT 13 P2 BW1 -.88 TEH TEC.610 SBAY2 23 C 47 l l l l 164 75.34 88 PCT 13 P2 10H.77 TEH TEC.610 SBAY2 23 C 35 l l 164 75 1.09 125 PCT 26 P2 BW2.77 TEH TEC.610 SBAY2 23 C 35 l l 164 75 2.76 139 WAR.32 P9 BW2.93 VS3 TEC.610 ZYAX2 32 C 64 l l l l 35 76.25 95 PCT 11 P2 04H.65 TEC TEH.610 SBAY2 8 H 85 l l l l 47 76.33 110 PCT 14 P2 BW2.96 TEC TEH.610 SBAY2 8 H 91 l l l l 165 76.97 90 PCT 23 P2 BW2.90 TEH TEC.610 SBAY2 24 C 35 l l 165 76 2.36 127 WAR.35 P9 BW2.90 VS3 TEC.610 ZYAX2 32 C 65 l l l l 24 77.27 84 PCT 10 P2 BW2 -1.12 TEH TEC.610 SBAY2 5 C 46 l l l l 42 77.48 138 PCT 18 P2 BW1 -.90 TEC TEH.610 SBAY2 8 H 71 l l l l 46 77.25 81 PCT 11 P2 BW2.95 TEC TEH.610 SBAY2 8 H 69 l l l l 48 77.30 110 PCT 13 P2 BW2.70 TEC TEH.610 SBAY2 8 H 68 l l l l 112 77.32 133 PCT 11 P2 VS2.80 TEC TEH.610 SBAY2 15 H 76 l l l l 116 77.54 90 PCT 16 P2 VS2.85 TEH TEC.610 SBAY2 24 C 61 l l l l 128 77.78 97 PCT 20 P2 VS3 -.65 TEH TEC.610 SBAY2 24 C 55 l l 128 77 1.20 111 WAR.59 P15 VS3 -.62 VS3 TEH.610 ZYAX2 34 H 59 l l l
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
l ROW COL VOLTS DEG IND PER CRLEN CHN LOCN INCH1 INCH2 BEGT ENDT PDIA PTYPE CAL L IDX UTIL1 UTIL2l
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
10 ST Max
SG - 31 Calls of Interest Palo Verde 3 U3R20 PVNGS3 20180401 04/20/2018 13:40:22
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
l ROW COL VOLTS DEG IND PER CRLEN CHN LOCN INCH1 INCH2 BEGT ENDT PDIA PTYPE CAL L IDX UTIL1 UTIL2l
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
l 164 77.29 76 PCT 10 P2 10H.67 TEH TEC.610 SBAY2 24 C 37 l l 164 77.72 96 PCT 19 P2 BW2.77 TEH TEC.610 SBAY2 24 C 37 l l l l 166 77.79 66 PCT 21 P2 BW2.88 TEH TEC.610 SBAY2 24 C 36 l l 166 77 1.84 135 WAR.27 P8 BW2.98 VS3 TEC.610 ZYAX2 32 C 66 l l l l 41 78.40 121 PCT 13 P2 BW1 -.61 TEC TEH.610 SBAY2 7 H 79 l l l l 45 78.30 102 PCT 11 P2 BW1 -1.10 TEC TEH.610 SBAY2 7 H 81 l l l l 47 78.36 71 PCT 12 P2 BW2 1.04 TEC TEH.610 SBAY2 7 H 82 l l l l 49 78.49 121 PCT 15 P2 BW2.32 TEC TEH.610 SBAY2 7 H 83 l l l l 51 78.43 38 PCT 14 P2 09H -.92 TEC TEH.610 SBAY2 7 H 84 l l l l 89 78.32 92 PCT 13 P2 09H.65 TEC TEH.610 SBAY2 16 H 135 l l l l 97 78.27 85 PCT 11 P2 VS2 -.98 TEC TEH.610 SBAY2 16 H 139 l l l l 159 78.32 73 PCT 13 P2 BW2 -.84 TEH TEC.610 SBAY2 23 C 82 l l l l 161 78.30 29 PCT 12 P2 BW2 -.91 TEH TEC.610 SBAY2 23 C 83 l l l l 163 78.49 83 PCT 17 P2 BW2 -.84 TEH TEC.610 SBAY2 23 C 84 l l 163 78.37 125 PCT 14 P2 BW2.82 TEH TEC.610 SBAY2 23 C 84 l l l l 165 78.55 116 PCT 18 P2 BW2 -.98 TEH TEC.610 SBAY2 23 C 85 l l l l 30 79.33 118 PCT 11 P2 08C -.85 TEC TEH.610 SBAY2 7 H 69 l l l l 32 79.46 132 PCT 14 P2 BW1 -.96 TEC TEH.610 SBAY2 7 H 68 l l l l 42 79.33 123 PCT 11 P2 08H -.08 TEC TEH.610 SBAY2 7 H 63 l l 42 79.34 132 PCT 12 P2 VS3 -.67 TEC TEH.610 SBAY2 7 H 63 l l l l 48 79.51 80 PCT 16 P2 BW2.86 TEC TEH.610 SBAY2 7 H 60 l l l l 76 79.61 121 PCT 20 P2 VS2.64 TEC TEH.610 SBAY2 16 H 117 l l 76 79 2.19 120 WAR.70 P29 VS2.90 VS3 TEH.610 ZYAX2 34 H 29 l l l l 122 79.26 47 PCT 11 P2 VS1.85 TEH TEC.610 SBAY2 23 C 98 l l l l 158 79.44 101 PCT 16 P2 BW2.86 TEH TEC.610 SBAY2 23 C 99 l
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
l ROW COL VOLTS DEG IND PER CRLEN CHN LOCN INCH1 INCH2 BEGT ENDT PDIA PTYPE CAL L IDX UTIL1 UTIL2l
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
11 ST Max
SG - 31 Calls of Interest Palo Verde 3 U3R20 PVNGS3 20180401 04/20/2018 13:40:22
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
l ROW COL VOLTS DEG IND PER CRLEN CHN LOCN INCH1 INCH2 BEGT ENDT PDIA PTYPE CAL L IDX UTIL1 UTIL2l
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
l l l 162 79.44 74 PCT 16 P2 BW2 -.75 TEH TEC.610 SBAY2 23 C 88 l l l l 164 79.29 97 PCT 12 P2 VS2 -.82 TEH TEC.610 SBAY2 23 C 87 l l l l 166 79.29 93 PCT 12 P2 10H.77 TEH TEC.610 SBAY2 23 C 86 l l 166 79.37 74 PCT 14 P2 BW2 -.83 TEH TEC.610 SBAY2 23 C 86 l l l l 33 80.88 112 PCT 25 P2 BW1.90 TEC TEH.610 SBAY2 8 H 42 l l 33 80 TBP P2 BW1.90 TEC TEH.610 SBAY2 29 H 46 l l 33 80 1.95 81 WAR.59 P9 BW1 1.06 VS3 TEH.610 ZYAX2 34 H 28 l l l l 37 80.32 96 PCT 14 P2 BW1 -.99 TEC TEH.610 SBAY2 8 H 44 l l l l 39 80.50 118 PCT 18 P2 BW1 -1.09 TEC TEH.610 SBAY2 8 H 45 l l l l 45 80.22 48 PCT 10 P2 BW2 1.03 TEC TEH.610 SBAY2 8 H 48 l l l l 53 80.20 103 PCT 10 P2 BW1 -1.12 TEC TEH.610 SBAY2 8 H 52 l l l l 103 80.56 99 PCT 19 P2 VS3 -.90 TEC TEH.610 SBAY2 16 H 86 l l l l 105 80.33 103 PCT 13 P2 VS3 -.84 TEC TEH.610 SBAY2 16 H 87 l l l l 121 80.41 79 PCT 13 P2 VS3.88 TEH TEC.610 SBAY2 24 C 66 l l l l 163 80.48 69 PCT 15 P2 BW2.85 TEH TEC.610 SBAY2 24 C 87 l l l l 32 81.85 109 PCT 25 P2 BW1.98 TEC TEH.610 SBAY2 8 H 40 l l 32 81 TBP P2 BW1.98 TEC TEH.610 SBAY2 29 H 47 l l 32 81 1.54 318 WAR.29 P9 BW1 1.35 VS3 TEH.610 ZYAX2 34 H 26 l l l l 34 81.28 96 PCT 12 P2 06H.94 TEC TEH.610 SBAY2 8 H 39 l l 34 81.74 117 PCT 23 P2 BW1.98 TEC TEH.610 SBAY2 8 H 39 l l 34 81 1.91 84 WAR.37 P9 BW1 1.30 VS3 TEH.610 ZYAX2 34 H 27 l l l l 36 81.41 103 PCT 16 P2 BW1 1.12 TEC TEH.610 SBAY2 8 H 38 l l l l 44 81.48 90 PCT 18 P2 VS3.97 TEC TEH.610 SBAY2 8 H 34 l l l l 78 81.24 100 PCT 10 P2 VS3.72 TEC TEH.610 SBAY2 16 H 60 l l l l 90 81.26 102 PCT 11 P2 10H -1.07 TEC TEH.610 SBAY2 16 H 50 l l l
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
l ROW COL VOLTS DEG IND PER CRLEN CHN LOCN INCH1 INCH2 BEGT ENDT PDIA PTYPE CAL L IDX UTIL1 UTIL2l
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
12 ST Max
SG - 31 Calls of Interest Palo Verde 3 U3R20 PVNGS3 20180401 04/20/2018 13:40:22
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
l ROW COL VOLTS DEG IND PER CRLEN CHN LOCN INCH1 INCH2 BEGT ENDT PDIA PTYPE CAL L IDX UTIL1 UTIL2l
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
l 98 81.24 82 PCT 10 P2 BW1.85 TEC TEH.610 SBAY2 16 H 42 l l l l 122 81.30 64 PCT 10 P2 VS1.86 TEH TEC.610 SBAY2 24 C 99 l l l l 35 82.35 147 PCT 12 P2 BW1.94 TEC TEH.610 SBAY2 7 H 37 l l l l 37 82.46 97 PCT 15 P2 BW1 -1.08 TEC TEH.610 SBAY2 7 H 38 l l 37 82.20 141 PCT 9 P2 08C.79 TEC TEH.610 SBAY2 7 H 38 l l l l 39 82.49 111 PCT 15 P2 BW1 -1.18 TEC TEH.610 SBAY2 7 H 39 l l l l 45 82.31 125 PCT 11 P2 BW1.95 TEC TEH.610 SBAY2 7 H 42 l l 45 82.31 93 PCT 11 P2 BW2.85 TEC TEH.610 SBAY2 7 H 42 l l l l 47 82.55 112 PCT 16 P2 BW2.96 TEC TEH.610 SBAY2 7 H 43 l l l l 51 82.33 124 PCT 11 P2 BW1 -.98 TEC TEH.610 SBAY2 7 H 45 l l l l 97 82.27 130 PCT 10 P2 10H.74 TEC TEH.610 SBAY2 15 H 64 l l l l 165 82.52 121 PCT 17 P2 BW2.98 TEC TEH.610 SBAY2 27 H 121 l l l l 167 82.44 104 PCT 15 P2 BW2.86 TEC TEH.610 SBAY2 28 H 67 l l l l 46 83.33 88 PCT 11 P2 BW2 -.87 TEC TEH.610 SBAY2 7 H 31 l l l l 50 83.65 104 PCT 18 P2 09H -.23 TEC TEH.610 SBAY2 7 H 29 l l 50 83.63 112 PCT 18 P2 VS3 -.90 TEC TEH.610 SBAY2 7 H 29 l l l l 118 83.80 116 PCT 22 P2 VS3 -.38 TEC TEH.610 SBAY2 27 H 93 l l 118 83 2.04 109 WAR.57 P15 VS3 -.25 VS3 TEH.610 ZYAX2 34 H 58 l l l l 168 83.25 138 PCT 10 P2 BW2 -.89 TEC TEH.610 SBAY2 27 H 67 l l l l 37 84.28 102 PCT 13 P2 BW1 -1.09 TEC TEH.610 SBAY2 6 H 213 l l l l 39 84.77 118 PCT 24 P2 BW1 -1.55 TEC TEH.610 SBAY2 6 H 214 l l 39 84 1.85 272 WAR.26 P27 BW1 -1.39 VS3 TEH.610 ZYAX2 34 H 25 l l l l 41 84.27 60 PCT 12 P2 08H -.87 TEC TEH.610 SBAY2 6 H 215 l l l l 43 84.26 99 PCT 12 P2 BW1 -1.58 TEC TEH.610 SBAY2 6 H 216 l l 43 84.20 138 PCT 10 P2 BW1.50 TEC TEH.610 SBAY2 6 H 216 l l l
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
l ROW COL VOLTS DEG IND PER CRLEN CHN LOCN INCH1 INCH2 BEGT ENDT PDIA PTYPE CAL L IDX UTIL1 UTIL2l
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
13 ST Max
SG - 31 Calls of Interest Palo Verde 3 U3R20 PVNGS3 20180401 04/20/2018 13:40:22
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
l ROW COL VOLTS DEG IND PER CRLEN CHN LOCN INCH1 INCH2 BEGT ENDT PDIA PTYPE CAL L IDX UTIL1 UTIL2l
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
l 45 84.30 128 PCT 13 P2 BW1.73 TEC TEH.610 SBAY2 6 H 218 l l 45 84.22 112 PCT 11 P2 VS3.80 TEC TEH.610 SBAY2 6 H 218 l l l l 47 84.21 122 PCT 10 P2 08H.08 TEC TEH.610 SBAY2 6 H 219 l l 47 84.70 118 PCT 23 P2 BW1.34 TEC TEH.610 SBAY2 6 H 219 l l 47 84.40 118 PCT 16 P2 BW2.45 TEC TEH.610 SBAY2 6 H 219 l l 47 84 1.70 83 WAR.46 P9 BW1 1.15 VS3 TEH.610 ZYAX2 34 H 21 l l l l 49 84.35 117 PCT 15 P2 08H.79 TEC TEH.610 SBAY2 6 H 220 l l l l 53 84.21 112 PCT 10 P2 VS3.91 TEC TEH.610 SBAY2 6 H 222 l l l l 167 84.68 43 SVI.00 P48 TSC.23 01C TEC.610 ZYAX2 31 C 49 l l l l 40 85.25 74 PCT 12 P2 08H.11 TEC TEH.610 SBAY2 6 H 209 l l 40 85.20 120 PCT 10 P2 VS3 -.74 TEC TEH.610 SBAY2 6 H 209 l l l l 46 85.60 119 PCT 21 P2 BW1 -.93 TEC TEH.610 SBAY2 6 H 206 l l 46 85 1.60 263 WAR.54 P27 BW1 -1.15 VS3 TEH.610 ZYAX2 34 H 20 l l l l 48 85.43 86 PCT 17 P2 VS3 -.97 TEC TEH.610 SBAY2 6 H 205 l l l l 52 85.23 141 PCT 11 P2 VS3.67 TEC TEH.610 SBAY2 6 H 203 l l l l 116 85.31 127 PCT 11 P2 VS2.85 TEC TEH.610 SBAY2 28 H 40 l l l l 122 85.38 88 PCT 13 P2 VS2.92 TEC TEH.610 SBAY2 28 H 37 l l 122 85.68 114 PCT 20 P2 VS4.44 TEC TEH.610 SBAY2 28 H 37 l l 122 85.84 53 WAR.15 P33 VS4.53 VS3 TEC.610 ZYAX2 32 C 50 l l l l 164 85.25 67 PCT 10 P2 VS2 1.00 TEC TEH.610 SBAY2 28 H 16 l l l l 166 85.36 126 SVI.00 P39 TSC.12 01C TEC.610 ZYAX2 31 C 48 l l l l 39 86 1.43 106 PCT 30 P2 BW1.56 TEC TEH.610 SBAY2 5 H 161 l l 39 86 TBP P2 BW1.56 TEC TEH.610 SBAY2 29 H 44 l l 39 86 2.87 78 WAR.72 P9 BW1.50 VS3 TEH.610 ZYAX2 34 H 24 l l l l 41 86.35 135 PCT 12 P2 08C.81 TEC TEH.610 SBAY2 5 H 162 l l l l 45 86.62 125 PCT 21 P2 BW1.48 TEC TEH.610 SBAY2 6 H 217 l l 45 86 1.14 98 WAR.25 P9 BW1.79 VS3 TEH.610 ZYAX2 34 H 19 l l l l 47 86.56 109 PCT 17 P2 BW1.59 TEC TEH.610 SBAY2 5 H 165 l
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
l ROW COL VOLTS DEG IND PER CRLEN CHN LOCN INCH1 INCH2 BEGT ENDT PDIA PTYPE CAL L IDX UTIL1 UTIL2l
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
14 ST Max
SG - 31 Calls of Interest Palo Verde 3 U3R20 PVNGS3 20180401 04/20/2018 13:40:22
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
l ROW COL VOLTS DEG IND PER CRLEN CHN LOCN INCH1 INCH2 BEGT ENDT PDIA PTYPE CAL L IDX UTIL1 UTIL2l
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
l l l 49 86.38 123 PCT 13 P2 BW1.36 TEC TEH.610 SBAY2 5 H 166 l l 49 86.41 92 PCT 14 P2 BW2.34 TEC TEH.610 SBAY2 5 H 166 l l l l 51 86.31 122 PCT 11 P2 BW1 -.98 TEC TEH.610 SBAY2 5 H 167 l l l l 63 86.40 114 PCT 13 P2 VS3.91 TEC TEH.610 SBAY2 7 H 16 l l l l 65 86.43 132 PCT 14 P2 09H.71 TEC TEH.610 SBAY2 7 H 15 l l l l 115 86.35 134 PCT 13 P2 VS3.65 TEC TEH.610 SBAY2 27 H 39 l l 115 86.44 129 PCT 15 P2 VS4 -.75 TEC TEH.610 SBAY2 27 H 39 l l l l 127 86.20 49 PCT 8 P2 VS4.84 TEC TEH.610 SBAY2 27 H 45 l l l l 42 87.49 127 PCT 15 P2 BW2 -.95 TEC TEH.610 SBAY2 5 H 159 l l l l 118 87.70 92 PCT 20 P2 VS3.78 TEC TEH.610 SBAY2 27 H 37 l l 118 87 1.87 118 WAR.60 P30 VS3 1.13 VS3 TEH.610 ZYAX2 34 H 57 l l l l 124 87.26 133 PCT 10 P2 VS3 -.65 TEC TEH.610 SBAY2 27 H 35 l l l l 41 88.71 118 PCT 19 P2 BW1 -1.38 TEC TEH.610 SBAY2 3 H 52 l l l l 43 88.31 108 PCT 11 P2 BW2.41 TEC TEH.610 SBAY2 5 H 163 l l l l 45 88.29 99 PCT 11 P2 BW1.43 TEC TEH.610 SBAY2 4 H 49 l l 45 88.32 127 PCT 12 P2 BW2 -1.26 TEC TEH.610 SBAY2 4 H 49 l l 45 88.26 63 PCT 10 P2 BW2.53 TEC TEH.610 SBAY2 4 H 49 l l l l 47 88.41 137 PCT 13 P2 BW1.89 TEC TEH.610 SBAY2 3 H 51 l l 47 88.71 114 PCT 19 P2 BW2 1.08 TEC TEH.610 SBAY2 3 H 51 l l l l 53 88.45 93 PCT 17 P2 VS3 -1.02 TEC TEH.610 SBAY2 4 H 19 l l l l 57 88.60 125 PCT 17 P2 VS3.79 TEC TEH.610 SBAY2 3 H 6 l l l l 79 88.24 123 PCT 11 P2 09H.82 TEC TEH.610 SBAY2 14 H 131 l l l l 97 88.21 106 PCT 10 P2 BW2.38 TEC TEH.610 SBAY2 14 H 142 l l l l 103 88.37 89 PCT 15 P2 VS2 -1.06 TEC TEH.610 SBAY2 14 H 145 l l l l 125 88.45 82 PCT 16 P2 VS3 -1.11 TEC TEH.610 SBAY2 26 H 219 l
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
l ROW COL VOLTS DEG IND PER CRLEN CHN LOCN INCH1 INCH2 BEGT ENDT PDIA PTYPE CAL L IDX UTIL1 UTIL2l
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
15 ST Max
SG - 31 Calls of Interest Palo Verde 3 U3R20 PVNGS3 20180401 04/20/2018 13:40:22
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
l ROW COL VOLTS DEG IND PER CRLEN CHN LOCN INCH1 INCH2 BEGT ENDT PDIA PTYPE CAL L IDX UTIL1 UTIL2l
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
l l l 42 89.64 111 PCT 18 P2 BW1 -.91 TEC TEH.610 SBAY2 3 H 53 l l l l 48 89.49 116 PCT 15 P2 09H -1.14 TEC TEH.610 SBAY2 3 H 50 l l l l 54 89.26 81 PCT 10 P2 VS3 -1.01 TEC TEH.610 SBAY2 4 H 20 l l l l 64 89.38 123 PCT 13 P2 09H.77 TEC TEH.610 SBAY2 5 H 148 l l l l 98 89.37 94 PCT 13 P2 10H.78 TEC TEH.610 SBAY2 13 H 75 l l l l 102 89.30 125 PCT 11 P2 VS3 -.86 TEC TEH.610 SBAY2 13 H 77 l l l l 128 89.30 126 PCT 12 P2 VS1.54 TEC TEH.610 SBAY2 26 H 209 l l l l 130 89.32 82 PCT 13 P2 VS1.79 TEC TEH.610 SBAY2 26 H 208 l l l l 166 89.96 86 PCT 26 P2 BW2.98 TEC TEH.610 SBAY2 26 H 190 l l 166 89 2.48 125 WAR.34 P3 BW2.62 VS3 TEC.610 ZYAX2 33 C 6 l l l l 170 89.46 132 PCT 15 P2 BW2.54 TEC TEH.610 SBAY2 27 H 122 l l l l 43 90 6.56 99 PCT 56 P2 BW1 -1.08 TEC TEH.610 SBAY2 3 H 54 l l 43 90.69 118 PCT 19 P2 BW1 -.36 TEC TEH.610 SBAY2 3 H 54 l l 43 90 TBP P2 BW1 -1.08 TEC TEH.610 SBAY2 29 H 39 l l 43 90 5.29 92 PCT 54 P10 BW1 -.87 TEC TEH.610 SBAY2 31 H 5 l l 43 90 5.29 92 PCT 53 P9 BW1 -.84 TEC TEH.610 SBAY2 31 H 5 l l 43 90 9.09 97 WAR.47 P27 BW1 -.64 VS3 TEH.610 ZYAX2 34 H 18 l l 43 90 1.09 135 WAR.39 P27 BW1 -.10 VS3 TEH.610 ZYAX2 34 H 18 l l l l 45 90.60 109 PCT 20 P2 BW2 -1.33 TEC TEH.610 SBAY2 4 H 97 l l 45 90 2.04 94 WAR.31 P19 BW2 -.72 VS3 TEC.610 ZYAX2 32 C 26 l l l l 89 90.64 120 PCT 18 P2 VS2 -.92 TEC TEH.610 SBAY2 13 H 140 l l l l 111 90.18 117 PCT 7 P2 VS3 -.91 TEC TEH.610 SBAY2 13 H 151 l l l l 127 90.44 50 PCT 14 P2 VS3 -1.01 TEC TEH.610 SBAY2 25 H 231 l l l l 147 90.20 63 PCT 8 P2 BW1.77 TEC TEH.610 SBAY2 25 H 241 l l l l 44 91 1.88 109 PCT 33 P2 BW1 1.05 TEC TEH.610 SBAY2 3 H 55 l l 44 91.66 104 PCT 18 P2 VS3 -.84 TEC TEH.610 SBAY2 3 H 55 l l 44 91.77 107 PCT 20 P2 BW2 -.92 TEC TEH.610 SBAY2 3 H 55 l
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
l ROW COL VOLTS DEG IND PER CRLEN CHN LOCN INCH1 INCH2 BEGT ENDT PDIA PTYPE CAL L IDX UTIL1 UTIL2l
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
16 ST Max
SG - 31 Calls of Interest Palo Verde 3 U3R20 PVNGS3 20180401 04/20/2018 13:40:22
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
l ROW COL VOLTS DEG IND PER CRLEN CHN LOCN INCH1 INCH2 BEGT ENDT PDIA PTYPE CAL L IDX UTIL1 UTIL2l
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
l 44 91 TBP P2 BW1 1.05 TEC TEH.610 SBAY2 29 H 37 l l 44 91.97 76 WAR.23 P19 BW2 -1.03 VS3 TEC.610 ZYAX2 32 C 27 l l 44 91 2.22 77 WAR.34 P8 BW1.93 VS3 TEH.610 ZYAX2 34 H 16 l l 44 91 1.35 280 WAR.25 P6 VS3 -.54 VS3 TEH.610 ZYAX2 34 H 16 l l l l 46 91.30 137 PCT 11 P2 BW1 -1.05 TEC TEH.610 SBAY2 4 H 96 l l 46 91.56 110 PCT 17 P2 BW2 -.94 TEC TEH.610 SBAY2 4 H 96 l l l l 48 91.47 108 PCT 17 P2 BW1 -.98 TEC TEH.610 SBAY2 4 H 51 l l 48 91.28 129 PCT 11 P2 BW1.76 TEC TEH.610 SBAY2 4 H 51 l l 48 91.30 106 PCT 13 P2 VS3 -1.02 TEC TEH.610 SBAY2 4 H 51 l l l l 58 91.29 107 PCT 10 P2 BW1 -1.94 TEC TEH.610 SBAY2 3 H 18 l l l l 80 91.21 104 PCT 10 P2 VS3.76 TEC TEH.610 SBAY2 14 H 60 l l l l 82 91.26 85 PCT 12 P2 VS2.60 TEC TEH.610 SBAY2 14 H 61 l l l l 88 91.21 78 PCT 10 P2 BW1 -.85 TEC TEH.610 SBAY2 14 H 64 l l l l 96 91.25 80 PCT 11 P2 10H.82 TEC TEH.610 SBAY2 14 H 70 l l l l 162 91.30 69 PCT 11 P2 BW1 -.99 TEC TEH.610 SBAY2 25 H 193 l l l l 164 91.27 35 PCT 10 P2 BW2 -1.35 TEC TEH.610 SBAY2 25 H 192 l l l l 170 91.28 120 PCT 10 P2 BW2.83 TEC TEH.610 SBAY2 25 H 189 l l l l 45 92.70 119 PCT 19 P2 BW1 -.89 TEC TEH.610 SBAY2 3 H 56 l l 45 92.37 118 PCT 12 P2 BW2 -.97 TEC TEH.610 SBAY2 3 H 56 l l l l 47 92.48 130 PCT 17 P2 BW1.40 TEC TEH.610 SBAY2 4 H 95 l l 47 92.90 99 PCT 25 P2 BW2 1.10 TEC TEH.610 SBAY2 4 H 95 l l 47 92 TBP P2 BW2 1.10 TEC TEH.610 SBAY2 29 H 35 l l 47 92 2.36 132 WAR.37 P5 BW2.93 VS3 TEC.610 ZYAX2 32 C 28 l l l l 49 92 1.19 117 PCT 29 P2 BW1.35 TEC TEH.610 SBAY2 4 H 52 l l 49 92 1.47 114 PCT 33 P2 BW2.95 TEC TEH.610 SBAY2 4 H 52 l l 49 92 TBP P2 BW1.35 TEC TEH.610 SBAY2 29 H 34 l l 49 92 2.61 122 WAR.41 P4 BW2 1.27 VS3 TEC.610 ZYAX2 32 C 29 l l 49 92 2.55 83 WAR.60 P9 BW1.59 VS3 TEH.610 ZYAX2 34 H 15 l l l l 51 92.35 81 PCT 12 P2 BW1 -.93 TEC TEH.610 SBAY2 3 H 47 l l l
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
l ROW COL VOLTS DEG IND PER CRLEN CHN LOCN INCH1 INCH2 BEGT ENDT PDIA PTYPE CAL L IDX UTIL1 UTIL2l
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
17 ST Max
SG - 31 Calls of Interest Palo Verde 3 U3R20 PVNGS3 20180401 04/20/2018 13:40:22
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
l ROW COL VOLTS DEG IND PER CRLEN CHN LOCN INCH1 INCH2 BEGT ENDT PDIA PTYPE CAL L IDX UTIL1 UTIL2l
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
l 53 92.32 98 PCT 11 P2 VS3.81 TEC TEH.610 SBAY2 3 H 26 l l l l 65 92.35 135 PCT 14 P2 09H.74 TEC TEH.610 SBAY2 4 H 9 l l l l 97 92.43 98 PCT 14 P2 10H.86 TEC TEH.610 SBAY2 9 H 209 l l l l 119 92.23 106 PCT 10 P2 VS2 -.94 TEC TEH.610 SBAY2 2 H 212 l l l l 161 92.23 72 PCT 10 P2 VS2 -.97 TEC TEH.610 SBAY2 2 H 191 l l l l 165 92.33 92 PCT 14 P2 BW2.96 TEC TEH.610 SBAY2 2 H 189 l l l l 46 93 2.24 104 PCT 36 P2 BW1 -.88 TEC TEH.610 SBAY2 3 H 57 l l 46 93.80 117 PCT 21 P2 BW1.91 TEC TEH.610 SBAY2 3 H 57 l l 46 93 TBP P2 BW1 -.88 TEC TEH.610 SBAY2 29 H 36 l l 46 93 4.78 271 WAR.98 P27 BW1 -.81 VS3 TEH.610 ZYAX2 34 H 13 l l 46 93 2.28 77 WAR.68 P9 BW1.96 VS3 TEH.610 ZYAX2 34 H 13 l l l l 48 93.75 104 PCT 23 P2 BW1 -.84 TEC TEH.610 SBAY2 4 H 94 l l 48 93.41 123 PCT 16 P2 VS3 -.96 TEC TEH.610 SBAY2 4 H 94 l l 48 93 1.38 110 PCT 32 P2 BW2.91 TEC TEH.610 SBAY2 4 H 94 l l 48 93 TBP P2 BW2.91 TEC TEH.610 SBAY2 29 H 33 l l 48 93 1.76 82 WAR.35 P5 BW2.99 VS3 TEC.610 ZYAX2 32 C 30 l l 48 93 2.66 263 WAR.71 P27 BW1 -.46 VS3 TEH.610 ZYAX2 34 H 14 l l 48 93 1.26 295 WAR.22 P23 VS3 -.79 VS3 TEH.610 ZYAX2 34 H 14 l l l l 60 93 1.29 122 PCT 27 P2 VS4 -1.04 TEC TEH.610 SBAY2 3 H 16 l l 60 93 1.26 95 WAR.32 P21 VS4 -1.21 VS3 TEC.610 ZYAX2 32 C 36 l l l l 90 93.47 100 PCT 15 P2 10H -1.15 TEC TEH.610 SBAY2 11 H 11 l l l l 108 93.21 111 PCT 10 P2 09H.73 TEC TEH.610 SBAY2 2 H 155 l l l l 114 93.31 115 PCT 13 P2 VS4.69 TEC TEH.610 SBAY2 2 H 158 l l l l 160 93.28 121 PCT 12 P2 BW2 -1.27 TEC TEH.610 SBAY2 2 H 181 l l l l 47 94.33 104 PCT 11 P2 BW1 1.04 TEC TEH.610 SBAY2 3 H 58 l l l l 49 94.26 74 PCT 10 P2 BW1 -1.28 TEC TEH.610 SBAY2 4 H 93 l l 49 94.34 135 PCT 14 P2 BW1.35 TEC TEH.610 SBAY2 4 H 93 l l 49 94.29 78 PCT 11 P2 VS3.98 TEC TEH.610 SBAY2 4 H 93 l l l l 71 94.26 104 PCT 12 P2 VS3 -.93 TEC TEH.610 SBAY2 6 H 174 l
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
l ROW COL VOLTS DEG IND PER CRLEN CHN LOCN INCH1 INCH2 BEGT ENDT PDIA PTYPE CAL L IDX UTIL1 UTIL2l
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
18 ST Max
SG - 31 Calls of Interest Palo Verde 3 U3R20 PVNGS3 20180401 04/20/2018 13:40:22
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
l ROW COL VOLTS DEG IND PER CRLEN CHN LOCN INCH1 INCH2 BEGT ENDT PDIA PTYPE CAL L IDX UTIL1 UTIL2l
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
l l l 111 94 1.02 121 PCT 25 P2 VS2 -.98 TEC TEH.610 SBAY2 13 H 6 l l 111 94.52 105 PCT 16 P2 VS3.71 TEC TEH.610 SBAY2 13 H 6 l l 111 94 2.51 292 WAR.62 P30 VS2 -.87 VS3 TEH.610 ZYAX2 34 H 68 l l 111 94 1.34 116 WAR.44 P15 VS3.63 VS3 TEH.610 ZYAX2 34 H 68 l l l l 139 94.25 58 PCT 10 P2 BW1.74 TEC TEH.610 SBAY2 1 H 197 l l l l 167 94.28 140 PCT 10 P2 BW2 -.77 TEC TEH.610 SBAY2 1 H 183 l l l l 48 95.61 112 PCT 17 P2 VS3 1.03 TEC TEH.610 SBAY2 3 H 59 l l 48 95 1.68 99 PCT 32 P2 BW2.78 TEC TEH.610 SBAY2 3 H 59 l l 48 95 TBP P2 BW2.78 TEC TEH.610 SBAY2 29 H 32 l l 48 95 2.19 84 WAR.34 P5 BW2.97 VS3 TEC.610 ZYAX2 32 C 31 l l l l 50 95.52 109 PCT 18 P2 VS3.70 TEC TEH.610 SBAY2 4 H 92 l l 50 95.52 101 PCT 18 P2 BW2.87 TEC TEH.610 SBAY2 4 H 92 l l l l 56 95.28 59 PCT 10 P2 BW2 1.83 TEC TEH.610 SBAY2 3 H 29 l l l l 70 95.30 114 PCT 13 P2 08H.05 TEC TEH.610 SBAY2 6 H 173 l l l l 128 95.40 115 PCT 14 P2 VS3.72 TEC TEH.610 SBAY2 1 H 159 l l l l 47 96.50 126 PCT 15 P2 BW1.86 TEC TEH.610 SBAY2 3 H 89 l l l l 49 96.43 138 PCT 13 P2 BW1.54 TEC TEH.610 SBAY2 3 H 60 l l l l 97 96.28 124 PCT 10 P2 VS3 -.91 TEC TEH.610 SBAY2 11 H 20 l l l l 99 96.27 116 PCT 10 P2 VS3 -1.06 TEC TEH.610 SBAY2 11 H 21 l l l l 107 96.22 77 PCT 10 P2 VS3 -.94 TEC TEH.610 SBAY2 2 H 148 l l l l 111 96.69 108 PCT 22 P2 VS2 -.91 TEC TEH.610 SBAY2 2 H 146 l l 111 96 1.80 294 WAR.69 P31 VS2 -.97 VS3 TEH.610 ZYAX2 34 H 67 l l l l 121 96.28 107 PCT 12 P2 VS2 -.93 TEC TEH.610 SBAY2 2 H 141 l l l l 48 97.29 130 PCT 10 P2 VS3 -.94 TEC TEH.610 SBAY2 3 H 88 l l 48 97.41 78 PCT 13 P2 VS3.92 TEC TEH.610 SBAY2 3 H 88 l l l l 54 97.27 70 PCT 12 P2 09H.80 TEC TEH.610 SBAY2 4 H 57 l l 54 97.53 106 PCT 17 P2 VS3 -.73 TEC TEH.610 SBAY2 4 H 57 l
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
l ROW COL VOLTS DEG IND PER CRLEN CHN LOCN INCH1 INCH2 BEGT ENDT PDIA PTYPE CAL L IDX UTIL1 UTIL2l
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
19 ST Max
SG - 31 Calls of Interest Palo Verde 3 U3R20 PVNGS3 20180401 04/20/2018 13:40:22
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
l ROW COL VOLTS DEG IND PER CRLEN CHN LOCN INCH1 INCH2 BEGT ENDT PDIA PTYPE CAL L IDX UTIL1 UTIL2l
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
l l l 60 97.25 120 PCT 10 P2 VS2 -.83 TEC TEH.610 SBAY2 4 H 39 l l l l 64 97.29 162 PCT 11 P2 VS2.71 TEC TEH.610 SBAY2 5 H 121 l l l l 66 97.20 92 PCT 10 P2 VS3.55 TEC TEH.610 SBAY2 6 H 190 l l l l 90 97.38 108 PCT 15 P2 10H -1.18 TEC TEH.610 SBAY2 10 H 255 l l l l 106 97.22 68 PCT 10 P2 VS2.84 TEC TEH.610 SBAY2 2 H 83 l l l l 114 97.33 101 PCT 14 P2 VS2.76 TEC TEH.610 SBAY2 2 H 87 l l l l 118 97.30 92 PCT 13 P2 VS3.82 TEC TEH.610 SBAY2 2 H 89 l l l l 130 97.42 112 PCT 16 P2 VS3 -.90 TEC TEH.610 SBAY2 2 H 95 l l l l 132 97.24 103 PCT 11 P2 VS1.71 TEC TEH.610 SBAY2 2 H 96 l l l l 148 97.24 104 PCT 11 P2 BW2 -1.39 TEC TEH.610 SBAY2 2 H 104 l l l l 47 98 3.63 109 PCT 47 P2 BW1.39 TEC TEH.610 SBAY2 4 H 99 l l 47 98 3.50 106 PCT 47 P2 BW2 -1.05 TEC TEH.610 SBAY2 4 H 99 l l 47 98 TBP P2 BW2 -1.05 TEC TEH.610 SBAY2 29 H 31 l l 47 98 3.49 102 PCT 46 P10 BW1.56 TEC TEH.610 SBAY2 31 H 6 l l 47 98 3.49 102 PCT 46 P9 BW1.59 TEC TEH.610 SBAY2 31 H 6 l l 47 98 3.27 98 PCT 45 P9 BW2 -.56 TEC TEH.610 SBAY2 31 H 6 l l 47 98 3.27 98 PCT 45 P10 BW2 -.54 TEC TEH.610 SBAY2 31 H 6 l l 47 98 6.50 92 WAR.39 P18 BW2 -.81 VS3 TEC.610 ZYAX2 32 C 33 l l 47 98 4.89 82 WAR.51 P9 BW1.44 VS3 TEH.610 ZYAX2 34 H 12 l l l l 49 98.46 114 PCT 14 P2 BW1 -1.26 TEC TEH.610 SBAY2 3 H 87 l l 49 98.86 120 PCT 22 P2 BW2 -.79 TEC TEH.610 SBAY2 3 H 87 l l 49 98 1.73 131 WAR.30 P19 BW2 -.98 VS3 TEC.610 ZYAX2 32 C 32 l l l l 59 98.30 112 PCT 10 P2 VS2 -1.25 TEC TEH.610 SBAY2 3 H 32 l l l l 71 98.35 100 PCT 12 P2 VS3 -.90 TEC TEH.610 SBAY2 5 H 105 l l l l 89 98.37 71 PCT 12 P2 VS2.76 TEC TEH.610 SBAY2 13 H 129 l l 89 98.85 111 PCT 22 P2 VS3 -.97 TEC TEH.610 SBAY2 13 H 129 l l 89 98.68 106 PCT 19 P2 VS4.90 TEC TEH.610 SBAY2 13 H 129 l l 89 98 2.30 100 WAR.43 P17 VS3 -.94 VS3 TEC.610 ZYAX2 32 C 37 l l 89 98 2.24 102 WAR.23 P24 VS4.69 VS3 TEC.610 ZYAX2 32 C 37 l
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
l ROW COL VOLTS DEG IND PER CRLEN CHN LOCN INCH1 INCH2 BEGT ENDT PDIA PTYPE CAL L IDX UTIL1 UTIL2l
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
20 ST Max
SG - 31 Calls of Interest Palo Verde 3 U3R20 PVNGS3 20180401 04/20/2018 13:40:22
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
l ROW COL VOLTS DEG IND PER CRLEN CHN LOCN INCH1 INCH2 BEGT ENDT PDIA PTYPE CAL L IDX UTIL1 UTIL2l
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
l l l 91 98.32 138 PCT 13 P2 09H.53 TEC TEH.610 SBAY2 10 H 251 l l l l 111 98.26 90 PCT 10 P2 BW1 -.86 TEC TEH.610 SBAY2 1 H 142 l l l l 131 98.27 132 PCT 10 P2 BW1 -.79 TEC TEH.610 SBAY2 1 H 132 l l 131 98.31 110 PCT 11 P2 BW1.93 TEC TEH.610 SBAY2 1 H 132 l l l l 50 99.92 113 PCT 22 P2 BW2 -.88 TEC TEH.610 SBAY2 3 H 86 l l 50 99 2.22 100 WAR.29 P18 BW2 -1.00 VS3 TEC.610 ZYAX2 32 C 34 l l l l 76 99.57 140 PCT 17 P2 09H.84 TEC TEH.610 SBAY2 9 H 183 l l l l 94 99.28 134 PCT 10 P2 09H.83 TEC TEH.610 SBAY2 9 H 174 l l l l 124 99.27 120 PCT 10 P2 VS1.75 TEC TEH.610 SBAY2 1 H 88 l l l l 126 99.42 112 PCT 14 P2 VS3 -.76 TEC TEH.610 SBAY2 1 H 89 l l l l 128 99.30 142 PCT 11 P2 VS1.72 TEC TEH.610 SBAY2 1 H 90 l l l l 160 99.27 94 PCT 10 P2 BW2.51 TEC TEH.610 SBAY2 1 H 106 l l l l 168 99.36 108 PCT 12 P2 03C.88 TEC TEH.610 SBAY2 1 H 110 l l l l 47 100.90 101 PCT 25 P2 BW2.95 TEC TEH.610 SBAY2 4 H 135 l l 47 100 TBP P2 BW2.95 TEC TEH.610 SBAY2 29 H 26 l l 47 100 2.16 119 WAR.27 P4 BW2.83 VS3 TEC.610 ZYAX2 32 C 35 l l l l 107 100.26 78 PCT 11 P2 VS3 -.92 TEC TEH.610 SBAY2 2 H 77 l l l l 109 100.23 73 PCT 10 P2 VS3 -1.02 TEC TEH.610 SBAY2 2 H 76 l l l l 169 100.31 103 PCT 13 P2 04C.84 TEC TEH.610 SBAY2 2 H 46 l l l l 50 101.28 68 PCT 11 P2 VS3 -.95 TEC TEH.610 SBAY2 4 H 101 l l l l 52 101.52 114 PCT 15 P2 VS3 -.86 TEC TEH.610 SBAY2 3 H 84 l l l l 54 101.76 100 PCT 20 P2 BW1 -1.26 TEC TEH.610 SBAY2 3 H 65 l l 54 101.32 107 PCT 11 P2 VS3 -.93 TEC TEH.610 SBAY2 3 H 65 l l 54 101 2.16 267 WAR.56 P26 BW1 -1.11 VS3 TEH.610 ZYAX2 34 H 10 l l l l 66 101.67 126 PCT 22 P2 VS3.67 TEC TEH.610 SBAY2 4 H 32 l
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
l ROW COL VOLTS DEG IND PER CRLEN CHN LOCN INCH1 INCH2 BEGT ENDT PDIA PTYPE CAL L IDX UTIL1 UTIL2l
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
21 ST Max
SG - 31 Calls of Interest Palo Verde 3 U3R20 PVNGS3 20180401 04/20/2018 13:40:22
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
l ROW COL VOLTS DEG IND PER CRLEN CHN LOCN INCH1 INCH2 BEGT ENDT PDIA PTYPE CAL L IDX UTIL1 UTIL2l
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
l 66 101 1.56 108 WAR.65 P22 VS3 1.04 VS3 TEH.610 ZYAX2 34 H 7 l l l l 74 101.30 128 PCT 11 P2 08H.61 TEC TEH.610 SBAY2 5 H 89 l l 74 101.39 123 PCT 13 P2 09H -.27 TEC TEH.610 SBAY2 5 H 89 l l 74 101.27 133 PCT 10 P2 09H.88 TEC TEH.610 SBAY2 5 H 89 l l l l 76 101.61 113 PCT 20 P2 09H 1.04 TEC TEH.610 SBAY2 10 H 243 l l 76 101 1.46 118 WAR.31 P13 09H.55 09H TEH.610 ZYAX2 32 H 20 l l l l 84 101.30 134 PCT 11 P2 09H.66 TEC TEH.610 SBAY2 13 H 123 l l l l 96 101.31 67 PCT 11 P2 10H.81 TEC TEH.610 SBAY2 11 H 31 l l l l 118 101.44 126 PCT 16 P2 VS3.50 TEC TEH.610 SBAY2 2 H 18 l l l l 120 101.22 94 PCT 10 P2 VS2.84 TEC TEH.610 SBAY2 2 H 19 l l l l 122 101.22 98 PCT 10 P2 VS1.76 TEC TEH.610 SBAY2 2 H 20 l l l l 130 101.23 137 PCT 10 P2 VS4.70 TEC TEH.610 SBAY2 2 H 24 l l l l 53 102 1.97 109 PCT 34 P2 VS3 -.91 TEC TEH.610 SBAY2 3 H 83 l l 53 102 TBP P2 VS3 -.91 TEC TEH.610 SBAY2 29 H 29 l l 53 102 4.11 290 WAR.66 P31 VS3 -.62 VS3 TEH.610 ZYAX2 34 H 11 l l l l 111 102.18 116 PCT 7 P2 VS2 -1.03 TEC TEH.610 SBAY2 1 H 74 l l l l 165 102.10 77 PCT 8 P2 11H.41 TEC TEH.610 SBAY2 1 H 47 l l l l 52 103.27 93 PCT 10 P2 BW1.69 TEC TEH.610 SBAY2 4 H 103 l l l l 68 103.21 93 PCT 10 P2 09H.70 TEC TEH.610 SBAY2 6 H 162 l l l l 72 103.22 117 PCT 8 P2 09H -.24 TEC TEH.610 SBAY2 5 H 91 l l l l 74 103.29 140 PCT 11 P2 VS2 -.92 TEC TEH.610 SBAY2 5 H 86 l l l l 78 103.25 145 PCT 12 P2 09H.85 TEC TEH.610 SBAY2 6 H 112 l l l l 90 103.99 115 PCT 24 P2 10C -1.70 TEC TEH.610 SBAY2 9 H 160 l l 90 103 1.09 56 WAR.29 P12 10C -1.30 10C TEC.610 ZYAX2 32 C 38 l l l l 96 103.26 118 PCT 10 P2 BW1 -1.00 TEC TEH.610 SBAY2 13 H 26 l l l
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
l ROW COL VOLTS DEG IND PER CRLEN CHN LOCN INCH1 INCH2 BEGT ENDT PDIA PTYPE CAL L IDX UTIL1 UTIL2l
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
22 ST Max
SG - 31 Calls of Interest Palo Verde 3 U3R20 PVNGS3 20180401 04/20/2018 13:40:22
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
l ROW COL VOLTS DEG IND PER CRLEN CHN LOCN INCH1 INCH2 BEGT ENDT PDIA PTYPE CAL L IDX UTIL1 UTIL2l
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
l 102 103.53 126 PCT 16 P2 VS2.75 TEC TEH.610 SBAY2 13 H 23 l l l l 122 103.41 120 PCT 14 P2 VS3.95 TEC TEH.610 SBAY2 1 H 18 l l l l 132 103.38 104 PCT 13 P2 VS1.81 TEC TEH.610 SBAY2 1 H 23 l l l l 170 103.25 127 PCT 10 P2 11H.33 TEC TEH.610 SBAY2 1 H 44 l l l l 47 104.74 118 PCT 19 P2 BW1 -1.00 TEC TEH.610 SBAY2 3 H 119 l l 47 104.38 150 PCT 12 P2 BW2.49 TEC TEH.610 SBAY2 3 H 119 l l l l 49 104.45 91 PCT 14 P2 BW1 -1.16 TEC TEH.610 SBAY2 3 H 91 l l l l 67 104.32 83 PCT 14 P2 VS3 -1.07 TEC TEH.610 SBAY2 6 H 163 l l l l 71 104.51 98 PCT 16 P2 VS4 -.79 TEC TEH.610 SBAY2 5 H 92 l l l l 127 104.26 94 PCT 10 P2 VS3 -1.13 TEC TEH.610 SBAY2 17 H 75 l l l l 52 105.26 91 PCT 10 P2 VS3.93 TEC TEH.610 SBAY2 4 H 131 l l l l 76 105.49 133 PCT 18 P2 09H.79 TEC TEH.610 SBAY2 6 H 110 l l l l 98 105.44 114 PCT 14 P2 10H.83 TEC TEH.610 SBAY2 11 H 52 l l 98 105.28 71 PCT 10 P2 BW1.83 TEC TEH.610 SBAY2 11 H 52 l l l l 116 105.58 70 PCT 18 P2 VS2.91 TEC TEH.610 SBAY2 17 H 129 l l l l 150 105.33 83 PCT 12 P2 BW1 -1.29 TEC TEH.610 SBAY2 17 H 110 l l l l 47 106.91 107 PCT 26 P2 BW1 -.56 TEC TEH.610 SBAY2 6 H 26 l l 47 106.53 118 PCT 19 P2 VS3.78 TEC TEH.610 SBAY2 6 H 26 l l 47 106 TBP P2 BW1 -.56 TEC TEH.610 SBAY2 29 H 24 l l 47 106.79 237 WAR.42 P34 BW1 -1.10 VS3 TEH.610 ZYAX2 37 H 107 l l l l 75 106.38 102 PCT 16 P2 VS2 -1.01 TEC TEH.610 SBAY2 6 H 109 l l l l 79 106.33 112 PCT 13 P2 VS2.64 TEC TEH.610 SBAY2 10 H 196 l l l l 93 106.37 94 PCT 12 P2 BW1 -.82 TEC TEH.610 SBAY2 13 H 27 l l l l 95 106.26 125 PCT 10 P2 09H.83 TEC TEH.610 SBAY2 13 H 28 l l 95 106.29 111 PCT 10 P2 BW1 -.85 TEC TEH.610 SBAY2 13 H 28 l l l
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
l ROW COL VOLTS DEG IND PER CRLEN CHN LOCN INCH1 INCH2 BEGT ENDT PDIA PTYPE CAL L IDX UTIL1 UTIL2l
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
23 ST Max
SG - 31 Calls of Interest Palo Verde 3 U3R20 PVNGS3 20180401 04/20/2018 13:40:22
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
l ROW COL VOLTS DEG IND PER CRLEN CHN LOCN INCH1 INCH2 BEGT ENDT PDIA PTYPE CAL L IDX UTIL1 UTIL2l
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
l 99 106.23 109 PCT 9 P2 BW1 1.03 TEC TEH.610 SBAY2 13 H 30 l l l l 103 106.33 111 PCT 14 P2 VS3 -.93 TEC TEH.610 SBAY2 14 H 15 l l l l 109 106.37 124 PCT 15 P2 VS3 -.94 TEC TEH.610 SBAY2 14 H 18 l l l l 119 106.22 52 PCT 10 P2 VS2 -1.03 TEC TEH.610 SBAY2 18 H 84 l l l l 48 107.31 65 PCT 13 P2 VS3.87 TEC TEH.610 SBAY2 6 H 25 l l l l 50 107.28 112 PCT 10 P2 08H.77 TEC TEH.610 SBAY2 3 H 116 l l l l 52 107.30 96 PCT 10 P2 VS3.78 TEC TEH.610 SBAY2 3 H 94 l l l l 60 107.31 118 PCT 10 P2 VS3 -.91 TEC TEH.610 SBAY2 3 H 71 l l l l 66 107.32 120 PCT 14 P2 09H.60 TEC TEH.610 SBAY2 6 H 129 l l l l 88 107.34 122 PCT 12 P2 BW1.99 TEC TEH.610 SBAY2 9 H 142 l l l l 92 107.31 77 PCT 11 P2 BW1 -.84 TEC TEH.610 SBAY2 9 H 140 l l l l 94 107.24 124 PCT 9 P2 BW1 -1.25 TEC TEH.610 SBAY2 9 H 139 l l l l 98 107.24 107 PCT 9 P2 BW1.93 TEC TEH.610 SBAY2 13 H 41 l l l l 100 107.30 129 PCT 11 P2 10H.56 TEC TEH.610 SBAY2 13 H 40 l l l l 112 107.30 85 PCT 11 P2 VS4 -1.01 TEC TEH.610 SBAY2 13 H 34 l l l l 118 107.21 123 PCT 10 P2 VS3 -.37 TEC TEH.610 SBAY2 18 H 147 l l l l 124 107.31 86 PCT 13 P2 BW1.91 TEC TEH.610 SBAY2 18 H 144 l l l l 132 107.21 96 PCT 10 P2 VS1.70 TEC TEH.610 SBAY2 18 H 140 l l l l 160 107.25 70 PCT 11 P2 BW2 1.30 TEC TEH.610 SBAY2 18 H 122 l l l l 47 108.29 48 PCT 13 P2 BW1 -.40 TEC TEH.610 SBAY2 6 H 27 l l l l 67 108.33 101 PCT 12 P2 VS3 -.97 TEC TEH.610 SBAY2 5 H 96 l l l l 87 108 1.13 110 PCT 26 P2 VS4.77 TEC TEH.610 SBAY2 9 H 135 l l 87 108 2.58 105 WAR.32 P24 VS4.62 VS3 TEC.610 ZYAX2 32 C 39 l
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
l ROW COL VOLTS DEG IND PER CRLEN CHN LOCN INCH1 INCH2 BEGT ENDT PDIA PTYPE CAL L IDX UTIL1 UTIL2l
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
24 ST Max
SG - 31 Calls of Interest Palo Verde 3 U3R20 PVNGS3 20180401 04/20/2018 13:40:22
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
l ROW COL VOLTS DEG IND PER CRLEN CHN LOCN INCH1 INCH2 BEGT ENDT PDIA PTYPE CAL L IDX UTIL1 UTIL2l
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
l l l 89 108.72 114 PCT 20 P2 VS2 -.81 TEC TEH.610 SBAY2 9 H 136 l l 89 108 1.96 304 WAR.36 P7 VS2 -.48 VS3 TEH.610 ZYAX2 37 H 108 l l l l 103 108.27 84 PCT 10 P2 BW1 -.42 TEC TEH.610 SBAY2 11 H 59 l l 103 108.30 95 PCT 11 P2 VS2 -.98 TEC TEH.610 SBAY2 11 H 59 l l 103 108.30 121 PCT 11 P2 VS4.61 TEC TEH.610 SBAY2 11 H 59 l l 103 108.59 119 PCT 17 P2 VS4.98 TEC TEH.610 SBAY2 11 H 59 l l l l 105 108.50 108 PCT 16 P2 VS2.69 TEC TEH.610 SBAY2 11 H 60 l l 105 108.77 112 PCT 21 P2 VS3 -.82 TEC TEH.610 SBAY2 11 H 60 l l 105 108.40 101 PCT 13 P2 VS3 1.08 TEC TEH.610 SBAY2 11 H 60 l l 105 108.38 106 PCT 13 P2 VS4 -.86 TEC TEH.610 SBAY2 11 H 60 l l 105 108 2.07 296 WAR.45 P6 VS3 -.69 VS3 TEH.610 ZYAX2 37 H 22 l l 105 108.66 96 WAR.46 P23 VS3.89 VS3 TEH.610 ZYAX2 37 H 22 l l l l 107 108 1.07 115 PCT 25 P2 VS4 -.79 TEC TEH.610 SBAY2 11 H 61 l l 107 108 2.27 103 WAR.61 P1 VS4 -.78 VS3 TEC.610 ZYAX2 32 C 49 l l l l 109 108.31 123 PCT 11 P2 VS3 -.96 TEC TEH.610 SBAY2 11 H 62 l l l l 111 108.32 91 PCT 11 P2 VS2 -.91 TEC TEH.610 SBAY2 11 H 63 l l l l 113 108.56 147 PCT 17 P2 10H.80 TEC TEH.610 SBAY2 11 H 64 l l l l 117 108.31 142 PCT 11 P2 VS2 -1.17 TEC TEH.610 SBAY2 17 H 130 l l l l 171 108.71 106 PCT 22 P2 VS1 -.84 TEC TEH.610 SBAY2 20 H 25 l l 171 108.85 108 PCT 22 P2 VS1 -.84 TEC TEH.610 SBAY2 23 H 50 l l 171 108 1.83 287 WAR.29 P31 VS1 -.91 VS3 TEH.610 ZYAX2 37 H 33 l l l l 46 109 3.22 102 PCT 43 P2 BW1 -1.13 TEC TEH.610 SBAY2 5 H 23 l l 46 109.40 141 PCT 13 P2 BW1.99 TEC TEH.610 SBAY2 5 H 23 l l 46 109.34 97 PCT 12 P2 VS3.95 TEC TEH.610 SBAY2 5 H 23 l l 46 109.32 122 PCT 11 P2 BW2 -.80 TEC TEH.610 SBAY2 5 H 23 l l 46 109 TBP P2 BW1 -1.13 TEC TEH.610 SBAY2 29 H 30 l l 46 109 2.64 94 PCT 41 P9 BW1 -1.04 TEC TEH.610 SBAY2 31 H 7 l l 46 109 2.64 94 PCT 41 P10 BW1 -.95 TEC TEH.610 SBAY2 31 H 7 l l 46 109 5.07 282 WAR.47 P2 BW1 -.94 VS3 TEH.610 ZYAX2 37 H 99 l l l l 50 109.38 60 PCT 16 P2 VS3.83 TEC TEH.610 SBAY2 6 H 23 l l l l 58 109.37 112 PCT 15 P2 VS3 1.10 TEC TEH.610 SBAY2 4 H 108 l l l
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
l ROW COL VOLTS DEG IND PER CRLEN CHN LOCN INCH1 INCH2 BEGT ENDT PDIA PTYPE CAL L IDX UTIL1 UTIL2l
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
25 ST Max
SG - 31 Calls of Interest Palo Verde 3 U3R20 PVNGS3 20180401 04/20/2018 13:40:22
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
l ROW COL VOLTS DEG IND PER CRLEN CHN LOCN INCH1 INCH2 BEGT ENDT PDIA PTYPE CAL L IDX UTIL1 UTIL2l
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
l 82 109.37 151 PCT 12 P2 09H.89 TEC TEH.610 SBAY2 10 H 188 l l l l 92 109.89 112 PCT 25 P2 VS3 -.90 TEC TEH.610 SBAY2 10 H 181 l l 92 109 2.04 264 WAR.82 P22 VS3 -.73 VS3 TEH.610 ZYAX2 37 H 23 l l l l 98 109.38 107 PCT 15 P2 VS4 -.99 TEC TEH.610 SBAY2 14 H 27 l l l l 102 109.25 69 PCT 11 P2 VS2.77 TEC TEH.610 SBAY2 14 H 25 l l l l 112 109.26 92 PCT 10 P2 VS4 -.87 TEC TEH.610 SBAY2 11 H 67 l l l l 118 109.23 144 PCT 9 P2 VS4.58 TEC TEH.610 SBAY2 21 H 9 l l l l 122 109.35 109 PCT 12 P2 VS2.72 TEC TEH.610 SBAY2 21 H 11 l l 122 109.22 113 PCT 8 P2 VS3.66 TEC TEH.610 SBAY2 21 H 11 l l 122 109.31 86 PCT 11 P2 VS3.98 TEC TEH.610 SBAY2 21 H 11 l l l l 130 109.41 117 PCT 14 P2 VS1.81 TEC TEH.610 SBAY2 23 H 29 l l 130 109.32 116 PCT 11 P2 VS3.88 TEC TEH.610 SBAY2 23 H 29 l l 130 109.35 120 PCT 12 P2 VS4 -.78 TEC TEH.610 SBAY2 23 H 29 l l l l 132 109.38 100 PCT 13 P2 VS3.85 TEC TEH.610 SBAY2 23 H 30 l l l l 138 109.26 107 PCT 10 P2 BW1 -.82 TEC TEH.610 SBAY2 23 H 33 l l l l 47 110 3.22 106 PCT 43 P2 BW1 -.91 TEC TEH.610 SBAY2 5 H 22 l l 47 110 TBP P2 BW1 -.91 TEC TEH.610 SBAY2 29 H 14 l l 47 110 2.63 97 PCT 41 P9 BW1 -.41 TEC TEH.610 SBAY2 31 H 8 l l 47 110 2.63 97 PCT 41 P10 BW1 -.41 TEC TEH.610 SBAY2 31 H 8 l l 47 110 4.41 282 WAR.47 P2 BW1 -.80 VS3 TEH.610 ZYAX2 37 H 98 l l l l 49 110.63 131 PCT 21 P2 BW1.38 TEC TEH.610 SBAY2 6 H 28 l l 49 110 1.51 111 WAR.21 P16 BW1.88 VS3 TEH.610 ZYAX2 37 H 101 l l l l 51 110.42 125 PCT 17 P2 BW1 -.89 TEC TEH.610 SBAY2 6 H 22 l l l l 75 110.22 101 PCT 10 P2 VS3.89 TEC TEH.610 SBAY2 10 H 168 l l l l 83 110.36 132 PCT 14 P2 08H.87 TEC TEH.610 SBAY2 10 H 174 l l 83 110.24 139 PCT 10 P2 09H -.28 TEC TEH.610 SBAY2 10 H 174 l l l l 87 110.45 129 PCT 16 P2 09H.71 TEC TEH.610 SBAY2 10 H 176 l l l l 93 110.36 89 PCT 12 P2 VS2.75 TEC TEH.610 SBAY2 13 H 43 l
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
l ROW COL VOLTS DEG IND PER CRLEN CHN LOCN INCH1 INCH2 BEGT ENDT PDIA PTYPE CAL L IDX UTIL1 UTIL2l
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
26 ST Max
SG - 31 Calls of Interest Palo Verde 3 U3R20 PVNGS3 20180401 04/20/2018 13:40:22
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
l ROW COL VOLTS DEG IND PER CRLEN CHN LOCN INCH1 INCH2 BEGT ENDT PDIA PTYPE CAL L IDX UTIL1 UTIL2l
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
l 93 110.27 124 PCT 10 P2 VS3.78 TEC TEH.610 SBAY2 13 H 43 l l l l 95 110.40 107 PCT 13 P2 10H.80 TEC TEH.610 SBAY2 13 H 45 l l 95 110.34 127 PCT 12 P2 VS2.77 TEC TEH.610 SBAY2 13 H 45 l l 95 110.38 99 PCT 13 P2 VS4 -.78 TEC TEH.610 SBAY2 13 H 45 l l l l 103 110.50 135 PCT 16 P2 VS2 -.91 TEC TEH.610 SBAY2 13 H 49 l l l l 105 110.29 64 PCT 10 P2 VS4 -.85 TEC TEH.610 SBAY2 13 H 50 l l l l 107 110.26 118 PCT 10 P2 BW1 -1.55 TEC TEH.610 SBAY2 13 H 51 l l l l 109 110.24 90 PCT 9 P2 VS3.35 TEC TEH.610 SBAY2 13 H 52 l l l l 127 110.26 121 PCT 11 P2 VS1.39 TEC TEH.610 SBAY2 18 H 154 l l l l 48 111 4.92 97 PCT 51 P2 BW1 -.97 TEC TEH.610 SBAY2 5 H 21 l l 48 111.28 127 PCT 10 P2 BW1 1.02 TEC TEH.610 SBAY2 5 H 21 l l 48 111 TBP P2 BW1 -.97 TEC TEH.610 SBAY2 29 H 16 l l 48 111 4.05 91 PCT 49 P10 BW1 -.89 TEC TEH.610 SBAY2 31 H 9 l l 48 111 4.05 91 PCT 48 P9 BW1 -.83 TEC TEH.610 SBAY2 31 H 9 l l 48 111 7.67 277 WAR.59 P1 BW1 -.88 VS3 TEH.610 ZYAX2 37 H 100 l l l l 98 111.33 90 PCT 12 P2 BW1.97 TEC TEH.610 SBAY2 13 H 63 l l l l 102 111.39 118 PCT 13 P2 VS2.89 TEC TEH.610 SBAY2 13 H 61 l l l l 126 111.30 110 PCT 12 P2 VS3 -.68 TEC TEH.610 SBAY2 22 H 27 l l l l 162 111.31 80 PCT 13 P2 BW2 -1.39 TEC TEH.610 SBAY2 22 H 45 l l l l 45 112.33 74 PCT 14 P2 BW1 -1.43 TEC TEH.610 SBAY2 6 H 60 l l l l 47 112.13 114 PCT 9 P2 05H -.15 TEC TEH.610 SBAY2 5 H 24 l l 47 112 1.23 115 PCT 27 P2 BW1 -.90 TEC TEH.610 SBAY2 5 H 24 l l 47 112.60 115 PCT 18 P2 BW2.08 TEC TEH.610 SBAY2 5 H 24 l l 47 112 TBP P2 BW1 -.90 TEC TEH.610 SBAY2 29 H 17 l l 47 112 1.02 105 WAR.21 P33 BW1 -1.23 VS3 TEH.610 ZYAX2 37 H 102 l l l l 49 112.80 104 PCT 21 P2 BW1.43 TEC TEH.610 SBAY2 5 H 20 l l 49 112 1.60 110 WAR.34 P15 BW1.96 VS3 TEH.610 ZYAX2 37 H 106 l l l l 53 112.27 126 PCT 12 P2 BW1 -1.14 TEC TEH.610 SBAY2 6 H 20 l l l
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
l ROW COL VOLTS DEG IND PER CRLEN CHN LOCN INCH1 INCH2 BEGT ENDT PDIA PTYPE CAL L IDX UTIL1 UTIL2l
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
27 ST Max
SG - 31 Calls of Interest Palo Verde 3 U3R20 PVNGS3 20180401 04/20/2018 13:40:22
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
l ROW COL VOLTS DEG IND PER CRLEN CHN LOCN INCH1 INCH2 BEGT ENDT PDIA PTYPE CAL L IDX UTIL1 UTIL2l
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
l 65 112.43 108 PCT 14 P2 BW2.62 TEC TEH.610 SBAY2 5 H 78 l l l l 95 112.41 115 PCT 16 P2 10H -.15 TEC TEH.610 SBAY2 14 H 33 l l l l 103 112.46 120 PCT 17 P2 10H.84 TEC TEH.610 SBAY2 14 H 37 l l 103 112.20 127 PCT 10 P2 BW1 -.93 TEC TEH.610 SBAY2 14 H 37 l l l l 107 112.21 143 PCT 10 P2 BW1 -1.37 TEC TEH.610 SBAY2 14 H 39 l l l l 117 112.41 126 PCT 14 P2 VS2 -1.14 TEC TEH.610 SBAY2 21 H 39 l l l l 123 112.33 136 PCT 12 P2 VS1.65 TEC TEH.610 SBAY2 21 H 36 l l l l 159 112.29 94 PCT 12 P2 BW2 1.06 TEC TEH.610 SBAY2 22 H 55 l l l l 165 112.23 111 PCT 10 P2 BW2 -1.00 TEC TEH.610 SBAY2 22 H 52 l l l l 169 112.37 113 PCT 15 P2 BW2 1.00 TEC TEH.610 SBAY2 22 H 50 l l l l 46 113 1.00 104 PCT 27 P2 BW1 -.96 TEC TEH.610 SBAY2 6 H 59 l l 46 113.35 107 PCT 15 P2 BW2 -.90 TEC TEH.610 SBAY2 6 H 59 l l 46 113 TBP P2 BW1 -.96 TEC TEH.610 SBAY2 29 H 18 l l 46 113 1.70 117 WAR.59 P1 BW1 -.85 VS3 TEH.610 ZYAX2 37 H 103 l l l l 48 113.62 125 PCT 18 P2 VS3.87 TEC TEH.610 SBAY2 5 H 25 l l l l 98 113.54 125 PCT 19 P2 10H.75 TEC TEH.610 SBAY2 14 H 55 l l l l 128 113.20 150 PCT 9 P2 10C -.20 TEC TEH.610 SBAY2 21 H 48 l l l l 170 113.78 113 PCT 21 P2 BW2 1.24 TEC TEH.610 SBAY2 21 H 69 l l 170 113 1.97 121 WAR.32 P5 BW2.98 VS3 TEC.610 ZYAX2 33 C 25 l l l l 43 114.79 117 PCT 21 P2 BW1 -1.48 TEC TEH.610 SBAY2 5 H 51 l l 43 114.96 110 PCT 24 P2 BW2 -1.45 TEC TEH.610 SBAY2 5 H 51 l l 43 114 1.01 42 WAR.20 P41 BW2 -.89 VS3 TEC.610 ZYAX2 32 C 41 l l 43 114 1.45 118 WAR.30 P1 BW1 -.91 VS3 TEH.610 ZYAX2 37 H 97 l l l l 45 114 2.23 108 PCT 40 P2 BW1 -1.36 TEC TEH.610 SBAY2 6 H 61 l l 45 114.23 86 PCT 11 P2 BW1 -.66 TEC TEH.610 SBAY2 6 H 61 l l 45 114 TBP P2 BW1 -1.36 TEC TEH.610 SBAY2 29 H 19 l l 45 114 2.08 102 PCT 37 P9 BW1 -1.37 TEC TEH.610 SBAY2 31 H 10 l l 45 114 2.08 102 PCT 37 P10 BW1 -1.27 TEC TEH.610 SBAY2 31 H 10 l l 45 114 3.35 287 WAR.42 P32 BW1 -.91 VS3 TEH.610 ZYAX2 37 H 104 l
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
l ROW COL VOLTS DEG IND PER CRLEN CHN LOCN INCH1 INCH2 BEGT ENDT PDIA PTYPE CAL L IDX UTIL1 UTIL2l
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
28 ST Max
SG - 31 Calls of Interest Palo Verde 3 U3R20 PVNGS3 20180401 04/20/2018 13:40:22
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
l ROW COL VOLTS DEG IND PER CRLEN CHN LOCN INCH1 INCH2 BEGT ENDT PDIA PTYPE CAL L IDX UTIL1 UTIL2l
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
l l l 47 114.69 106 PCT 23 P2 BW1 -1.43 TEC TEH.610 SBAY2 6 H 58 l l 47 114.21 149 PCT 10 P2 BW1 -.37 TEC TEH.610 SBAY2 6 H 58 l l 47 114.48 130 PCT 18 P2 BW2 1.02 TEC TEH.610 SBAY2 6 H 58 l l 47 114 1.41 294 WAR.42 P32 BW1 -.91 BW2 TEH.610 ZYAX2 37 H 105 l l 47 114 1.15 128 WAR.00 P14 BW2.98 BW2 TEH.610 ZYAX2 37 H 105 l l l l 49 114.67 126 PCT 19 P2 BW1.89 TEC TEH.610 SBAY2 5 H 26 l l l l 93 114.26 114 PCT 12 P2 BW1 -.69 TEC TEH.610 SBAY2 14 H 82 l l l l 99 114.37 131 PCT 15 P2 10H.68 TEC TEH.610 SBAY2 14 H 107 l l l l 117 114.32 86 PCT 13 P2 VS2 -1.09 TEC TEH.610 SBAY2 22 H 77 l l l l 119 114.21 85 PCT 10 P2 VS2.72 TEC TEH.610 SBAY2 22 H 76 l l l l 133 114.21 148 PCT 10 P2 BW1 -1.05 TEC TEH.610 SBAY2 22 H 69 l l l l 169 114.41 87 PCT 14 P2 BW2.92 TEC TEH.610 SBAY2 23 H 62 l l l l 46 115.23 111 PCT 11 P2 VS3.89 TEC TEH.610 SBAY2 6 H 69 l l 46 115.28 125 PCT 12 P2 BW2 -.95 TEC TEH.610 SBAY2 6 H 69 l l 46 115.52 76 PCT 19 P2 BW2 1.02 TEC TEH.610 SBAY2 6 H 69 l l l l 96 115.31 127 PCT 13 P2 VS3.74 TEC TEH.610 SBAY2 14 H 125 l l l l 98 115.20 79 PCT 9 P2 BW1.85 TEC TEH.610 SBAY2 14 H 124 l l l l 114 115.28 94 PCT 12 P2 VS2.87 TEC TEH.610 SBAY2 14 H 116 l l l l 116 115.25 71 PCT 11 P2 VS2.76 TEC TEH.610 SBAY2 22 H 78 l l l l 126 115.48 138 PCT 17 P2 10H.70 TEC TEH.610 SBAY2 22 H 83 l l l l 130 115.38 131 PCT 15 P2 VS1.70 TEC TEH.610 SBAY2 22 H 85 l l l l 166 115.23 73 PCT 10 P2 BW2.50 TEC TEH.610 SBAY2 22 H 103 l l l l 168 115.89 86 PCT 25 P2 BW2.91 TEC TEH.610 SBAY2 22 H 104 l l 168 115 2.08 120 WAR.30 P5 BW2 1.10 VS3 TEC.610 ZYAX2 33 C 26 l l l l 170 115.28 56 PCT 10 P2 BW2.94 TEC TEH.610 SBAY2 23 H 63 l l l
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
l ROW COL VOLTS DEG IND PER CRLEN CHN LOCN INCH1 INCH2 BEGT ENDT PDIA PTYPE CAL L IDX UTIL1 UTIL2l
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
29 ST Max
SG - 31 Calls of Interest Palo Verde 3 U3R20 PVNGS3 20180401 04/20/2018 13:40:22
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
l ROW COL VOLTS DEG IND PER CRLEN CHN LOCN INCH1 INCH2 BEGT ENDT PDIA PTYPE CAL L IDX UTIL1 UTIL2l
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
l 41 116.47 80 PCT 18 P2 BW1 -1.65 TEC TEH.610 SBAY2 6 H 96 l l 41 116.37 133 PCT 15 P2 BW1 -.38 TEC TEH.610 SBAY2 6 H 96 l l 41 116 1.02 102 PCT 28 P2 BW2 -1.20 TEC TEH.610 SBAY2 6 H 96 l l 41 116 TBP P2 BW2 -1.20 TEC TEH.610 SBAY2 29 H 12 l l 41 116 2.66 95 WAR.35 P17 BW2 -.72 VS3 TEC.610 ZYAX2 32 C 42 l l l l 43 116.46 111 PCT 18 P2 BW2.50 TEC TEH.610 SBAY2 6 H 62 l l l l 47 116.47 105 PCT 18 P2 BW1 -.99 TEC TEH.610 SBAY2 6 H 70 l l 47 116.23 111 PCT 11 P2 BW2.50 TEC TEH.610 SBAY2 6 H 70 l l l l 49 116.32 104 PCT 14 P2 BW1.43 TEC TEH.610 SBAY2 6 H 56 l l l l 63 116.46 82 PCT 17 P2 VS2 -1.05 TEC TEH.610 SBAY2 4 H 120 l l l l 93 116 1.06 101 PCT 27 P2 VS4 -.76 TEC TEH.610 SBAY2 10 H 110 l l 93 116 2.19 103 WAR.45 P32 VS4 -.63 VS3 TEC.610 ZYAX2 32 C 40 l l l l 113 116.33 68 PCT 11 P2 VS1 -.89 TEC TEH.610 SBAY2 13 H 106 l l l l 117 116.29 138 PCT 10 P2 VS2 -1.12 TEC TEH.610 SBAY2 23 H 80 l l l l 165 116.22 71 PCT 10 P2 BW2 1.02 TEC TEH.610 SBAY2 24 H 20 l l l l 42 117.35 121 PCT 15 P2 VS3.68 TEC TEH.610 SBAY2 6 H 95 l l 42 117.24 141 PCT 11 P2 08C -.25 TEC TEH.610 SBAY2 6 H 95 l l l l 44 117.52 112 PCT 19 P2 BW1 -1.08 TEC TEH.610 SBAY2 6 H 63 l l l l 102 117.26 120 PCT 10 P2 VS2.63 TEC TEH.610 SBAY2 13 H 112 l l l l 106 117.26 77 PCT 10 P2 BW1 -1.43 TEC TEH.610 SBAY2 13 H 110 l l l l 114 117.75 114 PCT 20 P2 VS3 -.78 TEC TEH.610 SBAY2 23 H 82 l l 114 117 1.87 294 WAR.48 P31 VS3 -.64 VS3 TEH.610 ZYAX2 37 H 27 l l l l 120 117.37 117 PCT 13 P2 VS1.90 TEC TEH.610 SBAY2 25 H 5 l l l l 124 117.41 114 PCT 14 P2 VS1.81 TEC TEH.610 SBAY2 25 H 6 l l 124 117.85 125 PCT 22 P2 VS3 -.85 TEC TEH.610 SBAY2 25 H 6 l l 124 117.64 270 WAR.46 P36 VS1.75 VS3 TEH.610 ZYAX2 37 H 24 l l 124 117 2.05 110 WAR.49 P30 VS3 -1.09 VS3 TEH.610 ZYAX2 37 H 24 l l l l 128 117.26 123 PCT 10 P2 VS1.89 TEC TEH.610 SBAY2 25 H 8 l
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
l ROW COL VOLTS DEG IND PER CRLEN CHN LOCN INCH1 INCH2 BEGT ENDT PDIA PTYPE CAL L IDX UTIL1 UTIL2l
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
30 ST Max
SG - 31 Calls of Interest Palo Verde 3 U3R20 PVNGS3 20180401 04/20/2018 13:40:22
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
l ROW COL VOLTS DEG IND PER CRLEN CHN LOCN INCH1 INCH2 BEGT ENDT PDIA PTYPE CAL L IDX UTIL1 UTIL2l
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
l l l 166 117.71 99 PCT 22 P2 BW2 1.28 TEC TEH.610 SBAY2 24 H 24 l l 166 117 1.70 132 WAR.34 P6 BW2.90 VS3 TEC.610 ZYAX2 33 C 27 l l l l 168 117.28 61 PCT 12 P2 BW2 -.62 TEC TEH.610 SBAY2 24 H 23 l l l l 39 118.60 126 PCT 18 P2 VS3.69 TEC TEH.610 SBAY2 5 H 71 l l l l 41 118.26 112 PCT 10 P2 08H.92 TEC TEH.610 SBAY2 5 H 53 l l 41 118.49 78 PCT 16 P2 BW1 -.92 TEC TEH.610 SBAY2 5 H 53 l l l l 43 118.40 104 PCT 16 P2 BW2 -1.33 TEC TEH.610 SBAY2 6 H 94 l l 43 118.23 79 PCT 11 P2 BW2.39 TEC TEH.610 SBAY2 6 H 94 l l l l 45 118.26 133 PCT 12 P2 08C -1.00 TEC TEH.610 SBAY2 6 H 64 l l l l 53 118.31 117 PCT 11 P2 VS3.84 TEC TEH.610 SBAY2 5 H 30 l l l l 59 118.28 111 PCT 13 P2 BW2.75 TEC TEH.610 SBAY2 6 H 14 l l l l 101 118.23 43 PCT 11 P2 BW1.58 TEC TEH.610 SBAY2 14 H 130 l l l l 107 118.28 103 PCT 10 P2 VS3 -1.00 TEC TEH.610 SBAY2 15 H 178 l l l l 111 118.27 79 PCT 10 P2 VS4 -.84 TEC TEH.610 SBAY2 17 H 17 l l l l 167 118 1.22 108 PCT 30 P2 BW2.96 TEC TEH.610 SBAY2 24 H 25 l l 167 118 TBP P2 BW2.96 TEC TEH.610 SBAY2 29 H 50 l l 167 118 2.73 101 WAR.39 P5 BW2.96 VS3 TEC.610 ZYAX2 33 C 30 l l l l 169 118.35 117 PCT 12 P2 05H.78 TEC TEH.610 SBAY2 25 H 26 l l l l 38 119.54 123 PCT 16 P2 VS3.65 TEC TEH.610 SBAY2 5 H 141 l l l l 40 119.38 131 PCT 13 P2 08C -.10 TEC TEH.610 SBAY2 5 H 70 l l l l 42 119.76 115 PCT 21 P2 BW1 -1.06 TEC TEH.610 SBAY2 5 H 54 l l 42 119.37 129 WAR.24 P33 BW1 -1.10 VS3 TEH.610 ZYAX2 37 H 93 l l l l 44 119.21 137 PCT 10 P2 08H.80 TEC TEH.610 SBAY2 6 H 93 l l 44 119.50 85 PCT 18 P2 BW1 -.99 TEC TEH.610 SBAY2 6 H 93 l l 44 119.22 85 PCT 10 P2 VS3 -.95 TEC TEH.610 SBAY2 6 H 93 l l l l 46 119.84 101 PCT 25 P2 BW1 -1.11 TEC TEH.610 SBAY2 6 H 65 l
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
l ROW COL VOLTS DEG IND PER CRLEN CHN LOCN INCH1 INCH2 BEGT ENDT PDIA PTYPE CAL L IDX UTIL1 UTIL2l
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
31 ST Max
SG - 31 Calls of Interest Palo Verde 3 U3R20 PVNGS3 20180401 04/20/2018 13:40:22
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
l ROW COL VOLTS DEG IND PER CRLEN CHN LOCN INCH1 INCH2 BEGT ENDT PDIA PTYPE CAL L IDX UTIL1 UTIL2l
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
l 46 119 TBP P2 BW1 -1.11 TEC TEH.610 SBAY2 29 H 22 l l 46 119 1.51 270 WAR.60 P1 BW1 -1.06 VS3 TEH.610 ZYAX2 37 H 95 l l l l 50 119.32 72 PCT 14 P2 BW2.78 TEC TEH.610 SBAY2 6 H 73 l l l l 60 119.24 106 PCT 11 P2 BW1 1.01 TEC TEH.610 SBAY2 6 H 13 l l l l 90 119.45 100 PCT 17 P2 10H -1.54 TEC TEH.610 SBAY2 10 H 107 l l l l 124 119.18 33 PCT 8 P2 VS1.71 TEC TEH.610 SBAY2 26 H 8 l l l l 166 119.23 52 PCT 10 P2 BW2 1.02 TEC TEH.610 SBAY2 26 H 29 l l l l 168 119.30 79 PCT 11 P2 BW2.50 TEC TEH.610 SBAY2 25 H 27 l l l l 37 120.45 126 PCT 15 P2 VS3.36 TEC TEH.610 SBAY2 5 H 140 l l l l 39 120.37 123 PCT 13 P2 BW1 -1.56 TEC TEH.610 SBAY2 5 H 137 l l l l 41 120 1.21 114 PCT 27 P2 BW2 -1.26 TEC TEH.610 SBAY2 5 H 69 l l 41 120 TBP P2 BW2 -1.26 TEC TEH.610 SBAY2 29 H 7 l l 41 120 2.36 130 WAR.32 P17 BW2 -.78 VS3 TEC.610 ZYAX2 32 C 46 l l l l 43 120 1.08 114 PCT 25 P2 BW1 -1.00 TEC TEH.610 SBAY2 5 H 55 l l 43 120 1.23 110 PCT 27 P2 BW2 -.82 TEC TEH.610 SBAY2 5 H 55 l l 43 120 TBP P2 BW1 -1.00 TEC TEH.610 SBAY2 29 H 10 l l 43 120 3.05 129 WAR.30 P17 BW2 -.58 VS3 TEC.610 ZYAX2 32 C 45 l l 43 120 2.73 115 WAR.33 P1 BW1 -.96 VS3 TEH.610 ZYAX2 37 H 94 l l l l 45 120.47 84 PCT 18 P2 BW2.53 TEC TEH.610 SBAY2 6 H 92 l l l l 89 120.35 113 PCT 14 P2 VS2 -.99 TEC TEH.610 SBAY2 10 H 82 l l l l 91 120.21 110 PCT 10 P2 BW1 -.80 TEC TEH.610 SBAY2 10 H 81 l l l l 36 121 1.26 115 PCT 28 P2 BW1.99 TEC TEH.610 SBAY2 5 H 139 l l 36 121 TBP P2 BW1.99 TEC TEH.610 SBAY2 29 H 11 l l 36 121 2.67 114 WAR.68 P16 BW1.82 VS3 TEH.610 ZYAX2 37 H 96 l l l l 40 121.18 148 PCT 10 P2 05H.87 TEC TEH.610 SBAY2 6 H 192 l l l l 62 121.21 90 PCT 10 P2 VS3 -.89 TEC TEH.610 SBAY2 6 H 11 l l l l 64 121.26 140 PCT 12 P2 09H.57 TEC TEH.610 SBAY2 8 H 223 l
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
l ROW COL VOLTS DEG IND PER CRLEN CHN LOCN INCH1 INCH2 BEGT ENDT PDIA PTYPE CAL L IDX UTIL1 UTIL2l
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
32 ST Max
SG - 31 Calls of Interest Palo Verde 3 U3R20 PVNGS3 20180401 04/20/2018 13:40:22
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
l ROW COL VOLTS DEG IND PER CRLEN CHN LOCN INCH1 INCH2 BEGT ENDT PDIA PTYPE CAL L IDX UTIL1 UTIL2l
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
l l l 74 121.30 103 PCT 10 P2 VS2.71 TEC TEH.610 SBAY2 9 H 70 l l l l 112 121.26 119 PCT 11 P2 10H.74 TEC TEH.610 SBAY2 18 H 14 l l l l 164 121.47 93 PCT 15 P2 BW2.92 TEC TEH.610 SBAY2 25 H 78 l l l l 166 121 1.01 117 PCT 26 P2 BW2.88 TEC TEH.610 SBAY2 26 H 31 l l 166 121 2.30 105 WAR.29 P5 BW2.76 VS3 TEC.610 ZYAX2 33 C 29 l l l l 168 121.18 119 PCT 7 P2 10H.66 TEC TEH.610 SBAY2 25 H 79 l l 168 121.29 100 PCT 10 P2 BW2.95 TEC TEH.610 SBAY2 25 H 79 l l l l 39 122.58 129 PCT 17 P2 08H.79 TEC TEH.610 SBAY2 7 H 194 l l 39 122.50 127 PCT 15 P2 BW1 -1.00 TEC TEH.610 SBAY2 7 H 194 l l 39 122.83 122 PCT 22 P2 BW2 -.82 TEC TEH.610 SBAY2 7 H 194 l l 39 122 2.08 139 WAR.20 P17 BW2 -.86 VS3 TEC.610 ZYAX2 32 C 47 l l l l 41 122.83 117 PCT 22 P2 BW1 -.98 TEC TEH.610 SBAY2 7 H 193 l l 41 122.81 100 PCT 21 P2 BW2 -.80 TEC TEH.610 SBAY2 7 H 193 l l 41 122 2.08 99 WAR.47 P17 BW2 -.69 VS3 TEC.610 ZYAX2 32 C 44 l l 41 122 1.77 115 WAR.46 P1 BW1 -.93 VS3 TEH.610 ZYAX2 37 H 92 l l l l 47 122.56 112 PCT 20 P2 BW2 1.11 TEC TEH.610 SBAY2 6 H 90 l l 47 122 1.92 141 WAR.29 P4 BW2.90 VS3 TEC.610 ZYAX2 32 C 43 l l l l 59 122.27 124 PCT 10 P2 BW1 -1.01 TEC TEH.610 SBAY2 5 H 10 l l l l 71 122 1.20 125 PCT 27 P2 VS2 -.75 TEC TEH.610 SBAY2 9 H 65 l l 71 122 3.07 313 WAR.56 P6 VS2 -.84 VS3 TEH.610 ZYAX2 37 H 87 l l l l 91 122.19 74 PCT 7 P2 10H -1.59 TEC TEH.610 SBAY2 9 H 55 l l l l 111 122.21 51 PCT 10 P2 BW2 -.93 TEC TEH.610 SBAY2 18 H 18 l l l l 167 122.31 92 PCT 12 P2 BW2.91 TEC TEH.610 SBAY2 26 H 32 l l l l 32 123.38 102 PCT 13 P2 BW1 -1.08 TEC TEH.610 SBAY2 7 H 183 l l 32 123.29 142 PCT 10 P2 BW1 1.06 TEC TEH.610 SBAY2 7 H 183 l l l l 34 123.29 93 PCT 10 P2 BW1 -1.09 TEC TEH.610 SBAY2 7 H 184 l l l l 62 123.38 131 PCT 15 P2 BW1.55 TEC TEH.610 SBAY2 6 H 41 l l l
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
l ROW COL VOLTS DEG IND PER CRLEN CHN LOCN INCH1 INCH2 BEGT ENDT PDIA PTYPE CAL L IDX UTIL1 UTIL2l
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
33 ST Max
SG - 31 Calls of Interest Palo Verde 3 U3R20 PVNGS3 20180401 04/20/2018 13:40:22
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
l ROW COL VOLTS DEG IND PER CRLEN CHN LOCN INCH1 INCH2 BEGT ENDT PDIA PTYPE CAL L IDX UTIL1 UTIL2l
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
l 126 123.37 121 PCT 14 P2 VS2.88 TEC TEH.610 SBAY2 26 H 66 l l 126 123.59 120 PCT 19 P2 VS3 -1.01 TEC TEH.610 SBAY2 26 H 66 l l 126 123 1.25 118 PCT 29 P2 VS3 -.70 TEC TEH.610 SBAY2 26 H 66 l l 126 123.34 119 PCT 13 P2 VS3.70 TEC TEH.610 SBAY2 26 H 66 l l 126 123 1.88 265 WAR.74 P22 VS3 -.72 VS3 TEH.610 ZYAX2 37 H 25 l l l l 132 123.23 100 PCT 10 P2 VS1.79 TEC TEH.610 SBAY2 26 H 69 l l l l 162 123.39 92 PCT 15 P2 BW2 -1.43 TEC TEH.610 SBAY2 26 H 84 l l l l 166 123.61 131 PCT 20 P2 BW2.85 TEC TEH.610 SBAY2 26 H 86 l l 166 123 1.76 110 WAR.26 P5 BW2.90 VS3 TEC.610 ZYAX2 33 C 31 l l l l 168 123.36 130 PCT 12 P2 BW2.91 TEC TEH.610 SBAY2 25 H 80 l l l l 31 124.53 131 PCT 16 P2 VS3.74 TEC TEH.610 SBAY2 7 H 182 l l 31 124 1.07 109 PCT 25 P2 BW2 -.84 TEC TEH.610 SBAY2 7 H 182 l l 31 124 TBP P2 BW2 -.84 TEC TEH.610 SBAY2 29 H 5 l l 31 124 2.89 132 WAR.28 P17 BW2 -.77 VS3 TEC.610 ZYAX2 32 C 48 l l l l 33 124.36 127 PCT 12 P2 BW2 -.82 TEC TEH.610 SBAY2 7 H 181 l l l l 35 124.37 93 PCT 12 P2 BW1 -1.01 TEC TEH.610 SBAY2 7 H 180 l l 35 124.32 136 PCT 11 P2 BW2 -.80 TEC TEH.610 SBAY2 7 H 180 l l l l 39 124.32 143 PCT 11 P2 BW1 -1.01 TEC TEH.610 SBAY2 7 H 178 l l 39 124.34 138 PCT 12 P2 BW2 -.77 TEC TEH.610 SBAY2 7 H 178 l l l l 41 124.54 83 PCT 16 P2 BW1 -1.01 TEC TEH.610 SBAY2 7 H 177 l l 41 124.29 117 PCT 10 P2 BW2 -.85 TEC TEH.610 SBAY2 7 H 177 l l 41 124.38 106 PCT 13 P2 BW2 1.05 TEC TEH.610 SBAY2 7 H 177 l l l l 57 124.21 116 PCT 10 P2 VS3.95 TEC TEH.610 SBAY2 6 H 48 l l l l 87 124.35 133 PCT 14 P2 09H.97 TEC TEH.610 SBAY2 10 H 50 l l l l 99 124.21 144 PCT 10 P2 09H.87 TEC TEH.610 SBAY2 18 H 28 l l 99 124.24 86 PCT 11 P2 VS3 -1.02 TEC TEH.610 SBAY2 18 H 28 l l l l 133 124.26 84 PCT 11 P2 VS2 -.86 TEC TEH.610 SBAY2 26 H 104 l l 133 124.69 113 PCT 21 P2 VS3 -.92 TEC TEH.610 SBAY2 26 H 104 l l 133 124 1.85 295 WAR.46 P30 VS3 -.81 VS3 TEH.610 ZYAX2 37 H 26 l l l l 163 124.72 103 PCT 22 P2 BW2.99 TEC TEH.610 SBAY2 26 H 87 l
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
l ROW COL VOLTS DEG IND PER CRLEN CHN LOCN INCH1 INCH2 BEGT ENDT PDIA PTYPE CAL L IDX UTIL1 UTIL2l
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
34 ST Max
SG - 31 Calls of Interest Palo Verde 3 U3R20 PVNGS3 20180401 04/20/2018 13:40:22
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
l ROW COL VOLTS DEG IND PER CRLEN CHN LOCN INCH1 INCH2 BEGT ENDT PDIA PTYPE CAL L IDX UTIL1 UTIL2l
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
l 163 124 2.09 104 WAR.79 P5 BW2.84 VS3 TEC.610 ZYAX2 33 C 28 l l l l 165 124.32 110 PCT 11 P2 BW2.94 TEC TEH.610 SBAY2 25 H 84 l l l l 167 124.30 71 PCT 11 P2 BW2.93 TEC TEH.610 SBAY2 25 H 81 l l l l 124 125.52 78 PCT 18 P2 VS1.82 TEC TEH.610 SBAY2 26 H 118 l l l l 128 125.31 107 PCT 12 P2 VS2.74 TEC TEH.610 SBAY2 26 H 120 l l l l 162 125.28 81 PCT 11 P2 VS4.79 TEC TEH.610 SBAY2 26 H 88 l l l l 164 125.30 65 PCT 12 P2 BW2.89 TEC TEH.610 SBAY2 26 H 137 l l l l 166 125.82 118 PCT 22 P2 BW2.97 TEC TEH.610 SBAY2 25 H 82 l l 166 125 1.63 127 WAR.15 P5 BW2.92 VS3 TEC.610 ZYAX2 33 C 32 l l l l 27 126.44 116 PCT 17 P2 08H.75 TEC TEH.610 SBAY2 8 H 206 l l l l 31 126.23 121 PCT 11 P2 VS3.70 TEC TEH.610 SBAY2 8 H 204 l l l l 39 126.29 110 PCT 13 P2 BW1 -1.04 TEC TEH.610 SBAY2 8 H 200 l l 39 126.26 56 PCT 12 P2 BW2.51 TEC TEH.610 SBAY2 8 H 200 l l l l 43 126.35 63 PCT 14 P2 BW2 1.10 TEC TEH.610 SBAY2 8 H 198 l l l l 57 126.21 92 PCT 10 P2 BW1 -.94 TEC TEH.610 SBAY2 8 H 193 l l l l 63 126.26 108 PCT 10 P2 VS3.93 TEC TEH.610 SBAY2 5 H 6 l l l l 65 126.38 66 PCT 15 P2 VS2 -.96 TEC TEH.610 SBAY2 8 H 191 l l 65 126.28 94 PCT 12 P2 BW2 1.01 TEC TEH.610 SBAY2 8 H 191 l l l l 69 126.23 108 PCT 11 P2 VS3 -.74 TEC TEH.610 SBAY2 8 H 190 l l l l 73 126.29 113 PCT 10 P2 BW1.86 TEC TEH.610 SBAY2 9 H 42 l l l l 75 126.38 99 PCT 13 P2 BW1 -1.05 TEC TEH.610 SBAY2 9 H 41 l l l l 133 126.28 91 PCT 10 P2 VS1.87 TEC TEH.610 SBAY2 25 H 99 l l l l 36 127.29 114 PCT 10 P2 BW2 -.78 TEC TEH.610 SBAY2 7 H 166 l l l l 46 127.32 141 PCT 11 P2 BW2 -.75 TEC TEH.610 SBAY2 7 H 171 l
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
l ROW COL VOLTS DEG IND PER CRLEN CHN LOCN INCH1 INCH2 BEGT ENDT PDIA PTYPE CAL L IDX UTIL1 UTIL2l
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
35 ST Max
SG - 31 Calls of Interest Palo Verde 3 U3R20 PVNGS3 20180401 04/20/2018 13:40:22
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
l ROW COL VOLTS DEG IND PER CRLEN CHN LOCN INCH1 INCH2 BEGT ENDT PDIA PTYPE CAL L IDX UTIL1 UTIL2l
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
l l l 54 127.24 109 PCT 11 P2 09H.40 TEC TEH.610 SBAY2 6 H 99 l l l l 56 127.28 74 PCT 10 P2 BW1 -1.95 TEC TEH.610 SBAY2 5 H 39 l l l l 90 127.41 79 PCT 13 P2 10C -1.28 TEC TEH.610 SBAY2 9 H 32 l l l l 106 127.27 87 PCT 10 P2 09H.68 TEC TEH.610 SBAY2 17 H 54 l l l l 126 127.36 145 PCT 12 P2 VS1.45 TEC TEH.610 SBAY2 25 H 115 l l 126 127.27 133 PCT 10 P2 VS3 -.75 TEC TEH.610 SBAY2 25 H 115 l l 126 127.37 95 PCT 13 P2 VS4 -.90 TEC TEH.610 SBAY2 25 H 115 l l l l 130 127.37 122 PCT 13 P2 VS1.69 TEC TEH.610 SBAY2 25 H 117 l l l l 132 127.28 132 PCT 10 P2 VS1.74 TEC TEH.610 SBAY2 25 H 118 l l l l 41 128.40 123 PCT 13 P2 BW2 -.95 TEC TEH.610 SBAY2 7 H 142 l l l l 59 128.35 112 PCT 12 P2 BW2 -.97 TEC TEH.610 SBAY2 7 H 136 l l l l 69 128.30 72 PCT 12 P2 VS3 -.88 TEC TEH.610 SBAY2 10 H 6 l l l l 127 128.37 73 PCT 14 P2 BW2.91 TEC TEH.610 SBAY2 26 H 144 l l l l 58 129.20 93 PCT 10 P2 BW1.83 TEC TEH.610 SBAY2 8 H 182 l l l l 82 129.26 84 PCT 10 P2 BW1 -.84 TEC TEH.610 SBAY2 9 H 22 l l l l 94 129.27 98 PCT 12 P2 VS2.61 TEC TEH.610 SBAY2 18 H 58 l l l l 126 129.41 122 PCT 15 P2 VS3 -.90 TEC TEH.610 SBAY2 26 H 181 l l l l 128 129.41 108 PCT 15 P2 VS1.67 TEC TEH.610 SBAY2 26 H 180 l l l l 130 129.45 113 PCT 16 P2 VS1.77 TEC TEH.610 SBAY2 26 H 179 l l l l 162 129.38 84 PCT 14 P2 BW2.47 TEC TEH.610 SBAY2 26 H 163 l l l l 9 130.15 118 PCT 9 P2 06H.08 TEH TEC.610 SBAY2 25 C 184 l l l l 49 130.22 116 PCT 10 P2 BW1.35 TEC TEH.610 SBAY2 8 H 133 l l l l 59 130.22 106 PCT 10 P2 BW2 1.04 TEC TEH.610 SBAY2 8 H 129 l
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
l ROW COL VOLTS DEG IND PER CRLEN CHN LOCN INCH1 INCH2 BEGT ENDT PDIA PTYPE CAL L IDX UTIL1 UTIL2l
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
36 ST Max
SG - 31 Calls of Interest Palo Verde 3 U3R20 PVNGS3 20180401 04/20/2018 13:40:22
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
l ROW COL VOLTS DEG IND PER CRLEN CHN LOCN INCH1 INCH2 BEGT ENDT PDIA PTYPE CAL L IDX UTIL1 UTIL2l
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
l l l 63 130.22 116 PCT 10 P2 BW2 1.02 TEC TEH.610 SBAY2 8 H 125 l l l l 65 130.23 61 PCT 11 P2 BW2 1.19 TEC TEH.610 SBAY2 8 H 124 l l l l 101 130.27 92 PCT 10 P2 BW1.57 TEC TEH.610 SBAY2 17 H 63 l l l l 103 130.28 42 PCT 11 P2 VS3 -.97 TEC TEH.610 SBAY2 17 H 62 l l l l 107 130.38 139 PCT 13 P2 10H.75 TEC TEH.610 SBAY2 17 H 60 l l l l 133 130.31 117 PCT 11 P2 VS1 -.78 TEC TEH.610 SBAY2 25 H 146 l l l l 161 130.33 125 PCT 12 P2 BW2.98 TEC TEH.610 SBAY2 25 H 160 l l l l 165 130.38 138 PCT 13 P2 BW2 -.97 TEC TEH.610 SBAY2 25 H 162 l l l l 4 131.15 112 PCT 9 P2 06C -1.02 TEH TEC.610 SBAY2 25 C 185 l l l l 6 131.12 83 PCT 9 P2 01C -.18 TEH TEC.610 SBAY2 25 C 186 l l l l 74 131.15 134 PCT 6 P2 08H.66 TEH TEC.610 SBAY2 219 C 99 l l l l 98 131.26 119 PCT 10 P2 VS3 -.78 TEC TEH.610 SBAY2 23 H 12 l l 98 131.49 106 PCT 16 P2 VS4.95 TEC TEH.610 SBAY2 23 H 12 l l l l 126 131.24 112 PCT 9 P2 VS4 1.16 TEC TEH.610 SBAY2 25 H 183 l l l l 156 131.44 130 PCT 14 P2 BW2 -.87 TEC TEH.610 SBAY2 25 H 168 l l l l 162 131 1.46 122 PCT 30 P2 BW2.86 TEC TEH.610 SBAY2 25 H 165 l l 162 131 TBP P2 BW2.86 TEC TEH.610 SBAY2 29 H 51 l l 162 131 1.18 79 WAR.31 P35 BW2.72 VS3 TEC.610 ZYAX2 33 C 33 l l l l 5 132.47 91 PCT 14 P2 BW2 -.81 TEH TEC.610 SBAY2 26 C 185 l l l l 7 132.38 69 PCT 12 P2 BW2 -.80 TEH TEC.610 SBAY2 26 C 184 l l l l 43 132.28 143 PCT 10 P2 08H.74 TEH TEC.610 SBAY2 217 C 120 l l l l 93 132.30 94 PCT 13 P2 10H.82 TEC TEH.610 SBAY2 18 H 79 l l l l 159 132.38 38 PCT 12 P2 BW2.90 TEH TEC.610 SBAY2 225 C 32 l l l
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
l ROW COL VOLTS DEG IND PER CRLEN CHN LOCN INCH1 INCH2 BEGT ENDT PDIA PTYPE CAL L IDX UTIL1 UTIL2l
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
37 ST Max
SG - 31 Calls of Interest Palo Verde 3 U3R20 PVNGS3 20180401 04/20/2018 13:40:22
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
l ROW COL VOLTS DEG IND PER CRLEN CHN LOCN INCH1 INCH2 BEGT ENDT PDIA PTYPE CAL L IDX UTIL1 UTIL2l
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
l 161 132.27 129 PCT 10 P2 BW2.86 TEH TEC.610 SBAY2 226 C 110 l l l l 163 132.28 79 PCT 11 P2 BW2.88 TEH TEC.610 SBAY2 226 C 109 l l l l 8 133.35 107 PCT 12 P2 BW2 1.13 TEH TEC.610 SBAY2 26 C 190 l l l l 92 133.45 133 PCT 14 P2 10H 1.31 TEH TEC.610 SBAY2 220 C 114 l l 92 133.31 83 PCT 11 P2 BW1 -1.21 TEH TEC.610 SBAY2 220 C 114 l l l l 96 133.50 144 PCT 16 P2 09H.74 TEH TEC.610 SBAY2 220 C 116 l l l l 98 133.36 98 PCT 12 P2 VS3 -.75 TEH TEC.610 SBAY2 220 C 117 l l l l 130 133.37 135 PCT 12 P2 VS1.67 TEH TEC.610 SBAY2 225 C 47 l l l l 160 133.62 100 PCT 18 P2 BW2.86 TEH TEC.610 SBAY2 226 C 111 l l l l 55 134.31 115 PCT 11 P2 VS3 -.98 TEH TEC.610 SBAY2 220 C 91 l l l l 65 134.17 148 PCT 7 P2 09H.82 TEH TEC.610 SBAY2 220 C 86 l l l l 89 134.30 129 PCT 11 P2 VS2 -.78 TEH TEC.610 SBAY2 220 C 135 l l l l 91 134.46 125 PCT 15 P2 VS3 -.80 TEH TEC.610 SBAY2 220 C 136 l l l l 97 134.30 147 PCT 11 P2 10H.74 TEH TEC.610 SBAY2 220 C 118 l l l l 111 134.34 94 PCT 12 P2 BW2 -.95 TEH TEC.610 SBAY2 226 C 12 l l l l 115 134.26 141 PCT 10 P2 VS3 -.88 TEH TEC.610 SBAY2 226 C 14 l l l l 121 134.27 142 PCT 10 P2 VS3 -.74 TEH TEC.610 SBAY2 226 C 17 l l l l 48 135.29 87 PCT 10 P2 09C -1.04 TEH TEC.610 SBAY2 217 C 154 l l l l 102 135.34 136 PCT 12 P2 10H.67 TEH TEC.610 SBAY2 226 C 63 l l l l 112 135.39 131 PCT 14 P2 VS2.83 TEH TEC.610 SBAY2 226 C 60 l l l l 122 135.25 85 PCT 10 P2 VS1.73 TEH TEC.610 SBAY2 226 C 55 l l l l 124 135.32 144 PCT 12 P2 VS1.83 TEH TEC.610 SBAY2 226 C 54 l l l l 128 135.39 116 PCT 13 P2 VS2.95 TEH TEC.610 SBAY2 226 C 52 l
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
l ROW COL VOLTS DEG IND PER CRLEN CHN LOCN INCH1 INCH2 BEGT ENDT PDIA PTYPE CAL L IDX UTIL1 UTIL2l
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
38 ST Max
SG - 31 Calls of Interest Palo Verde 3 U3R20 PVNGS3 20180401 04/20/2018 13:40:22
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
l ROW COL VOLTS DEG IND PER CRLEN CHN LOCN INCH1 INCH2 BEGT ENDT PDIA PTYPE CAL L IDX UTIL1 UTIL2l
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
l l l 144 135.31 136 PCT 12 P2 VS2.80 TEH TEC.610 SBAY2 226 C 42 l l l l 63 136.32 110 PCT 11 P2 VS3 1.03 TEH TEC.610 SBAY2 219 C 74 l l l l 69 136.55 140 PCT 16 P2 09H.67 TEH TEC.610 SBAY2 221 C 18 l l l l 38 137.34 159 PCT 12 P2 VS3.89 TEH TEC.610 SBAY2 218 C 165 l l l l 126 137.38 105 PCT 12 P2 VS3 1.20 TEH TEC.610 SBAY2 223 C 231 l l l l 158 137.30 152 PCT 11 P2 BW2 -.95 TEH TEC.610 SBAY2 226 C 104 l l l l 13 138.42 108 PCT 14 P2 BW1 -.16 TEH TEC.610 SBAY2 218 C 152 l l l l 25 138.42 87 PCT 14 P2 BW1 -1.30 TEH TEC.610 SBAY2 218 C 187 l l l l 37 138.26 101 PCT 10 P2 08H -.25 TEH TEC.610 SBAY2 218 C 181 l l l l 53 138.35 102 PCT 12 P2 BW1 -.98 TEH TEC.610 SBAY2 220 C 66 l l l l 107 138.31 138 PCT 12 P2 09H.78 TEH TEC.610 SBAY2 226 C 72 l l l l 157 138.42 92 PCT 14 P2 BW2 1.02 TEH TEC.610 SBAY2 226 C 103 l l l l 64 139.32 134 PCT 11 P2 BW1.90 TEH TEC.610 SBAY2 219 C 60 l l l l 106 139.38 139 PCT 13 P2 09H.85 TEH TEC.610 SBAY2 224 C 240 l l l l 156 139.33 45 PCT 12 P2 BW2.36 TEH TEC.610 SBAY2 226 C 102 l l l l 53 140.45 58 PCT 14 P2 BW1 -.95 TEH TEC.610 SBAY2 219 C 22 l l l l 59 140.34 105 PCT 11 P2 VS3.91 TEH TEC.610 SBAY2 219 C 25 l l l l 65 140.28 32 PCT 10 P2 VS2 -.94 TEH TEC.610 SBAY2 219 C 28 l l l l 103 140.30 152 PCT 11 P2 10H.71 TEH TEC.610 SBAY2 223 C 190 l l l l 128 141.44 131 PCT 13 P2 VS3 -.70 TEH TEC.610 SBAY2 223 C 169 l l l l 130 141.27 135 PCT 9 P2 VS1.75 TEH TEC.610 SBAY2 223 C 168 l l 130 141.37 127 PCT 12 P2 VS2.89 TEH TEC.610 SBAY2 223 C 168 l l 130 141.32 145 PCT 11 P2 VS3 -.72 TEH TEC.610 SBAY2 223 C 168 l
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
l ROW COL VOLTS DEG IND PER CRLEN CHN LOCN INCH1 INCH2 BEGT ENDT PDIA PTYPE CAL L IDX UTIL1 UTIL2l
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
39 ST Max
SG - 31 Calls of Interest Palo Verde 3 U3R20 PVNGS3 20180401 04/20/2018 13:40:22
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
l ROW COL VOLTS DEG IND PER CRLEN CHN LOCN INCH1 INCH2 BEGT ENDT PDIA PTYPE CAL L IDX UTIL1 UTIL2l
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
l l l 55 142.35 79 PCT 12 P2 BW1 1.91 TEH TEC.610 SBAY2 220 C 20 l l l l 59 142.39 78 PCT 13 P2 VS3.99 TEH TEC.610 SBAY2 220 C 22 l l l l 71 142.28 107 PCT 10 P2 VS2 -.78 TEH TEC.610 SBAY2 220 C 30 l l l l 105 142.27 138 PCT 10 P2 10H.81 TEH TEC.610 SBAY2 224 C 192 l l 105 142.40 117 PCT 13 P2 VS2.85 TEH TEC.610 SBAY2 224 C 192 l l l l 114 143.32 119 PCT 11 P2 VS2.86 TEH TEC.610 SBAY2 224 C 181 l l l l 120 143.47 105 PCT 15 P2 VS2 -.84 TEH TEC.610 SBAY2 224 C 178 l l l l 41 144.14 135 PCT 8 P2 08C.91 TEH TEC.610 SBAY2 217 C 17 l l l l 65 144.43 142 PCT 14 P2 09H.81 TEH TEC.610 SBAY2 217 C 33 l l l l 87 144.31 101 PCT 11 P2 BW1 -1.19 TEH TEC.610 SBAY2 217 C 44 l l l l 91 144.36 100 PCT 12 P2 VS3.47 TEH TEC.610 SBAY2 217 C 46 l l l l 94 145.71 121 PCT 19 P2 VS2.95 TEH TEC.610 SBAY2 218 C 50 l l 94 145.38 115 PCT 13 P2 VS4 -.75 TEH TEC.610 SBAY2 218 C 50 l l l l 104 145.35 143 PCT 11 P2 09H.82 TEH TEC.610 SBAY2 223 C 128 l l l l 114 145 1.07 107 WAR.47 P30 VS3 -.72 VS3 TEH.610 ZYAX2 37 H 45 l l 114 145.85 116 PCT 21 P2 VS3 -.70 TEH TEC.610 SBAY2 223 C 123 l l l l 126 145.33 145 PCT 12 P2 VS1.44 TEH TEC.610 SBAY2 224 C 122 l l l l 128 145.35 109 PCT 12 P2 VS1.83 TEH TEC.610 SBAY2 224 C 121 l l 128 145.28 135 PCT 10 P2 VS3 -.68 TEH TEC.610 SBAY2 224 C 121 l l l l 130 145.51 128 PCT 16 P2 VS1.70 TEH TEC.610 SBAY2 224 C 120 l l l l 132 145.56 129 PCT 17 P2 VS1.73 TEH TEC.610 SBAY2 224 C 119 l l l l 49 146.40 133 PCT 13 P2 BW1.59 TEH TEC.610 SBAY2 218 C 20 l l l l 85 146.27 105 PCT 10 P2 VS2.77 TEH TEC.610 SBAY2 218 C 38 l l l l 89 146.27 129 PCT 10 P2 VS2.82 TEH TEC.610 SBAY2 218 C 40 l
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
l ROW COL VOLTS DEG IND PER CRLEN CHN LOCN INCH1 INCH2 BEGT ENDT PDIA PTYPE CAL L IDX UTIL1 UTIL2l
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
40 ST Max
SG - 31 Calls of Interest Palo Verde 3 U3R20 PVNGS3 20180401 04/20/2018 13:40:22
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
l ROW COL VOLTS DEG IND PER CRLEN CHN LOCN INCH1 INCH2 BEGT ENDT PDIA PTYPE CAL L IDX UTIL1 UTIL2l
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
l l l 105 146.38 93 PCT 13 P2 VS2.78 TEH TEC.610 SBAY2 224 C 141 l l l l 147 146.29 127 PCT 11 P2 11H.60 TEH TEC.610 SBAY2 224 C 162 l l l l 94 147.30 130 PCT 11 P2 VS4.53 TEH TEC.610 SBAY2 214 C 185 l l l l 110 147.27 123 PCT 10 P2 VS4 -.83 TEH TEC.610 SBAY2 224 C 131 l l l l 128 147.32 136 PCT 10 P2 VS3 -.78 TEH TEC.610 SBAY2 223 C 118 l l l l 152 147.37 106 PCT 12 P2 BW1.83 TEH TEC.610 SBAY2 223 C 106 l l l l 25 148.31 64 PCT 11 P2 BW1 -.91 TEH TEC.610 SBAY2 214 C 148 l l l l 49 148.44 94 PCT 14 P2 BW1.89 TEH TEC.610 SBAY2 214 C 161 l l l l 61 148.34 108 PCT 12 P2 VS3.88 TEH TEC.610 SBAY2 214 C 168 l l l l 63 148.37 118 PCT 12 P2 VS3 1.14 TEH TEC.610 SBAY2 214 C 169 l l l l 87 148.39 88 PCT 13 P2 VS2 -.70 TEH TEC.610 SBAY2 214 C 181 l l l l 105 148 2.96 294 WAR.56 P6 VS3 -.62 VS3 TEH.610 ZYAX2 37 H 43 l l 105 148.31 63 PCT 11 P2 VS2.90 TEH TEC.610 SBAY2 224 C 86 l l 105 148 1.31 95 PCT 28 P2 VS3 -.73 TEH TEC.610 SBAY2 224 C 86 l l l l 107 148.31 109 PCT 11 P2 VS2 -.85 TEH TEC.610 SBAY2 224 C 87 l l l l 46 149.23 155 PCT 8 P2 BW1.96 TEH TEC.610 SBAY2 216 C 110 l l l l 78 149.32 134 PCT 11 P2 VS2 -.75 TEH TEC.610 SBAY2 213 C 170 l l l l 108 149.64 124 PCT 18 P2 10H.63 TEH TEC.610 SBAY2 224 C 72 l l l l 114 149 2.57 111 WAR.56 P31 VS2.90 VS3 TEH.610 ZYAX2 37 H 44 l l 114 149 1.30 111 PCT 28 P2 VS2.80 TEH TEC.610 SBAY2 224 C 69 l l l l 148 149 1.38 116 WAR.25 P13 11H.60 11H TEH.610 ZYAX2 37 H 34 l l 148 149.83 130 PCT 21 P2 11H.66 TEH TEC.610 SBAY2 216 C 92 l l l l 49 150.32 98 PCT 11 P2 BW1.36 TEH TEC.610 SBAY2 213 C 138 l l l l 51 150.29 65 PCT 10 P2 BW1 -.70 TEH TEC.610 SBAY2 213 C 140 l
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
l ROW COL VOLTS DEG IND PER CRLEN CHN LOCN INCH1 INCH2 BEGT ENDT PDIA PTYPE CAL L IDX UTIL1 UTIL2l
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
41 ST Max
SG - 31 Calls of Interest Palo Verde 3 U3R20 PVNGS3 20180401 04/20/2018 13:40:22
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
l ROW COL VOLTS DEG IND PER CRLEN CHN LOCN INCH1 INCH2 BEGT ENDT PDIA PTYPE CAL L IDX UTIL1 UTIL2l
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
l l l 53 150.30 130 PCT 10 P2 VS3 1.10 TEH TEC.610 SBAY2 213 C 141 l l l l 111 150.34 132 PCT 11 P2 10H.64 TEH TEC.610 SBAY2 223 C 88 l l l l 117 150.33 137 PCT 11 P2 BW2 -1.00 TEH TEC.610 SBAY2 223 C 91 l l l l 121 150.48 59 PCT 14 P2 BW2 -.83 TEH TEC.610 SBAY2 223 C 93 l l l l 125 150.32 70 PCT 11 P2 VS1 1.09 TEH TEC.610 SBAY2 223 C 95 l l l l 143 150.38 117 PCT 12 P2 11H.65 TEH TEC.610 SBAY2 223 C 104 l l l l 74 151.25 125 PCT 9 P2 VS2.71 TEH TEC.610 SBAY2 214 C 109 l l l l 82 151.28 67 PCT 10 P2 09H.74 TEH TEC.610 SBAY2 214 C 103 l l l l 100 151.32 123 PCT 11 P2 VS2.85 TEH TEC.610 SBAY2 223 C 72 l l l l 124 151.28 85 PCT 10 P2 BW2.90 TEH TEC.610 SBAY2 223 C 60 l l l l 128 151.30 141 PCT 10 P2 VS1.87 TEH TEC.610 SBAY2 223 C 58 l l 128 151.33 127 PCT 11 P2 VS2.61 TEH TEC.610 SBAY2 223 C 58 l l l l 65 152.43 138 PCT 14 P2 09H.75 TEH TEC.610 SBAY2 214 C 82 l l l l 67 152.29 68 PCT 10 P2 BW2 -.36 TEH TEC.610 SBAY2 214 C 83 l l l l 89 152.55 126 PCT 16 P2 VS2.80 TEH TEC.610 SBAY2 214 C 94 l l l l 105 152.35 130 PCT 12 P2 10H.72 TEH TEC.610 SBAY2 224 C 29 l l l l 149 152.35 98 PCT 11 P2 BW1 1.19 TEH TEC.610 SBAY2 215 C 102 l l l l 60 153.44 91 PCT 13 P2 VS3.95 TEH TEC.610 SBAY2 213 C 93 l l l l 82 153.34 146 PCT 12 P2 VS2.67 TEH TEC.610 SBAY2 212 C 68 l l l l 92 153.31 142 PCT 11 P2 VS2 -.80 TEH TEC.610 SBAY2 212 C 89 l l l l 106 153.31 94 PCT 11 P2 BW2 -1.39 TEH TEC.610 SBAY2 224 C 22 l l l l 128 153.31 119 PCT 11 P2 VS3 -.68 TEH TEC.610 SBAY2 224 C 12 l l l
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
l ROW COL VOLTS DEG IND PER CRLEN CHN LOCN INCH1 INCH2 BEGT ENDT PDIA PTYPE CAL L IDX UTIL1 UTIL2l
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
42 ST Max
SG - 31 Calls of Interest Palo Verde 3 U3R20 PVNGS3 20180401 04/20/2018 13:40:22
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
l ROW COL VOLTS DEG IND PER CRLEN CHN LOCN INCH1 INCH2 BEGT ENDT PDIA PTYPE CAL L IDX UTIL1 UTIL2l
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
l 132 153.32 118 PCT 11 P2 VS1.83 TEH TEC.610 SBAY2 224 C 10 l l 132 153.30 151 PCT 11 P2 VS3 -.68 TEH TEC.610 SBAY2 224 C 10 l l l l 59 154.30 122 PCT 10 P2 VS3.99 TEH TEC.610 SBAY2 213 C 65 l l l l 101 154.30 128 PCT 11 P2 BW1.98 TEH TEC.610 SBAY2 212 C 129 l l l l 107 154.41 131 PCT 13 P2 10H.27 TEH TEC.610 SBAY2 212 C 171 l l l l 121 154.53 94 PCT 15 P2 BW2 -1.00 TEH TEC.610 SBAY2 223 C 34 l l l l 127 154.32 120 PCT 11 P2 BW2.80 TEH TEC.610 SBAY2 223 C 37 l l l l 8 155.34 52 PCT 12 P2 BW1 -.74 TEH TEC.610 SBAY2 29 C 21 l l l l 118 155.37 79 PCT 12 P2 BW2.51 TEH TEC.610 SBAY2 223 C 18 l l l l 59 156.42 124 PCT 14 P2 VS3.70 TEH TEC.610 SBAY2 210 C 250 l l l l 67 156.31 138 PCT 11 P2 VS3 -.87 TEH TEC.610 SBAY2 212 C 10 l l l l 89 156.12 107 PCT 8 P2 09H -.03 TEH TEC.610 SBAY2 212 C 84 l l 89 156.26 145 PCT 10 P2 VS2.83 TEH TEC.610 SBAY2 212 C 84 l l l l 113 156.46 140 PCT 14 P2 10H.77 TEH TEC.610 SBAY2 222 C 59 l l l l 56 157.63 129 PCT 17 P2 VS3.75 TEH TEC.610 SBAY2 211 C 27 l l l l 86 157.42 133 PCT 13 P2 09H.78 TEH TEC.610 SBAY2 211 C 61 l l l l 92 157.38 126 PCT 12 P2 10H 1.51 TEH TEC.610 SBAY2 211 C 80 l l l l 96 157.28 146 PCT 10 P2 VS4 -.82 TEH TEC.610 SBAY2 212 C 123 l l l l 102 157.36 136 PCT 11 P2 10H.68 TEH TEC.610 SBAY2 211 C 125 l l l l 132 157.47 136 PCT 15 P2 VS1.80 TEH TEC.610 SBAY2 222 C 45 l l l l 140 157.31 138 PCT 10 P2 11H.51 TEH TEC.610 SBAY2 215 C 109 l l l l 49 158.34 137 PCT 11 P2 BW1.94 TEH TEC.610 SBAY2 209 C 225 l l l l 91 158.39 116 PCT 12 P2 VS2.43 TEH TEC.610 SBAY2 211 C 77 l l l
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
l ROW COL VOLTS DEG IND PER CRLEN CHN LOCN INCH1 INCH2 BEGT ENDT PDIA PTYPE CAL L IDX UTIL1 UTIL2l
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
43 ST Max
SG - 31 Calls of Interest Palo Verde 3 U3R20 PVNGS3 20180401 04/20/2018 13:40:22
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
l ROW COL VOLTS DEG IND PER CRLEN CHN LOCN INCH1 INCH2 BEGT ENDT PDIA PTYPE CAL L IDX UTIL1 UTIL2l
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
l 99 158.34 98 PCT 11 P2 VS2.78 TEH TEC.610 SBAY2 211 C 119 l l l l 103 158.37 126 PCT 13 P2 VS3.97 TEH TEC.610 SBAY2 212 C 165 l l l l 105 158.40 127 PCT 12 P2 VS2.71 TEH TEC.610 SBAY2 215 C 119 l l l l 107 158.29 127 PCT 10 P2 VS4 -.72 TEH TEC.610 SBAY2 211 C 159 l l l l 115 158.51 122 PCT 15 P2 VS3 -.70 TEH TEC.610 SBAY2 221 C 50 l l l l 117 158.38 117 PCT 12 P2 VS1 -.57 TEH TEC.610 SBAY2 221 C 51 l l l l 30 159.28 136 PCT 10 P2 VS3 -.82 TEH TEC.610 SBAY2 210 C 210 l l l l 48 159.26 131 PCT 10 P2 BW1 -.73 TEH TEC.610 SBAY2 210 C 201 l l l l 82 159.61 123 PCT 17 P2 VS2.70 TEH TEC.610 SBAY2 211 C 52 l l l l 100 159 TBP P2 VS3 -.32 TEC TEH.610 SBAY2 29 H 52 l l 100 159 2.81 78 WAR.55 P22 VS3 -.45 VS3 TEH.610 ZYAX2 37 H 39 l l 100 159 1.65 108 PCT 30 P2 VS3 -.32 TEH TEC.610 SBAY2 211 C 127 l l l l 112 159 1.75 109 WAR.40 P48 VS3 -.96 VS3 TEH.610 ZYAX2 37 H 38 l l 112 159 1.39 109 PCT 28 P2 VS3 -.81 TEH TEC.610 SBAY2 216 C 78 l l l l 118 159.39 140 PCT 12 P2 VS3 -.99 TEH TEC.610 SBAY2 216 C 80 l l l l 124 159.34 134 PCT 11 P2 VS2.93 TEH TEC.610 SBAY2 216 C 83 l l 124 159.54 103 PCT 16 P2 VS3 -.96 TEH TEC.610 SBAY2 216 C 83 l l l l 126 159.45 113 PCT 14 P2 VS1.45 TEH TEC.610 SBAY2 216 C 84 l l l l 128 159.22 80 PCT 8 P2 VS1.83 TEH TEC.610 SBAY2 216 C 85 l l l l 132 159.41 125 PCT 13 P2 VS1.69 TEH TEC.610 SBAY2 214 C 46 l l l l 57 160.29 133 PCT 10 P2 VS3 -.90 TEH TEC.610 SBAY2 210 C 170 l l l l 77 160.40 123 PCT 13 P2 VS2 -.84 TEH TEC.610 SBAY2 210 C 180 l l l l 91 160.39 84 PCT 12 P2 BW1 -.75 TEH TEC.610 SBAY2 211 C 92 l l l l 95 160.32 135 PCT 11 P2 10H.65 TEH TEC.610 SBAY2 212 C 135 l l l
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
l ROW COL VOLTS DEG IND PER CRLEN CHN LOCN INCH1 INCH2 BEGT ENDT PDIA PTYPE CAL L IDX UTIL1 UTIL2l
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
44 ST Max
SG - 31 Calls of Interest Palo Verde 3 U3R20 PVNGS3 20180401 04/20/2018 13:40:22
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
l ROW COL VOLTS DEG IND PER CRLEN CHN LOCN INCH1 INCH2 BEGT ENDT PDIA PTYPE CAL L IDX UTIL1 UTIL2l
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
l 99 160 2.04 297 WAR.42 P6 VS3 -1.17 VS3 TEH.610 ZYAX2 37 H 40 l l 99 160 1.00 98 PCT 23 P2 VS3 -1.27 TEH TEC.610 SBAY2 211 C 128 l l l l 101 160 1.17 98 WAR.22 P48 VS3 -1.08 VS3 TEH.610 ZYAX2 37 H 41 l l 101 160.99 110 PCT 24 P2 VS3 -.96 TEH TEC.610 SBAY2 212 C 163 l l l l 103 160.34 120 PCT 11 P2 BW2.35 TEH TEC.610 SBAY2 216 C 74 l l l l 80 161.29 121 PCT 10 P2 VS2 -.86 TEH TEC.610 SBAY2 212 C 75 l l l l 98 161.35 144 PCT 11 P2 10H.83 TEH TEC.610 SBAY2 211 C 129 l l l l 100 161.59 138 PCT 17 P2 09H.56 TEH TEC.610 SBAY2 212 C 162 l l l l 124 161.61 123 PCT 17 P2 VS3 -.54 TEH TEC.610 SBAY2 215 C 91 l l l l 128 161.67 137 PCT 18 P2 VS1.89 TEH TEC.610 SBAY2 215 C 93 l l l l 35 162.51 139 PCT 15 P2 08H.86 TEH TEC.610 SBAY2 209 C 149 l l l l 57 162.37 115 PCT 11 P2 BW1 1.78 TEH TEC.610 SBAY2 209 C 159 l l l l 79 162.32 142 PCT 10 P2 09H.90 TEH TEC.610 SBAY2 209 C 169 l l l l 87 162.49 102 PCT 14 P2 VS4.88 TEH TEC.610 SBAY2 211 C 73 l l l l 91 162.28 145 PCT 10 P2 BW1.44 TEH TEC.610 SBAY2 212 C 118 l l l l 93 162.21 150 PCT 8 P2 09H.65 TEH TEC.610 SBAY2 212 C 137 l l l l 95 162.37 133 PCT 12 P2 09H.69 TEH TEC.610 SBAY2 211 C 115 l l l l 103 162.39 131 PCT 12 P2 10H.61 TEH TEC.610 SBAY2 211 C 155 l l l l 125 162.33 114 PCT 11 P2 VS2 -.68 TEH TEC.610 SBAY2 215 C 64 l l 125 162.39 115 PCT 12 P2 VS3 -.86 TEH TEC.610 SBAY2 215 C 64 l l l l 135 162.31 81 PCT 10 P2 BW1.87 TEH TEC.610 SBAY2 213 C 36 l l l l 92 163.27 115 PCT 10 P2 BW1 -1.29 TEH TEC.610 SBAY2 212 C 138 l l 92 163.29 140 PCT 11 P2 VS2.75 TEH TEC.610 SBAY2 212 C 138 l l l l 94 163.40 127 PCT 12 P2 VS2.76 TEH TEC.610 SBAY2 211 C 114 l l l
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
l ROW COL VOLTS DEG IND PER CRLEN CHN LOCN INCH1 INCH2 BEGT ENDT PDIA PTYPE CAL L IDX UTIL1 UTIL2l
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
45 ST Max
SG - 31 Calls of Interest Palo Verde 3 U3R20 PVNGS3 20180401 04/20/2018 13:40:22
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
l ROW COL VOLTS DEG IND PER CRLEN CHN LOCN INCH1 INCH2 BEGT ENDT PDIA PTYPE CAL L IDX UTIL1 UTIL2l
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
l 96 163.45 111 PCT 13 P2 VS2.84 TEH TEC.610 SBAY2 211 C 131 l l 96 163.65 125 PCT 17 P2 VS4 -.68 TEH TEC.610 SBAY2 211 C 131 l l l l 126 163.35 119 PCT 11 P2 BW1.83 TEH TEC.610 SBAY2 216 C 46 l l l l 132 163.63 124 PCT 18 P2 VS1 -.72 TEH TEC.610 SBAY2 214 C 33 l l 132 163.44 115 PCT 14 P2 VS4 -.72 TEH TEC.610 SBAY2 214 C 33 l l l l 134 163.37 143 PCT 12 P2 BW1.55 TEH TEC.610 SBAY2 213 C 35 l l l l 47 164.30 99 PCT 11 P2 BW1.78 TEH TEC.610 SBAY2 210 C 89 l l l l 91 164.29 108 PCT 10 P2 BW1 -.88 TEH TEC.610 SBAY2 212 C 139 l l 91 164.27 141 PCT 10 P2 BW1.71 TEH TEC.610 SBAY2 212 C 139 l l l l 99 164.47 114 PCT 14 P2 VS3 -1.03 TEH TEC.610 SBAY2 216 C 33 l l l l 109 164.44 128 PCT 14 P2 BW1 -1.89 TEH TEC.610 SBAY2 216 C 37 l l l l 113 164.45 75 PCT 14 P2 VS1 -.64 TEH TEC.610 SBAY2 216 C 39 l l l l 117 164.32 90 PCT 11 P2 VS3 -.95 TEH TEC.610 SBAY2 216 C 41 l l l l 123 164.36 118 PCT 12 P2 VS3 -.98 TEH TEC.610 SBAY2 216 C 44 l l l l 125 164.36 120 PCT 12 P2 BW1 1.09 TEH TEC.610 SBAY2 216 C 45 l l l l 56 165.29 145 PCT 10 P2 BW1 -1.76 TEH TEC.610 SBAY2 209 C 113 l l l l 70 165.26 148 PCT 9 P2 VS2.44 TEH TEC.610 SBAY2 209 C 106 l l l l 102 165.29 130 PCT 10 P2 BW1 -1.13 TEH TEC.610 SBAY2 215 C 62 l l l l 104 165.36 120 PCT 11 P2 VS3 -.93 TEH TEC.610 SBAY2 215 C 61 l l l l 130 165.25 122 PCT 9 P2 BW1 -.15 TEH TEC.610 SBAY2 213 C 26 l l l l 45 166.32 108 PCT 10 P2 08C -1.16 TEH TEC.610 SBAY2 209 C 84 l l l l 49 166.47 122 PCT 14 P2 BW1 1.12 TEH TEC.610 SBAY2 209 C 86 l l l l 71 166.27 133 PCT 9 P2 BW1 1.19 TEH TEC.610 SBAY2 209 C 97 l l l l 91 166.36 98 PCT 11 P2 10C -1.68 TEH TEC.610 SBAY2 211 C 111 l
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
l ROW COL VOLTS DEG IND PER CRLEN CHN LOCN INCH1 INCH2 BEGT ENDT PDIA PTYPE CAL L IDX UTIL1 UTIL2l
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
46 ST Max
SG - 31 Calls of Interest Palo Verde 3 U3R20 PVNGS3 20180401 04/20/2018 13:40:22
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
l ROW COL VOLTS DEG IND PER CRLEN CHN LOCN INCH1 INCH2 BEGT ENDT PDIA PTYPE CAL L IDX UTIL1 UTIL2l
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
l l l 97 166.37 91 PCT 12 P2 10H -.20 TEH TEC.610 SBAY2 215 C 34 l l l l 99 166.32 130 PCT 11 P2 VS3 -1.13 TEH TEC.610 SBAY2 211 C 151 l l l l 123 166.37 117 PCT 12 P2 VS3 -1.13 TEH TEC.610 SBAY2 214 C 26 l l l l 125 166.32 118 PCT 11 P2 VS2 -.65 TEH TEC.610 SBAY2 214 C 25 l l l l 44 167.31 156 PCT 11 P2 BW1.86 TEH TEC.610 SBAY2 210 C 54 l l l l 80 167.30 133 PCT 11 P2 VS2 -.77 TEH TEC.610 SBAY2 210 C 33 l l l l 110 167.35 152 PCT 11 P2 BW1.71 TEH TEC.610 SBAY2 216 C 23 l l l l 124 167.30 140 PCT 11 P2 10H.73 TEH TEC.610 SBAY2 214 C 22 l l l l 23 168.30 133 PCT 11 P2 08H -.20 TEH TEC.610 SBAY2 208 C 240 l l l l 59 168.27 101 PCT 10 P2 BW1.83 TEH TEC.610 SBAY2 210 C 19 l l l l 87 168.32 136 PCT 11 P2 VS2 -.72 TEH TEC.610 SBAY2 212 C 143 l l l l 101 168.32 114 PCT 11 P2 VS2 -.81 TEH TEC.610 SBAY2 216 C 7 l l l l 109 168.30 103 PCT 10 P2 09H.75 TEH TEC.610 SBAY2 216 C 11 l l l l 129 168.30 120 PCT 10 P2 VS1 -.80 TEH TEC.610 SBAY2 213 C 19 l l l l 56 169.32 99 PCT 10 P2 BW1 -1.70 TEH TEC.610 SBAY2 209 C 44 l l l l 62 169.38 73 PCT 12 P2 VS2 -.70 TEH TEC.610 SBAY2 209 C 41 l l l l 66 169.33 94 PCT 11 P2 VS2 -.65 TEH TEC.610 SBAY2 209 C 39 l l l l 70 169.29 141 PCT 10 P2 VS2.65 TEH TEC.610 SBAY2 209 C 37 l l l l 92 169.26 127 PCT 10 P2 VS2 -.80 TEH TEC.610 SBAY2 212 C 155 l l l l 96 169.29 136 PCT 10 P2 VS2.84 TEH TEC.610 SBAY2 211 C 148 l l l l 102 169.38 136 PCT 12 P2 VS3.71 TEH TEC.610 SBAY2 215 C 27 l l l l 106 169.33 121 PCT 10 P2 10C.67 TEH TEC.610 SBAY2 215 C 25 l
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
l ROW COL VOLTS DEG IND PER CRLEN CHN LOCN INCH1 INCH2 BEGT ENDT PDIA PTYPE CAL L IDX UTIL1 UTIL2l
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
47 ST Max
SG - 31 Calls of Interest Palo Verde 3 U3R20 PVNGS3 20180401 04/20/2018 13:40:22
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
l ROW COL VOLTS DEG IND PER CRLEN CHN LOCN INCH1 INCH2 BEGT ENDT PDIA PTYPE CAL L IDX UTIL1 UTIL2l
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
l l l 128 169 NDF P2 TSC.98 01C TEC.610 ZYAX2 31 C 45 l l 128 169.68 101 PCT 18 P2 VS3 -1.06 TEH TEC.610 SBAY2 213 C 16 l l l l 79 170.23 129 PCT 8 P2 BW1 1.09 TEH TEC.610 SBAY2 209 C 29 l l l l 97 170.29 87 PCT 10 P2 VS3 -.97 TEH TEC.610 SBAY2 215 C 6 l l l l 99 170.31 139 PCT 10 P2 VS4 1.32 TEH TEC.610 SBAY2 215 C 7 l l l l 103 170.27 95 PCT 9 P2 BW1.89 TEH TEC.610 SBAY2 215 C 9 l l l l 119 170.27 138 PCT 10 P2 09H.78 TEH TEC.610 SBAY2 214 C 19 l l l l 121 170.27 152 PCT 9 P2 10H.73 TEH TEC.610 SBAY2 214 C 18 l l l l 70 171.27 128 PCT 10 P2 VS2.61 TEH TEC.610 SBAY2 208 C 205 l l l l 90 171.34 133 PCT 12 P2 09H.71 TEH TEC.610 SBAY2 212 C 153 l l l l 94 171.35 141 PCT 11 P2 09H.89 TEH TEC.610 SBAY2 211 C 146 l l l l 114 171.42 129 PCT 14 P2 10H.56 TEH TEC.610 SBAY2 214 C 11 l l l l 122 171.35 131 PCT 12 P2 05C.84 TEH TEC.610 SBAY2 214 C 15 l l l l 15 172.37 131 PCT 12 P2 08H -.28 TEH TEC.610 SBAY2 208 C 165 l l l l 31 172.27 128 PCT 10 P2 VS3 -.85 TEH TEC.610 SBAY2 208 C 173 l l l l 89 172.35 140 PCT 12 P2 VS2 -.75 TEH TEC.610 SBAY2 212 C 152 l l 89 172.28 121 PCT 10 P2 VS4.95 TEH TEC.610 SBAY2 212 C 152 l l l l 93 172.32 133 PCT 10 P2 10H.64 TEH TEC.610 SBAY2 211 C 145 l l l l 105 172.31 86 PCT 11 P2 VS3 -.88 TEH TEC.610 SBAY2 212 C 183 l l l l 111 172.27 89 PCT 10 P2 BW1 -.90 TEH TEC.610 SBAY2 212 C 180 l l l l 113 172.30 156 PCT 11 P2 BW1.61 TEH TEC.610 SBAY2 212 C 179 l l l l 56 173.43 105 PCT 13 P2 BW1 -1.61 TEH TEC.610 SBAY2 207 C 221 l l 56 173.21 123 PCT 7 P2 VS3 -.88 TEH TEC.610 SBAY2 207 C 221 l l l
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
l ROW COL VOLTS DEG IND PER CRLEN CHN LOCN INCH1 INCH2 BEGT ENDT PDIA PTYPE CAL L IDX UTIL1 UTIL2l
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
48 ST Max
SG - 31 Calls of Interest Palo Verde 3 U3R20 PVNGS3 20180401 04/20/2018 13:40:22
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
l ROW COL VOLTS DEG IND PER CRLEN CHN LOCN INCH1 INCH2 BEGT ENDT PDIA PTYPE CAL L IDX UTIL1 UTIL2l
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
l 92 173.30 118 PCT 10 P2 VS3 1.01 TEH TEC.610 SBAY2 211 C 144 l l l l 96 173 1.29 307 WAR.24 P7 VS3.46 VS3 TEH.610 ZYAX2 37 H 42 l l 96 173.82 118 PCT 20 P2 VS3.70 TEH TEC.610 SBAY2 211 C 186 l l l l 98 173.48 122 PCT 14 P2 VS4 -.55 TEH TEC.610 SBAY2 211 C 187 l l l l 108 173.50 133 PCT 15 P2 10H.65 TEH TEC.610 SBAY2 213 C 7 l l l l 114 173.29 62 PCT 11 P2 VS1.74 TEH TEC.610 SBAY2 212 C 175 l l l l 57 174.32 83 PCT 10 P2 VS3 1.00 TEH TEC.610 SBAY2 207 C 191 l l l l 63 174.32 106 PCT 10 P2 VS3 1.03 TEH TEC.610 SBAY2 207 C 194 l l l l 65 174.27 43 PCT 9 P2 BW2.37 TEH TEC.610 SBAY2 207 C 195 l l l l 89 174.29 114 PCT 10 P2 BW1 -.72 TEH TEC.610 SBAY2 211 C 184 l l 89 174.34 104 PCT 11 P2 VS2.91 TEH TEC.610 SBAY2 211 C 184 l l l l 93 174.35 128 PCT 11 P2 VS2.94 TEH TEC.610 SBAY2 211 C 183 l l l l 99 174.23 145 PCT 9 P2 09H.76 TEH TEC.610 SBAY2 211 C 180 l l 99 174.28 109 PCT 9 P2 VS3 -1.16 TEH TEC.610 SBAY2 211 C 180 l l l l 115 174.26 155 PCT 9 P2 09H.80 TEH TEC.610 SBAY2 211 C 172 l l 115 174.29 151 PCT 10 P2 VS1.81 TEH TEC.610 SBAY2 211 C 172 l l l l 80 175.21 141 PCT 8 P2 VS2.65 TEH TEC.610 SBAY2 208 C 125 l l l l 82 175.57 125 PCT 17 P2 VS2.83 TEH TEC.610 SBAY2 208 C 124 l l l l 100 175.41 133 PCT 13 P2 VS3.50 TEH TEC.610 SBAY2 208 C 114 l l l l 106 175.47 138 PCT 15 P2 10H.76 TEH TEC.610 SBAY2 208 C 111 l l l l 118 175.37 138 PCT 12 P2 BW1 -.72 TEH TEC.610 SBAY2 211 C 168 l l l l 79 176.66 117 PCT 18 P2 VS4 -.87 TEH TEC.610 SBAY2 208 C 89 l l l l 87 176.98 295 WAR.37 P40 VS2.61 VS3 TEH.610 ZYAX2 35 H 17 l l 87 176.83 115 PCT 21 P2 VS2.72 TEH TEC.610 SBAY2 208 C 93 l l l l 89 176.30 121 PCT 11 P2 BW1.77 TEH TEC.610 SBAY2 208 C 94 l
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
l ROW COL VOLTS DEG IND PER CRLEN CHN LOCN INCH1 INCH2 BEGT ENDT PDIA PTYPE CAL L IDX UTIL1 UTIL2l
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
49 ST Max
SG - 31 Calls of Interest Palo Verde 3 U3R20 PVNGS3 20180401 04/20/2018 13:40:22
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
l ROW COL VOLTS DEG IND PER CRLEN CHN LOCN INCH1 INCH2 BEGT ENDT PDIA PTYPE CAL L IDX UTIL1 UTIL2l
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
l l l 91 176.36 129 PCT 12 P2 BW1 -.71 TEH TEC.610 SBAY2 208 C 95 l l 91 176.41 105 PCT 13 P2 BW2 -.96 TEH TEC.610 SBAY2 208 C 95 l l l l 99 176.43 124 PCT 14 P2 VS3 -1.24 TEH TEC.610 SBAY2 208 C 99 l l l l 103 176.35 98 PCT 12 P2 VS3 -1.01 TEH TEC.610 SBAY2 208 C 101 l l l l 54 177.26 132 PCT 9 P2 VS3 -.87 TEH TEC.610 SBAY2 207 C 146 l l l l 60 177.34 50 PCT 11 P2 BW1 -.89 TEH TEC.610 SBAY2 207 C 143 l l l l 94 177.33 137 PCT 11 P2 VS2.66 TEH TEC.610 SBAY2 207 C 124 l l l l 98 177.29 155 PCT 10 P2 BW2 1.01 TEH TEC.610 SBAY2 207 C 118 l l l l 77 178.32 117 PCT 11 P2 VS3 -1.09 TEH TEC.610 SBAY2 207 C 83 l l l l 81 178 2.61 96 WAR.34 P23 BW2.92 VS3 TEC.610 ZYAX2 33 C 34 l l 81 178 1.57 103 PCT 29 P2 BW2 1.03 TEH TEC.610 SBAY2 207 C 85 l l l l 101 178.29 108 PCT 10 P2 VS3 -.97 TEH TEC.610 SBAY2 207 C 95 l l l l 105 178.46 106 PCT 14 P2 VS4.76 TEH TEC.610 SBAY2 207 C 97 l l l l 113 178.32 84 PCT 10 P2 04C.85 TEH TEC.610 SBAY2 211 C 166 l l l l 104 179.42 103 PCT 13 P2 VS3 -.76 TEH TEC.610 SBAY2 206 C 301 l l l l 110 179.36 101 PCT 11 P2 VS3 -1.04 TEH TEC.610 SBAY2 207 C 104 l l l l 43 180.27 121 PCT 10 P2 08C.81 TEH TEC.610 SBAY2 206 C 266 l l l l 67 180.34 88 PCT 11 P2 VS3 1.05 TEH TEC.610 SBAY2 206 C 278 l l l l 79 180.27 75 PCT 10 P2 VS3 -.86 TEH TEC.610 SBAY2 206 C 284 l l l l 85 180.38 111 PCT 12 P2 VS4.73 TEH TEC.610 SBAY2 206 C 287 l l l l 89 180.28 100 PCT 10 P2 BW1 -1.37 TEH TEC.610 SBAY2 206 C 289 l l l l 91 180.28 100 PCT 10 P2 BW1 -1.20 TEH TEC.610 SBAY2 206 C 290 l l l l 103 180.60 127 PCT 17 P2 VS3 -1.09 TEH TEC.610 SBAY2 206 C 296 l
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
l ROW COL VOLTS DEG IND PER CRLEN CHN LOCN INCH1 INCH2 BEGT ENDT PDIA PTYPE CAL L IDX UTIL1 UTIL2l
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
50 ST Max
SG - 31 Calls of Interest Palo Verde 3 U3R20 PVNGS3 20180401 04/20/2018 13:40:22
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
l ROW COL VOLTS DEG IND PER CRLEN CHN LOCN INCH1 INCH2 BEGT ENDT PDIA PTYPE CAL L IDX UTIL1 UTIL2l
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
l l l 105 180.53 132 PCT 16 P2 VS3 -1.07 TEH TEC.610 SBAY2 206 C 297 l l l l 107 180.42 122 PCT 13 P2 VS3 -1.09 TEH TEC.610 SBAY2 206 C 298 l l 107 180.29 114 PCT 10 P2 05C.75 TEH TEC.610 SBAY2 206 C 298 l l l l 56 181.33 35 PCT 11 P2 BW1 -1.66 TEH TEC.610 SBAY2 207 C 28 l l l l 88 181.31 117 PCT 10 P2 VS3 -.70 TEH TEC.610 SBAY2 207 C 12 l l l l 90 181.30 117 PCT 10 P2 VS3 -1.02 TEH TEC.610 SBAY2 207 C 11 l l l l 98 181 1.05 81 WAR.51 P43 VS3 -.97 VS3 TEH.610 ZYAX2 35 H 16 l l 98 181 1.01 104 PCT 23 P2 VS3 -.99 TEH TEC.610 SBAY2 207 C 7 l l l l 100 181 1.11 253 WAR.20 P43 VS3 -1.06 VS3 TEH.610 ZYAX2 35 H 15 l l 100 181 1.05 115 PCT 24 P2 VS3 -.95 TEH TEC.610 SBAY2 207 C 6 l l l l 106 181.65 110 PCT 17 P2 VS3 -1.04 TEH TEC.610 SBAY2 205 C 294 l l 106 181.34 136 PCT 11 P2 05C.76 TEH TEC.610 SBAY2 205 C 294 l l l l 75 182.44 112 PCT 13 P2 VS2 -.86 TEH TEC.610 SBAY2 205 C 279 l l l l 83 182.33 131 PCT 11 P2 VS2 -.81 TEH TEC.610 SBAY2 205 C 283 l l l l 85 182.39 82 PCT 12 P2 VS4.84 TEH TEC.610 SBAY2 205 C 284 l l l l 87 182.38 111 PCT 12 P2 VS3 -.98 TEH TEC.610 SBAY2 205 C 285 l l l l 99 182.38 121 PCT 12 P2 VS3 -1.36 TEH TEC.610 SBAY2 205 C 291 l l l l 103 182.36 107 PCT 11 P2 VS3 -1.09 TEH TEC.610 SBAY2 205 C 293 l l l l 4 183.27 145 PCT 10 P2 07C.78 TEH TEC.610 SBAY2 29 C 89 l l l l 10 183.38 111 PCT 13 P2 07H -1.05 TEH TEC.610 SBAY2 29 C 92 l l l l 82 183.39 65 PCT 12 P2 VS4 -.65 TEH TEC.610 SBAY2 206 C 214 l l l l 88 183.30 98 PCT 10 P2 VS2.68 TEH TEC.610 SBAY2 206 C 211 l l l l 94 183.31 124 PCT 10 P2 09H.76 TEH TEC.610 SBAY2 206 C 208 l l l l 102 183.31 74 PCT 11 P2 04C.74 TEH TEC.610 SBAY2 206 C 204 l
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
l ROW COL VOLTS DEG IND PER CRLEN CHN LOCN INCH1 INCH2 BEGT ENDT PDIA PTYPE CAL L IDX UTIL1 UTIL2l
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
51 ST Max
SG - 31 Calls of Interest Palo Verde 3 U3R20 PVNGS3 20180401 04/20/2018 13:40:22
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
l ROW COL VOLTS DEG IND PER CRLEN CHN LOCN INCH1 INCH2 BEGT ENDT PDIA PTYPE CAL L IDX UTIL1 UTIL2l
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
l l l 13 184.14 74 PCT 9 P2 08H.35 TEH TEC.610 SBAY2 206 C 160 l l l l 49 184.32 67 PCT 11 P2 BW2 -1.20 TEH TEC.610 SBAY2 206 C 178 l l l l 59 184.51 84 PCT 15 P2 BW2.40 TEH TEC.610 SBAY2 206 C 183 l l l l 81 184.39 54 PCT 13 P2 VS4 -.76 TEH TEC.610 SBAY2 206 C 194 l l l l 83 184.29 39 PCT 10 P2 BW1.00 TEH TEC.610 SBAY2 206 C 195 l l l l 97 184.35 118 PCT 12 P2 VS3 -1.15 TEH TEC.610 SBAY2 206 C 202 l l l l 99 184.70 118 PCT 19 P2 VS3 -1.38 TEH TEC.610 SBAY2 206 C 203 l l l l 80 185.55 132 PCT 15 P2 09H.67 TEH TEC.610 SBAY2 205 C 212 l l l l 96 185.34 135 PCT 11 P2 BW1.33 TEH TEC.610 SBAY2 205 C 204 l l l l 47 186.32 95 PCT 10 P2 BW1 -1.13 TEH TEC.610 SBAY2 205 C 178 l l l l 77 186.48 111 PCT 14 P2 VS3 -1.14 TEH TEC.610 SBAY2 205 C 193 l l l l 81 186 1.93 106 WAR.54 P32 VS4 -.93 VS3 TEC.610 ZYAX2 33 C 35 l l 81 186 1.01 100 PCT 23 P2 VS4 -.72 TEH TEC.610 SBAY2 205 C 195 l l l l 92 187.28 71 PCT 10 P2 05C.76 TEH TEC.610 SBAY2 206 C 118 l l l l 53 188.33 59 PCT 11 P2 BW2 -1.02 TEH TEC.610 SBAY2 206 C 99 l l l l 77 188.37 134 PCT 12 P2 VS3 -1.02 TEH TEC.610 SBAY2 206 C 111 l l l l 79 188.32 135 PCT 11 P2 VS3 -.96 TEH TEC.610 SBAY2 206 C 112 l l l l 81 188.30 105 PCT 10 P2 09C -.25 TEH TEC.610 SBAY2 206 C 113 l l l l 87 188.28 129 PCT 10 P2 VS3 -.93 TEH TEC.610 SBAY2 206 C 116 l l l l 89 188.48 114 PCT 15 P2 VS3 -1.14 TEH TEC.610 SBAY2 206 C 117 l l l l 58 189.57 120 PCT 16 P2 VS3 -.85 TEH TEC.610 SBAY2 205 C 136 l l l l 75 190.27 145 PCT 9 P2 VS2 -.90 TEH TEC.610 SBAY2 205 C 117 l l l
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
l ROW COL VOLTS DEG IND PER CRLEN CHN LOCN INCH1 INCH2 BEGT ENDT PDIA PTYPE CAL L IDX UTIL1 UTIL2l
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
52 ST Max
SG - 31 Calls of Interest Palo Verde 3 U3R20 PVNGS3 20180401 04/20/2018 13:40:22
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
l ROW COL VOLTS DEG IND PER CRLEN CHN LOCN INCH1 INCH2 BEGT ENDT PDIA PTYPE CAL L IDX UTIL1 UTIL2l
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
l 77 190.36 112 PCT 11 P2 VS3 -1.08 TEH TEC.610 SBAY2 205 C 118 l l l l 52 191.27 109 PCT 10 P2 09H.26 TEH TEC.610 SBAY2 206 C 54 l l l l 58 191.37 116 PCT 12 P2 BW1 -1.13 TEH TEC.610 SBAY2 206 C 51 l l l l 77 192.89 138 WAR.14 P47 VS3 -1.04 VS3 TEH.610 ZYAX2 35 H 11 l l 77 192 1.00 121 PCT 23 P2 VS3 -1.03 TEH TEC.610 SBAY2 206 C 39 l l l l 56 195.27 130 PCT 10 P2 09C.71 TEH TEC.610 SBAY2 204 C 143 l l l l 58 197.19 137 PCT 10 P2 03C.83 TEH TEC.610 SBAY2 204 C 86 l l l l 36 199.30 143 PCT 10 P2 08C.75 TEH TEC.610 SBAY2 204 C 48 l l l l 29 202.17 57 PCT 10 P2 08C -1.07 TEH TEC.610 SBAY2 204 C 36 l
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
l ROW COL VOLTS DEG IND PER CRLEN CHN LOCN INCH1 INCH2 BEGT ENDT PDIA PTYPE CAL L IDX UTIL1 UTIL2l
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
Tubes: 976 Records: 1329 53 ST Max
APPENDIX C STEAM GENERATOR 32
SUMMARY
DATA SHEETS
SG - 32 Calls of Interest Palo Verde 3 U3R20 PVNGS3 20180401 04/20/2018 13:40:22
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
l ROW COL VOLTS DEG IND PER CRLEN CHN LOCN INCH1 INCH2 BEGT ENDT PDIA PTYPE CAL L IDX UTIL1 UTIL2l
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
l 24 5.25 90 PCT 10 P2 03C.76 TEH TEC.610 SBAY2 1 C 21 l l l l 9 8.20 132 PCT 9 P2 05H.77 TEH TEC.610 SBAY2 26 C 11 l l l l 63 8.31 96 PCT 10 P2 BW1 -.68 TEH TEC.610 SBAY2 11 C 274 l l l l 71 10.33 104 PCT 11 P2 04C -.18 TEH TEC.610 SBAY2 11 C 281 l l l l 52 11.32 137 PCT 11 P2 VS3 -.72 TEH TEC.610 SBAY2 2 C 117 l l l l 75 12.75 119 PCT 20 P2 VS3 -.95 TEH TEC.610 SBAY2 13 C 10 l l 75 12.51 117 PCT 15 P2 VS3 1.02 TEH TEC.610 SBAY2 13 C 10 l l 75 12 2.04 143 WAR.58 P7 VS3 -.92 VS3 TEH.610 ZYAX2 27 H 80 l l 75 12 2.05 139 WAR.20 P31 VS3.79 VS3 TEH.610 ZYAX2 27 H 80 l l l l 72 13.08 131 NQI 3 08H 4.43 TEH TEC.610 SBAY2 14 C 9 l l 72 13 NDF P31 08H 4.43 09H TEH.610 ZYAX2 27 H 79 l l l l 74 13.29 102 PCT 10 P2 VS3 -.63 TEH TEC.610 SBAY2 13 C 12 l l l l 78 13.27 47 PCT 10 P2 BW1.71 TEH TEC.610 SBAY2 13 C 14 l l l l 71 14.43 123 PCT 13 P2 VS3 -.92 TEH TEC.610 SBAY2 14 C 11 l l l l 81 14.45 110 PCT 14 P2 VS4.99 TEH TEC.610 SBAY2 13 C 18 l l l l 83 14.31 132 PCT 11 P2 09H.73 TEH TEC.610 SBAY2 13 C 19 l l l l 74 15.44 146 PCT 14 P2 VS2.82 TEH TEC.610 SBAY2 14 C 15 l l l l 76 15.41 112 PCT 13 P2 VS4 -.65 TEH TEC.610 SBAY2 14 C 16 l l l l 82 15.65 108 PCT 18 P2 VS3 1.15 TEH TEC.610 SBAY2 13 C 21 l l l l 71 16.38 140 PCT 12 P2 VS2 -.97 TEH TEC.610 SBAY2 14 C 46 l l l l 14 17.32 139 PCT 11 P2 08H -1.19 TEH TEC.610 SBAY2 9 C 10 l l l l 74 17.33 151 PCT 11 P2 VS2.82 TEH TEC.610 SBAY2 14 C 66 l l l l 69 18.49 84 PCT 15 P2 VS3 -.77 TEH TEC.610 SBAY2 13 C 63 l l l l 73 18.39 108 PCT 13 P2 VS3 -.79 TEH TEC.610 SBAY2 13 C 61 l l l
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
l ROW COL VOLTS DEG IND PER CRLEN CHN LOCN INCH1 INCH2 BEGT ENDT PDIA PTYPE CAL L IDX UTIL1 UTIL2l
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
1 ST Max
SG - 32 Calls of Interest Palo Verde 3 U3R20 PVNGS3 20180401 04/20/2018 13:40:22
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
l ROW COL VOLTS DEG IND PER CRLEN CHN LOCN INCH1 INCH2 BEGT ENDT PDIA PTYPE CAL L IDX UTIL1 UTIL2l
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
l 75 18.34 83 PCT 11 P2 VS3 -.97 TEH TEC.610 SBAY2 13 C 60 l l l l 81 18.40 110 PCT 13 P2 VS3 -.93 TEH TEC.610 SBAY2 13 C 57 l l l l 83 18.30 145 PCT 10 P2 VS2 -.80 TEH TEC.610 SBAY2 14 C 27 l l l l 85 18.32 121 PCT 11 P2 VS2 -.92 TEH TEC.610 SBAY2 14 C 28 l l l l 89 18.28 147 PCT 10 P2 VS2 -.67 TEH TEC.610 SBAY2 13 C 31 l l l l 87 20.45 136 PCT 14 P2 VS2 -.62 TEH TEC.610 SBAY2 14 C 34 l l l l 97 20.33 113 PCT 11 P2 VS3 -.98 TEH TEC.610 SBAY2 13 C 40 l l l l 99 20.33 133 PCT 11 P2 VS3 -.85 TEH TEC.610 SBAY2 13 C 41 l l l l 86 21.42 138 PCT 13 P2 VS3.91 TEH TEC.610 SBAY2 14 C 101 l l l l 92 21.47 122 PCT 14 P2 BW1.15 TEH TEC.610 SBAY2 14 C 39 l l l l 100 21.34 129 PCT 11 P2 VS3 -.42 TEH TEC.610 SBAY2 14 C 132 l l l l 102 21 1.02 118 PCT 24 P2 VS3 -.85 TEH TEC.610 SBAY2 13 C 85 l l 102 21 2.37 100 WAR.32 P24 VS3 -.85 VS3 TEH.610 ZYAX2 27 H 77 l l l l 93 22.33 120 PCT 11 P2 VS2 -.98 TEH TEC.610 SBAY2 14 C 42 l l l l 95 22.47 119 PCT 14 P2 VS2 -.82 TEH TEC.610 SBAY2 14 C 43 l l l l 100 23.41 124 PCT 13 P2 VS3 -.32 TEH TEC.610 SBAY2 14 C 104 l l l l 25 24.42 74 PCT 13 P2 VS3 -.89 TEH TEC.610 SBAY2 3 C 120 l l l l 79 24.32 108 PCT 11 P2 VS4 -.67 TEH TEC.610 SBAY2 14 C 291 l l l l 83 24.39 72 PCT 13 P2 VS2 -.89 TEH TEC.610 SBAY2 13 C 256 l l l l 103 24.29 143 PCT 10 P2 BW1 1.07 TEH TEC.610 SBAY2 14 C 129 l l l l 109 24.37 89 PCT 12 P2 VS3.20 TEH TEC.610 SBAY2 13 C 110 l l l l 72 25.15 93 PCT 6 P2 07C.25 TEH TEC.610 SBAY2 16 C 16 l l l l 84 25.42 91 PCT 14 P2 VS4 -.76 TEH TEC.610 SBAY2 13 C 255 l
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
l ROW COL VOLTS DEG IND PER CRLEN CHN LOCN INCH1 INCH2 BEGT ENDT PDIA PTYPE CAL L IDX UTIL1 UTIL2l
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
2 ST Max
SG - 32 Calls of Interest Palo Verde 3 U3R20 PVNGS3 20180401 04/20/2018 13:40:22
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
l ROW COL VOLTS DEG IND PER CRLEN CHN LOCN INCH1 INCH2 BEGT ENDT PDIA PTYPE CAL L IDX UTIL1 UTIL2l
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
l l l 90 25.32 91 PCT 11 P2 10C -.45 TEH TEC.610 SBAY2 13 C 196 l l l l 102 25.35 124 PCT 11 P2 BW1.85 TEH TEC.610 SBAY2 14 C 106 l l l l 105 26.36 135 PCT 12 P2 BW1 1.10 TEH TEC.610 SBAY2 14 C 127 l l l l 111 26.41 97 PCT 13 P2 VS3 -.96 TEH TEC.610 SBAY2 13 C 112 l l l l 113 26.31 132 PCT 11 P2 VS3 -1.16 TEH TEC.610 SBAY2 13 C 119 l l 113 26.45 128 PCT 14 P2 VS3.50 TEH TEC.610 SBAY2 13 C 119 l l l l 80 27.32 90 PCT 11 P2 VS2 -.86 TEH TEC.610 SBAY2 15 C 45 l l l l 114 27.42 128 PCT 14 P2 VS3 -1.02 TEH TEC.610 SBAY2 13 C 120 l l l l 97 28.40 139 PCT 13 P2 VS2 -.77 TEH TEC.610 SBAY2 14 C 170 l l l l 111 28.64 122 PCT 18 P2 VS3.59 TEH TEC.610 SBAY2 13 C 102 l l l l 113 28.35 111 PCT 12 P2 VS3.47 TEH TEC.610 SBAY2 13 C 114 l l l l 94 29.32 89 PCT 11 P2 VS2 -.79 TEH TEC.610 SBAY2 13 C 199 l l l l 96 29.38 111 PCT 13 P2 10H.78 TEH TEC.610 SBAY2 13 C 185 l l l l 59 30.37 123 PCT 12 P2 09H.71 TEH TEC.610 SBAY2 15 C 61 l l l l 101 30.30 129 PCT 10 P2 VS3.88 TEH TEC.610 SBAY2 14 C 154 l l l l 115 30.32 125 PCT 11 P2 VS3.62 TEH TEC.610 SBAY2 13 C 116 l l l l 114 31.29 107 PCT 10 P2 VS3 1.03 TEH TEC.610 SBAY2 13 C 99 l l l l 118 31.30 95 PCT 11 P2 VS3 -.85 TEH TEC.610 SBAY2 19 C 45 l l l l 111 32.25 124 NQI 3 10H 13.16 TEH TEC.610 SBAY2 14 C 119 l l 111 32.39 106 PCT 12 P2 VS3.64 TEH TEC.610 SBAY2 14 C 119 l l 111 32 NDF 143 10H 13.16 VS3 TEH.610 ZYAX2 27 H 76 l l l l 117 32.57 118 PCT 17 P2 VS3 -1.24 TEH TEC.610 SBAY2 13 C 118 l l l l 123 32.43 119 PCT 14 P2 VS3.46 TEH TEC.610 SBAY2 19 C 24 l l l
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
l ROW COL VOLTS DEG IND PER CRLEN CHN LOCN INCH1 INCH2 BEGT ENDT PDIA PTYPE CAL L IDX UTIL1 UTIL2l
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
3 ST Max
SG - 32 Calls of Interest Palo Verde 3 U3R20 PVNGS3 20180401 04/20/2018 13:40:22
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
l ROW COL VOLTS DEG IND PER CRLEN CHN LOCN INCH1 INCH2 BEGT ENDT PDIA PTYPE CAL L IDX UTIL1 UTIL2l
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
l 2 33.28 113 PCT 11 P2 BW1 2.79 TEH TEC.610 SBAY2 25 C 78 l l l l 24 33.61 114 PCT 17 P2 VS3.91 TEH TEC.610 SBAY2 10 C 80 l l l l 108 33.30 55 PCT 11 P2 VS2 -.84 TEH TEC.610 SBAY2 13 C 134 l l l l 114 33.21 140 PCT 8 P2 10H -.25 TEH TEC.610 SBAY2 13 C 97 l l l l 120 33.35 89 PCT 11 P2 VS2.84 TEH TEC.610 SBAY2 20 C 15 l l l l 7 34.32 126 PCT 11 P2 BW2 1.50 TEH TEC.610 SBAY2 25 C 86 l l l l 23 34.90 120 PCT 22 P2 08H.62 TEH TEC.610 SBAY2 9 C 72 l l 23 34 1.39 88 WAR.28 P19 08H.54 08H TEH.610 ZYAX2 27 H 83 l l l l 37 34.42 153 PCT 14 P2 08H.72 TEH TEC.610 SBAY2 9 C 79 l l l l 77 34.36 107 PCT 12 P2 BW2 -1.38 TEH TEC.610 SBAY2 15 C 86 l l l l 85 34.67 66 PCT 18 P2 BW2.95 TEH TEC.610 SBAY2 15 C 82 l l l l 99 34.30 79 PCT 10 P2 VS2 -.62 TEH TEC.610 SBAY2 13 C 204 l l 99 34.81 110 PCT 21 P2 VS3 -1.03 TEH TEC.610 SBAY2 13 C 204 l l 99 34 1.38 306 WAR.31 P7 VS3 -.72 VS3 TEH.610 ZYAX2 27 H 75 l l l l 113 34.41 131 PCT 13 P2 VS4.85 TEH TEC.610 SBAY2 14 C 117 l l l l 117 34.34 99 PCT 12 P2 VS3 -1.06 TEH TEC.610 SBAY2 13 C 122 l l l l 100 35.39 96 PCT 13 P2 VS3 1.05 TEH TEC.610 SBAY2 13 C 205 l l l l 118 35.35 77 PCT 12 P2 VS3.92 TEH TEC.610 SBAY2 19 C 48 l l l l 103 36.27 107 PCT 10 P2 VS2.86 TEH TEC.610 SBAY2 13 C 179 l l l l 105 36.36 125 PCT 12 P2 VS3 -1.09 TEH TEC.610 SBAY2 14 C 178 l l l l 129 36.31 127 PCT 11 P2 VS3 -.94 TEH TEC.610 SBAY2 19 C 52 l l l l 88 37.35 141 PCT 12 P2 VS2 -.78 TEH TEC.610 SBAY2 16 C 117 l l l l 100 37.45 97 PCT 14 P2 10H.77 TEH TEC.610 SBAY2 14 C 203 l l l l 102 37.40 96 PCT 13 P2 VS3.91 TEH TEC.610 SBAY2 13 C 207 l
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
l ROW COL VOLTS DEG IND PER CRLEN CHN LOCN INCH1 INCH2 BEGT ENDT PDIA PTYPE CAL L IDX UTIL1 UTIL2l
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
4 ST Max
SG - 32 Calls of Interest Palo Verde 3 U3R20 PVNGS3 20180401 04/20/2018 13:40:22
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
l ROW COL VOLTS DEG IND PER CRLEN CHN LOCN INCH1 INCH2 BEGT ENDT PDIA PTYPE CAL L IDX UTIL1 UTIL2l
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
l l l 106 37.27 109 PCT 10 P2 VS2 -.94 TEH TEC.610 SBAY2 14 C 179 l l 106 37.37 126 PCT 12 P2 VS4.88 TEH TEC.610 SBAY2 14 C 179 l l l l 124 37.25 140 PCT 8 P2 10H.77 TEH TEC.610 SBAY2 20 C 19 l l l l 51 38.34 95 PCT 12 P2 09H.75 TEH TEC.610 SBAY2 9 C 130 l l l l 53 38.54 83 PCT 16 P2 09H.78 TEH TEC.610 SBAY2 9 C 131 l l l l 57 38.43 88 PCT 14 P2 09H.71 TEH TEC.610 SBAY2 15 C 135 l l l l 59 38.47 120 PCT 14 P2 09H.78 TEH TEC.610 SBAY2 15 C 134 l l l l 71 38.37 110 PCT 12 P2 VS3.99 TEH TEC.610 SBAY2 15 C 128 l l l l 113 38.41 118 PCT 13 P2 VS3 -.84 TEH TEC.610 SBAY2 13 C 129 l l l l 123 38.17 122 PCT 6 P2 10H.82 TEH TEC.610 SBAY2 20 C 63 l l l l 127 38.26 142 PCT 8 P2 10H.75 TEH TEC.610 SBAY2 20 C 44 l l l l 88 39.25 38 PCT 9 P2 VS4 -.63 TEH TEC.610 SBAY2 15 C 153 l l l l 130 39.33 89 PCT 12 P2 05H.83 TEH TEC.610 SBAY2 19 C 31 l l l l 134 39.30 56 PCT 11 P2 03C -.89 TEH TEC.610 SBAY2 19 C 44 l l l l 99 40.34 126 PCT 12 P2 VS3 -.93 TEH TEC.610 SBAY2 13 C 240 l l 99 40.53 109 PCT 16 P2 VS3.99 TEH TEC.610 SBAY2 13 C 240 l l l l 117 40.29 107 PCT 11 P2 VS3 -1.21 TEH TEC.610 SBAY2 19 C 81 l l l l 123 40.39 66 PCT 13 P2 BW1.79 TEH TEC.610 SBAY2 19 C 78 l l l l 125 40.46 90 PCT 15 P2 VS3 -.82 TEH TEC.610 SBAY2 19 C 77 l l l l 100 41.37 54 PCT 12 P2 10H.82 TEH TEC.610 SBAY2 13 C 239 l l l l 120 41.34 114 PCT 10 P2 VS3 -.73 TEH TEC.610 SBAY2 20 C 67 l l l l 132 41.29 118 PCT 10 P2 05H 1.00 TEH TEC.610 SBAY2 19 C 33 l l l l 136 41.27 133 PCT 10 P2 05H.81 TEH TEC.610 SBAY2 19 C 42 l
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
l ROW COL VOLTS DEG IND PER CRLEN CHN LOCN INCH1 INCH2 BEGT ENDT PDIA PTYPE CAL L IDX UTIL1 UTIL2l
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
5 ST Max
SG - 32 Calls of Interest Palo Verde 3 U3R20 PVNGS3 20180401 04/20/2018 13:40:22
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
l ROW COL VOLTS DEG IND PER CRLEN CHN LOCN INCH1 INCH2 BEGT ENDT PDIA PTYPE CAL L IDX UTIL1 UTIL2l
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
l l l 53 42.49 110 PCT 15 P2 09H.81 TEH TEC.610 SBAY2 9 C 173 l l l l 73 42.38 131 PCT 12 P2 09H.75 TEH TEC.610 SBAY2 15 C 169 l l l l 95 42.32 123 PCT 11 P2 VS2 -.68 TEH TEC.610 SBAY2 15 C 159 l l l l 99 42.37 116 PCT 12 P2 VS3 -1.22 TEH TEC.610 SBAY2 15 C 158 l l l l 117 42.30 88 PCT 11 P2 VS3 -.96 TEH TEC.610 SBAY2 13 C 125 l l l l 125 42.49 115 PCT 14 P2 VS4.84 TEH TEC.610 SBAY2 20 C 72 l l l l 48 43.44 111 PCT 14 P2 VS3 -.79 TEH TEC.610 SBAY2 9 C 177 l l l l 74 43.24 80 PCT 9 P2 VS2 -.81 TEH TEC.610 SBAY2 15 C 188 l l l l 76 43.28 102 PCT 10 P2 VS2 -.73 TEH TEC.610 SBAY2 15 C 189 l l l l 116 43.34 63 PCT 12 P2 VS2 1.11 TEH TEC.610 SBAY2 13 C 164 l l l l 122 43.35 136 PCT 12 P2 VS3.81 TEH TEC.610 SBAY2 19 C 84 l l l l 126 43.27 117 PCT 10 P2 VS1.58 TEH TEC.610 SBAY2 19 C 86 l l l l 93 44.44 124 PCT 14 P2 10H.76 TEH TEC.610 SBAY2 16 C 163 l l l l 99 44.49 124 PCT 15 P2 VS3 -1.07 TEH TEC.610 SBAY2 14 C 271 l l l l 119 44.29 41 PCT 11 P2 BW1.88 TEH TEC.610 SBAY2 19 C 90 l l l l 135 44.29 68 PCT 11 P2 VS1 -.76 TEH TEC.610 SBAY2 19 C 36 l l l l 120 45.77 106 PCT 19 P2 VS3.95 TEH TEC.610 SBAY2 20 C 78 l l l l 132 45.29 81 PCT 9 P2 VS3.90 TEH TEC.610 SBAY2 20 C 27 l l l l 63 46.30 90 PCT 10 P2 BW1 -1.19 TEH TEC.610 SBAY2 15 C 218 l l l l 89 46.29 47 PCT 10 P2 BW2.76 TEH TEC.610 SBAY2 15 C 231 l l l l 107 46.28 111 PCT 10 P2 BW2 -1.02 TEH TEC.610 SBAY2 14 C 243 l l l l 113 46.34 97 PCT 12 P2 VS1 -.67 TEH TEC.610 SBAY2 13 C 169 l
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
l ROW COL VOLTS DEG IND PER CRLEN CHN LOCN INCH1 INCH2 BEGT ENDT PDIA PTYPE CAL L IDX UTIL1 UTIL2l
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
6 ST Max
SG - 32 Calls of Interest Palo Verde 3 U3R20 PVNGS3 20180401 04/20/2018 13:40:22
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
l ROW COL VOLTS DEG IND PER CRLEN CHN LOCN INCH1 INCH2 BEGT ENDT PDIA PTYPE CAL L IDX UTIL1 UTIL2l
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
l l l 121 46.85 108 PCT 20 P2 VS2 -.83 TEH TEC.610 SBAY2 20 C 87 l l 121 46 1.68 93 WAR.28 P15 VS2 -.80 VS3 TEH.610 ZYAX2 27 H 72 l l l l 127 46.45 117 PCT 13 P2 VS1 -.80 TEH TEC.610 SBAY2 20 C 90 l l l l 74 47.36 107 PCT 12 P2 09C -.25 TEH TEC.610 SBAY2 15 C 247 l l l l 100 47.36 125 PCT 12 P2 10H.83 TEH TEC.610 SBAY2 15 C 234 l l l l 102 47.29 83 PCT 10 P2 VS3.92 TEH TEC.610 SBAY2 14 C 268 l l l l 104 47.29 112 PCT 10 P2 VS3.86 TEH TEC.610 SBAY2 15 C 233 l l l l 110 47.28 62 PCT 10 P2 VS3.88 TEH TEC.610 SBAY2 14 C 193 l l l l 126 47.40 86 PCT 13 P2 VS1.51 TEH TEC.610 SBAY2 19 C 103 l l 126 47.59 119 PCT 17 P2 VS4 -1.04 TEH TEC.610 SBAY2 19 C 103 l l l l 140 47.30 87 PCT 11 P2 VS4 -.78 TEH TEC.610 SBAY2 19 C 63 l l l l 51 48.53 83 PCT 15 P2 09H.94 TEH TEC.610 SBAY2 10 C 245 l l l l 57 48.31 144 PCT 11 P2 BW1 -1.84 TEH TEC.610 SBAY2 16 C 213 l l l l 59 48.25 129 PCT 9 P2 BW1 -.66 TEH TEC.610 SBAY2 16 C 214 l l l l 133 48.29 85 PCT 11 P2 BW1 -.99 TEH TEC.610 SBAY2 21 C 7 l l l l 140 49.21 120 PCT 7 P2 11H -.25 TEH TEC.610 SBAY2 20 C 58 l l l l 77 50.35 113 PCT 13 P2 VS2.61 TEH TEC.610 SBAY2 17 C 18 l l l l 81 50.33 119 PCT 12 P2 VS2.88 TEH TEC.610 SBAY2 17 C 20 l l l l 85 50.27 88 PCT 10 P2 VS2 -.66 TEH TEC.610 SBAY2 17 C 22 l l l l 141 50.35 133 PCT 11 P2 11H.75 TEH TEC.610 SBAY2 20 C 109 l l l l 145 50.28 66 PCT 10 P2 VS1 -1.04 TEH TEC.610 SBAY2 19 C 116 l l l l 72 51.31 128 PCT 12 P2 VS2 -.67 TEH TEC.610 SBAY2 17 C 50 l l l l 104 51.25 108 PCT 10 P2 VS3.95 TEH TEC.610 SBAY2 17 C 34 l
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
l ROW COL VOLTS DEG IND PER CRLEN CHN LOCN INCH1 INCH2 BEGT ENDT PDIA PTYPE CAL L IDX UTIL1 UTIL2l
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
7 ST Max
SG - 32 Calls of Interest Palo Verde 3 U3R20 PVNGS3 20180401 04/20/2018 13:40:22
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
l ROW COL VOLTS DEG IND PER CRLEN CHN LOCN INCH1 INCH2 BEGT ENDT PDIA PTYPE CAL L IDX UTIL1 UTIL2l
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
l l l 112 51.35 62 PCT 12 P2 BW1 1.39 TEH TEC.610 SBAY2 14 C 248 l l l l 124 51.34 54 PCT 12 P2 VS3.97 TEH TEC.610 SBAY2 21 C 18 l l l l 126 51.41 88 PCT 14 P2 VS1.48 TEH TEC.610 SBAY2 21 C 19 l l l l 53 52.21 144 PCT 9 P2 09H.76 TEH TEC.610 SBAY2 10 C 292 l l l l 103 52.33 109 PCT 11 P2 VS2 -.75 TEH TEC.610 SBAY2 18 C 28 l l 103 52.25 124 PCT 9 P2 VS4 -.82 TEH TEC.610 SBAY2 18 C 28 l l l l 105 52.46 132 PCT 14 P2 VS4 -.77 TEH TEC.610 SBAY2 18 C 29 l l l l 109 52.28 122 PCT 9 P2 VS3 -.98 TEH TEC.610 SBAY2 18 C 30 l l l l 125 52.33 93 PCT 12 P2 VS2 -.77 TEH TEC.610 SBAY2 21 C 35 l l l l 135 52.44 125 PCT 15 P2 VS3.84 TEH TEC.610 SBAY2 21 C 30 l l l l 68 53.29 123 PCT 10 P2 09H.83 TEH TEC.610 SBAY2 18 C 51 l l l l 100 53.25 103 PCT 8 P2 BW1 -1.12 TEH TEC.610 SBAY2 18 C 35 l l l l 102 53.33 99 PCT 11 P2 10H.86 TEH TEC.610 SBAY2 18 C 34 l l l l 106 53.95 110 PCT 22 P2 VS2 -.72 TEH TEC.610 SBAY2 18 C 32 l l 106 53 2.19 84 WAR.39 P15 VS2 -.65 VS3 TEH.610 ZYAX2 27 H 71 l l l l 118 53.25 90 PCT 8 P2 VS2 -.67 TEH TEC.610 SBAY2 22 C 17 l l l l 120 53.52 101 PCT 15 P2 VS2 -.69 TEH TEC.610 SBAY2 22 C 18 l l 120 53.32 105 PCT 10 P2 VS3 1.08 TEH TEC.610 SBAY2 22 C 18 l l l l 124 53.25 20 PCT 9 P2 05H.93 TEH TEC.610 SBAY2 22 C 20 l l l l 99 54.26 106 PCT 10 P2 VS2 -.93 TEH TEC.610 SBAY2 17 C 81 l l l l 101 54.32 98 PCT 12 P2 VS4 -.72 TEH TEC.610 SBAY2 17 C 82 l l l l 105 54.47 114 PCT 15 P2 VS3 -1.05 TEH TEC.610 SBAY2 17 C 84 l l l l 109 54.62 114 PCT 17 P2 VS4 1.25 TEH TEC.610 SBAY2 14 C 261 l l l
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
l ROW COL VOLTS DEG IND PER CRLEN CHN LOCN INCH1 INCH2 BEGT ENDT PDIA PTYPE CAL L IDX UTIL1 UTIL2l
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
8 ST Max
SG - 32 Calls of Interest Palo Verde 3 U3R20 PVNGS3 20180401 04/20/2018 13:40:22
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
l ROW COL VOLTS DEG IND PER CRLEN CHN LOCN INCH1 INCH2 BEGT ENDT PDIA PTYPE CAL L IDX UTIL1 UTIL2l
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
l 64 55.32 72 PCT 12 P2 VS3 1.05 TEH TEC.610 SBAY2 17 C 111 l l l l 98 55.26 74 PCT 10 P2 BW1 -1.08 TEH TEC.610 SBAY2 17 C 94 l l l l 118 55.53 115 PCT 16 P2 VS2 -.69 TEH TEC.610 SBAY2 21 C 39 l l 118 55.47 105 PCT 15 P2 VS3 1.10 TEH TEC.610 SBAY2 21 C 39 l l l l 120 55.33 94 PCT 12 P2 VS3 -.71 TEH TEC.610 SBAY2 21 C 40 l l l l 138 55.55 88 PCT 17 P2 VS1.80 TEH TEC.610 SBAY2 21 C 47 l l 138 55.26 113 PCT 10 P2 VS5 -.74 TEH TEC.610 SBAY2 21 C 47 l l l l 140 55.62 112 PCT 18 P2 VS1.87 TEH TEC.610 SBAY2 21 C 48 l l 140 55.33 93 PCT 12 P2 VS3.95 TEH TEC.610 SBAY2 21 C 48 l l l l 142 55.32 87 PCT 12 P2 VS3.78 TEH TEC.610 SBAY2 21 C 49 l l l l 144 55.48 109 PCT 15 P2 BW1 -.88 TEH TEC.610 SBAY2 21 C 50 l l l l 103 56.42 124 PCT 13 P2 VS3.83 TEH TEC.610 SBAY2 18 C 80 l l l l 117 56 1.08 110 PCT 25 P2 VS2 -.85 TEH TEC.610 SBAY2 21 C 65 l l 117 56.27 107 PCT 10 P2 VS3 -1.06 TEH TEC.610 SBAY2 21 C 65 l l 117 56 2.20 84 WAR.46 P15 VS2 -.80 VS3 TEH.610 ZYAX2 27 H 70 l l l l 139 56.24 117 PCT 9 P2 VS3.79 TEH TEC.610 SBAY2 21 C 54 l l l l 120 57.52 102 PCT 15 P2 VS2 -.76 TEH TEC.610 SBAY2 22 C 43 l l 120 57.32 116 PCT 10 P2 VS3 1.03 TEH TEC.610 SBAY2 22 C 43 l l l l 71 58.28 86 PCT 11 P2 BW1 -.36 TEH TEC.610 SBAY2 17 C 124 l l l l 95 58.33 94 PCT 12 P2 VS2 -.62 TEH TEC.610 SBAY2 17 C 136 l l l l 101 58.42 123 PCT 14 P2 VS3.68 TEH TEC.610 SBAY2 17 C 139 l l l l 105 58.26 130 PCT 10 P2 VS3 -1.09 TEH TEC.610 SBAY2 17 C 141 l l l l 96 59.48 130 PCT 16 P2 10H.87 TEH TEC.610 SBAY2 17 C 155 l l l l 98 59.38 128 PCT 13 P2 10H.80 TEH TEC.610 SBAY2 17 C 154 l l l l 118 59.27 104 PCT 10 P2 VS3 -.64 TEH TEC.610 SBAY2 21 C 66 l l l
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
l ROW COL VOLTS DEG IND PER CRLEN CHN LOCN INCH1 INCH2 BEGT ENDT PDIA PTYPE CAL L IDX UTIL1 UTIL2l
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
9 ST Max
SG - 32 Calls of Interest Palo Verde 3 U3R20 PVNGS3 20180401 04/20/2018 13:40:22
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
l ROW COL VOLTS DEG IND PER CRLEN CHN LOCN INCH1 INCH2 BEGT ENDT PDIA PTYPE CAL L IDX UTIL1 UTIL2l
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
l 120 59.25 51 PCT 10 P2 VS4.93 TEH TEC.610 SBAY2 21 C 67 l l l l 128 59.67 118 PCT 19 P2 VS3.98 TEH TEC.610 SBAY2 21 C 71 l l l l 12 61.31 66 PCT 10 P2 06H.56 TEH TEC.610 SBAY2 11 C 110 l l l l 40 61.31 56 PCT 10 P2 BW2 1.20 TEH TEC.610 SBAY2 11 C 96 l l l l 46 61.30 117 PCT 10 P2 BW1 -.75 TEH TEC.610 SBAY2 11 C 93 l l l l 94 61.43 126 PCT 13 P2 10H.75 TEH TEC.610 SBAY2 18 C 150 l l l l 98 61.34 136 PCT 11 P2 10H.79 TEH TEC.610 SBAY2 18 C 148 l l l l 106 61.38 106 PCT 12 P2 VS3 1.08 TEH TEC.610 SBAY2 18 C 144 l l l l 112 61.33 110 PCT 11 P2 VS2 -.77 TEH TEC.610 SBAY2 18 C 141 l l l l 118 61.50 93 PCT 14 P2 VS3 -.93 TEH TEC.610 SBAY2 22 C 72 l l l l 128 61.28 104 PCT 9 P2 VS1 -.77 TEH TEC.610 SBAY2 22 C 77 l l l l 41 62.38 122 PCT 12 P2 BW1 -.92 TEH TEC.610 SBAY2 12 C 130 l l l l 117 62.34 110 PCT 12 P2 VS3 -1.01 TEH TEC.610 SBAY2 17 C 205 l l l l 127 62.35 139 PCT 11 P2 VS1.46 TEH TEC.610 SBAY2 22 C 99 l l l l 157 62.25 89 PCT 10 P2 VS2 -.99 TEH TEC.610 SBAY2 19 C 128 l l l l 96 63.35 89 PCT 13 P2 10H.81 TEH TEC.610 SBAY2 17 C 217 l l l l 104 63.29 104 PCT 11 P2 BW2 -1.31 TEH TEC.610 SBAY2 17 C 213 l l l l 142 63.30 80 PCT 11 P2 VS3 1.00 TEH TEC.610 SBAY2 21 C 109 l l l l 158 63.26 132 PCT 10 P2 08H.83 TEH TEC.610 SBAY2 19 C 129 l l l l 41 64.29 139 PCT 10 P2 BW1 -1.35 TEH TEC.610 SBAY2 11 C 126 l l l l 107 64.30 127 PCT 10 P2 VS3.77 TEH TEC.610 SBAY2 18 C 200 l l l l 129 64.31 104 PCT 10 P2 VS1 -.77 TEH TEC.610 SBAY2 22 C 177 l l 129 64.44 83 PCT 13 P2 VS2 -.79 TEH TEC.610 SBAY2 22 C 177 l
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
l ROW COL VOLTS DEG IND PER CRLEN CHN LOCN INCH1 INCH2 BEGT ENDT PDIA PTYPE CAL L IDX UTIL1 UTIL2l
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
10 ST Max
SG - 32 Calls of Interest Palo Verde 3 U3R20 PVNGS3 20180401 04/20/2018 13:40:22
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
l ROW COL VOLTS DEG IND PER CRLEN CHN LOCN INCH1 INCH2 BEGT ENDT PDIA PTYPE CAL L IDX UTIL1 UTIL2l
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
l 129 64.54 120 PCT 15 P2 VS3.62 TEH TEC.610 SBAY2 22 C 177 l l 129 64 1.05 98 PCT 23 P2 VS4 -.69 TEH TEC.610 SBAY2 22 C 177 l l 129 64 1.79 282 WAR.23 P6 VS3.49 VS3 TEC.610 ZYAX2 228 C 8 l l 129 64 2.47 106 WAR.66 P5 VS4 -.69 VS3 TEC.610 ZYAX2 228 C 8 l l l l 8 65.14 111 PCT 8 P2 06H.77 TEH TEC.610 SBAY2 26 C 172 l l l l 24 65.43 78 PCT 13 P2 VS3.92 TEH TEC.610 SBAY2 11 C 148 l l l l 94 65.97 119 PCT 22 P2 VS3.89 TEH TEC.610 SBAY2 18 C 216 l l 94 65 2.31 303 WAR.50 P8 VS3.88 VS3 TEH.610 ZYAX2 27 H 69 l l l l 114 65.23 112 PCT 8 P2 05H.93 TEH TEC.610 SBAY2 18 C 206 l l l l 156 65.16 123 PCT 9 P2 11H -.20 TEH TEC.610 SBAY2 20 C 123 l l 156 65 NDF 59 FDP.99 01C TEC.610 ZYAX2 227 C 22 l l l l 37 66.34 95 PCT 11 P2 VS3 -.83 TEH TEC.610 SBAY2 12 C 174 l l l l 51 66.32 73 PCT 11 P2 09H.87 TEH TEC.610 SBAY2 12 C 181 l l l l 65 66.34 114 PCT 12 P2 BW1 -1.25 TEH TEC.610 SBAY2 17 C 237 l l l l 83 66.27 122 PCT 10 P2 09H.77 TEH TEC.610 SBAY2 17 C 246 l l l l 117 66.31 119 PCT 12 P2 VS2 -1.08 TEH TEC.610 SBAY2 17 C 263 l l l l 129 66.26 90 PCT 10 P2 VS2 -.83 TEH TEC.610 SBAY2 21 C 159 l l l l 10 67.43 85 PCT 13 P2 BW1 -.82 TEH TEC.610 SBAY2 26 C 174 l l l l 100 67.36 117 PCT 13 P2 10H.80 TEH TEC.610 SBAY2 17 C 273 l l l l 124 67.20 141 PCT 7 P2 VS1.80 TEH TEC.610 SBAY2 22 C 186 l l l l 146 67.34 121 PCT 11 P2 VS3 -.80 TEH TEC.610 SBAY2 22 C 198 l l l l 156 67.37 79 PCT 11 P2 VS5 -.76 TEH TEC.610 SBAY2 20 C 132 l l l l 53 68.40 113 PCT 12 P2 VS3.80 TEH TEC.610 SBAY2 11 C 176 l l l l 85 68.37 123 PCT 12 P2 VS2 -.62 TEH TEC.610 SBAY2 18 C 251 l l l l 117 68.33 134 PCT 10 P2 VS2 -1.09 TEH TEC.610 SBAY2 22 C 216 l
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
l ROW COL VOLTS DEG IND PER CRLEN CHN LOCN INCH1 INCH2 BEGT ENDT PDIA PTYPE CAL L IDX UTIL1 UTIL2l
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
11 ST Max
SG - 32 Calls of Interest Palo Verde 3 U3R20 PVNGS3 20180401 04/20/2018 13:40:22
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
l ROW COL VOLTS DEG IND PER CRLEN CHN LOCN INCH1 INCH2 BEGT ENDT PDIA PTYPE CAL L IDX UTIL1 UTIL2l
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
l l l 8 69.37 33 PCT 13 P2 BW1 -.57 TEH TEC.610 SBAY2 25 C 166 l l 8 69.26 25 PCT 10 P2 BW1 1.05 TEH TEC.610 SBAY2 25 C 166 l l l l 132 69.26 117 PCT 10 P2 VS1 -.67 TEH TEC.610 SBAY2 21 C 172 l l 132 69.17 130 PCT 7 P2 VS5.68 TEH TEC.610 SBAY2 21 C 172 l l l l 138 69.20 139 PCT 8 P2 VS1 -.45 TEH TEC.610 SBAY2 21 C 175 l l l l 162 69.29 124 PCT 10 P2 10H.61 TEH TEC.610 SBAY2 19 C 142 l l l l 111 70.60 113 PCT 18 P2 VS2 -.78 TEH TEC.610 SBAY2 17 C 322 l l 111 70.68 115 PCT 20 P2 VS3.92 TEH TEC.610 SBAY2 17 C 322 l l 111 70 1.95 134 WAR.53 P7 VS2 -.78 VS3 TEH.610 ZYAX2 27 H 68 l l 111 70 1.16 137 WAR.35 P32 VS3.79 VS3 TEH.610 ZYAX2 27 H 68 l l l l 125 70.36 104 PCT 13 P2 VS3 -.72 TEH TEC.610 SBAY2 21 C 195 l l 125 70.22 66 PCT 9 P2 VS4 -.88 TEH TEC.610 SBAY2 21 C 195 l l l l 131 70.26 81 PCT 10 P2 VS2 -.87 TEH TEC.610 SBAY2 21 C 192 l l l l 145 70.25 80 PCT 10 P2 VS1 -.85 TEH TEC.610 SBAY2 21 C 185 l l l l 157 70.34 115 PCT 11 P2 BW2.79 TEH TEC.610 SBAY2 22 C 129 l l l l 159 70.30 108 PCT 11 P2 VS1 -.63 TEH TEC.610 SBAY2 23 C 130 l l 159 70.27 77 PCT 10 P2 VS2 -.87 TEH TEC.610 SBAY2 23 C 130 l l 159 70.57 124 PCT 17 P2 BW2.74 TEH TEC.610 SBAY2 23 C 130 l l l l 161 70.37 127 PCT 13 P2 BW2.81 TEH TEC.610 SBAY2 21 C 119 l l l l 84 71.26 115 PCT 10 P2 09H.77 TEH TEC.610 SBAY2 17 C 342 l l l l 96 71.26 128 PCT 10 P2 10H.75 TEH TEC.610 SBAY2 17 C 336 l l l l 114 71.22 114 PCT 9 P2 VS2 -.82 TEH TEC.610 SBAY2 17 C 327 l l l l 120 71.25 68 PCT 8 P2 VS3.95 TEH TEC.610 SBAY2 22 C 217 l l l l 124 71.18 148 PCT 6 P2 VS1.86 TEH TEC.610 SBAY2 22 C 219 l l l l 128 71.23 63 PCT 8 P2 VS1 -.81 TEH TEC.610 SBAY2 22 C 221 l l l l 130 71.31 123 PCT 10 P2 VS1.80 TEH TEC.610 SBAY2 22 C 222 l
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
l ROW COL VOLTS DEG IND PER CRLEN CHN LOCN INCH1 INCH2 BEGT ENDT PDIA PTYPE CAL L IDX UTIL1 UTIL2l
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
12 ST Max
SG - 32 Calls of Interest Palo Verde 3 U3R20 PVNGS3 20180401 04/20/2018 13:40:22
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
l ROW COL VOLTS DEG IND PER CRLEN CHN LOCN INCH1 INCH2 BEGT ENDT PDIA PTYPE CAL L IDX UTIL1 UTIL2l
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
l l l 45 72.81 123 PCT 20 P2 08H.68 TEH TEC.610 SBAY2 11 C 215 l l 45 72 1.65 104 WAR.37 P26 08H.43 08H TEH.610 ZYAX2 27 H 52 l l l l 111 72.42 116 PCT 13 P2 VS2 -.70 TEH TEC.610 SBAY2 18 C 324 l l l l 161 72.42 42 PCT 14 P2 BW2 -.78 TEH TEC.610 SBAY2 21 C 129 l l l l 124 73.45 83 PCT 15 P2 VS3 1.04 TEH TEC.610 SBAY2 21 C 202 l l l l 134 73.27 52 PCT 10 P2 BW2 -.86 TEH TEC.610 SBAY2 21 C 207 l l l l 158 73.32 108 PCT 10 P2 VS5 -.82 TEH TEC.610 SBAY2 22 C 140 l l l l 164 73.16 120 PCT 7 P2 10H.78 TEH TEC.610 SBAY2 21 C 122 l l l l 11 74.45 104 PCT 14 P2 08C.77 TEH TEC.610 SBAY2 11 C 241 l l l l 19 74.32 123 PCT 10 P2 BW1 -.92 TEH TEC.610 SBAY2 11 C 250 l l l l 33 74.32 138 PCT 10 P2 VS3.80 TEC TEH.610 SBAY2 2 H 40 l l l l 47 74.32 129 PCT 10 P2 VS3 -.94 TEC TEH.610 SBAY2 2 H 33 l l l l 103 74.41 91 PCT 12 P2 05H.80 TEC TEH.610 SBAY2 5 H 137 l l l l 109 74.51 98 PCT 16 P2 VS4.96 TEH TEC.610 SBAY2 19 C 9 l l l l 125 74.22 41 PCT 8 P2 VS1 -.94 TEH TEC.610 SBAY2 23 C 20 l l 125 74.36 52 PCT 12 P2 VS2 -.72 TEH TEC.610 SBAY2 23 C 20 l l l l 129 74.28 90 PCT 10 P2 VS1 -.82 TEH TEC.610 SBAY2 23 C 18 l l 129 74.13 38 PCT 5 P2 VS3.82 TEH TEC.610 SBAY2 23 C 18 l l l l 147 74.29 85 PCT 10 P2 VS3.62 TEH TEC.610 SBAY2 23 C 9 l l l l 149 74.36 112 PCT 12 P2 VS3.60 TEH TEC.610 SBAY2 23 C 8 l l l l 157 74.23 106 PCT 9 P2 VS1.73 TEH TEC.610 SBAY2 23 C 5 l l 157 74.37 91 PCT 12 P2 VS3.62 TEH TEC.610 SBAY2 23 C 5 l l l l 18 75.31 92 PCT 10 P2 BW1.98 TEH TEC.610 SBAY2 11 C 245 l l l l 46 75.30 142 PCT 10 P2 VS3 1.02 TEC TEH.610 SBAY2 2 H 56 l
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
l ROW COL VOLTS DEG IND PER CRLEN CHN LOCN INCH1 INCH2 BEGT ENDT PDIA PTYPE CAL L IDX UTIL1 UTIL2l
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
13 ST Max
SG - 32 Calls of Interest Palo Verde 3 U3R20 PVNGS3 20180401 04/20/2018 13:40:22
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
l ROW COL VOLTS DEG IND PER CRLEN CHN LOCN INCH1 INCH2 BEGT ENDT PDIA PTYPE CAL L IDX UTIL1 UTIL2l
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
l l l 50 75.78 133 PCT 19 P2 08H.60 TEC TEH.610 SBAY2 2 H 58 l l 50 75 1.24 93 WAR.25 P18 08H.66 09H TEH.610 ZYAX2 27 H 44 l l l l 120 75.74 102 PCT 20 P2 VS2 -.73 TEH TEC.610 SBAY2 24 C 24 l l 120 75 2.27 125 WAR.44 P31 VS2 -.82 VS3 TEH.610 ZYAX2 27 H 66 l l l l 134 75.34 93 PCT 11 P2 VS1 -.76 TEH TEC.610 SBAY2 24 C 31 l l l l 164 75.42 133 PCT 14 P2 10H.76 TEH TEC.610 SBAY2 21 C 126 l l 164 75.62 68 PCT 18 P2 BW2 -.91 TEH TEC.610 SBAY2 21 C 126 l l 164 75 1.04 104 PCT 25 P2 BW2.81 TEH TEC.610 SBAY2 21 C 126 l l 164 75 1.33 105 WAR.34 P24 BW2 -.94 VS3 TEC.610 ZYAX2 228 C 23 l l 164 75 2.22 101 WAR.38 P9 BW2.81 VS3 TEC.610 ZYAX2 228 C 23 l l l l 37 76.33 140 PCT 11 P2 BW1 -1.22 TEC TEH.610 SBAY2 1 H 36 l l l l 45 76.45 141 PCT 13 P2 BW2.82 TEC TEH.610 SBAY2 1 H 32 l l l l 51 76.36 122 PCT 11 P2 VS3.99 TEC TEH.610 SBAY2 1 H 29 l l l l 53 76.29 118 PCT 10 P2 VS3.85 TEC TEH.610 SBAY2 1 H 28 l l l l 57 76.84 103 PCT 20 P2 09H.75 TEC TEH.610 SBAY2 1 H 26 l l 57 76 1.40 112 WAR.26 P9 09H.61 09H TEH.610 ZYAX2 27 H 43 l l l l 105 76 1.62 118 PCT 28 P2 VS3.66 TEC TEH.610 SBAY2 6 H 128 l l 105 76 2.90 96 WAR.49 P24 VS3.55 VS3 TEH.610 ZYAX2 27 H 67 l l l l 117 76.66 117 PCT 18 P2 VS3 -1.15 TEH TEC.610 SBAY2 24 C 61 l l l l 121 76.63 119 PCT 18 P2 VS3 -.82 TEH TEC.610 SBAY2 24 C 59 l l l l 135 76.21 82 PCT 8 P2 VS1 -.79 TEH TEC.610 SBAY2 24 C 52 l l l l 165 76.36 137 PCT 13 P2 10H.66 TEH TEC.610 SBAY2 21 C 125 l l l l 34 77.32 72 PCT 10 P2 VS3.88 TEC TEH.610 SBAY2 1 H 49 l l l l 48 77.36 123 PCT 11 P2 09C.16 TEC TEH.610 SBAY2 1 H 56 l l l l 82 77.41 137 PCT 12 P2 09H.85 TEC TEH.610 SBAY2 6 H 141 l l l l 88 77.48 133 PCT 13 P2 VS3.82 TEC TEH.610 SBAY2 6 H 138 l
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
l ROW COL VOLTS DEG IND PER CRLEN CHN LOCN INCH1 INCH2 BEGT ENDT PDIA PTYPE CAL L IDX UTIL1 UTIL2l
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
14 ST Max
SG - 32 Calls of Interest Palo Verde 3 U3R20 PVNGS3 20180401 04/20/2018 13:40:22
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
l ROW COL VOLTS DEG IND PER CRLEN CHN LOCN INCH1 INCH2 BEGT ENDT PDIA PTYPE CAL L IDX UTIL1 UTIL2l
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
l l l 112 77.32 97 PCT 10 P2 VS3 1.05 TEH TEC.610 SBAY2 20 C 11 l l l l 116 77.37 34 PCT 12 P2 VS2.89 TEH TEC.610 SBAY2 23 C 24 l l l l 120 77.26 51 PCT 10 P2 VS2 -.77 TEH TEC.610 SBAY2 23 C 25 l l 120 77.32 82 PCT 11 P2 VS3.88 TEH TEC.610 SBAY2 23 C 25 l l l l 126 77.53 132 PCT 16 P2 VS3 1.16 TEH TEC.610 SBAY2 23 C 28 l l l l 130 77.33 51 PCT 11 P2 VS4 -.84 TEH TEC.610 SBAY2 23 C 30 l l l l 138 77.29 110 PCT 10 P2 VS4 -.72 TEH TEC.610 SBAY2 23 C 34 l l l l 144 77.40 77 PCT 13 P2 VS4 -.73 TEH TEC.610 SBAY2 23 C 37 l l l l 166 77.28 120 PCT 11 P2 10H.76 TEH TEC.610 SBAY2 21 C 124 l l l l 27 78.53 114 PCT 15 P2 08H.77 TEC TEH.610 SBAY2 1 H 89 l l 27 78.92 105 PCT 21 P2 BW1.47 TEC TEH.610 SBAY2 1 H 89 l l 27 78.73 101 PCT 18 P2 BW2.57 TEC TEH.610 SBAY2 1 H 89 l l 27 78 2.65 153 WAR.61 P3 BW1.61 VS3 TEH.610 ZYAX2 27 H 37 l l l l 49 78.31 154 PCT 11 P2 09H -.16 TEC TEH.610 SBAY2 2 H 75 l l l l 51 78.41 133 PCT 12 P2 08H.65 TEC TEH.610 SBAY2 2 H 74 l l l l 117 78.32 112 PCT 11 P2 VS4 -.77 TEH TEC.610 SBAY2 23 C 64 l l l l 149 78.48 108 PCT 15 P2 VS3.62 TEH TEC.610 SBAY2 23 C 48 l l l l 165 78.26 145 PCT 10 P2 10H.73 TEH TEC.610 SBAY2 21 C 133 l l l l 34 79.20 135 PCT 11 P2 08H.73 TEC TEH.610 SBAY2 2 H 85 l l l l 72 79.53 135 PCT 15 P2 09H.83 TEC TEH.610 SBAY2 5 H 191 l l l l 104 79.43 141 PCT 13 P2 VS2.77 TEC TEH.610 SBAY2 5 H 175 l l l l 118 79.29 77 PCT 10 P2 VS3 -.35 TEH TEC.610 SBAY2 24 C 68 l l l l 158 79.30 58 PCT 11 P2 VS1.87 TEH TEC.610 SBAY2 24 C 88 l l l l 164 79.33 107 PCT 12 P2 VS5 1.01 TEH TEC.610 SBAY2 21 C 140 l
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
l ROW COL VOLTS DEG IND PER CRLEN CHN LOCN INCH1 INCH2 BEGT ENDT PDIA PTYPE CAL L IDX UTIL1 UTIL2l
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
15 ST Max
SG - 32 Calls of Interest Palo Verde 3 U3R20 PVNGS3 20180401 04/20/2018 13:40:22
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
l ROW COL VOLTS DEG IND PER CRLEN CHN LOCN INCH1 INCH2 BEGT ENDT PDIA PTYPE CAL L IDX UTIL1 UTIL2l
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
l l l 166 79.44 99 PCT 14 P2 VS5.94 TEH TEC.610 SBAY2 21 C 132 l l l l 31 80.59 119 PCT 16 P2 BW1 -1.26 TEC TEH.610 SBAY2 1 H 87 l l l l 33 80.46 144 PCT 14 P2 06H.78 TEC TEH.610 SBAY2 1 H 86 l l l l 37 80.74 117 PCT 18 P2 BW1 -.80 TEC TEH.610 SBAY2 1 H 84 l l l l 39 80.47 140 PCT 14 P2 BW1 -1.33 TEC TEH.610 SBAY2 1 H 83 l l l l 41 80.34 150 PCT 11 P2 BW1 -1.31 TEC TEH.610 SBAY2 1 H 82 l l l l 45 80.32 106 PCT 10 P2 BW2.43 TEC TEH.610 SBAY2 1 H 80 l l l l 47 80.43 67 PCT 13 P2 BW2.99 TEC TEH.610 SBAY2 1 H 79 l l l l 49 80.41 51 PCT 12 P2 BW2 -.66 TEC TEH.610 SBAY2 1 H 78 l l l l 55 80.32 26 PCT 10 P2 BW2 1.21 TEC TEH.610 SBAY2 1 H 75 l l l l 57 80.30 69 PCT 10 P2 BW2 1.57 TEC TEH.610 SBAY2 1 H 74 l l l l 71 80 1.02 129 PCT 22 P2 VS2 -.76 TEC TEH.610 SBAY2 6 H 152 l l 71 80 2.47 314 WAR.67 P6 VS2 -.76 VS3 TEH.610 ZYAX2 27 H 38 l l l l 107 80.36 126 PCT 11 P2 VS4.92 TEC TEH.610 SBAY2 22 H 164 l l l l 109 80.48 103 PCT 14 P2 VS3 -.88 TEC TEH.610 SBAY2 22 H 163 l l l l 133 80.31 135 PCT 10 P2 11C -.96 TEC TEH.610 SBAY2 22 H 151 l l l l 167 80.21 131 PCT 9 P2 VS3.55 TEH TEC.610 SBAY2 21 C 131 l l l l 34 81.31 124 PCT 10 P2 08C.70 TEC TEH.610 SBAY2 1 H 94 l l l l 36 81.41 99 PCT 13 P2 06H.80 TEC TEH.610 SBAY2 1 H 103 l l l l 40 81.34 143 PCT 11 P2 08H.66 TEC TEH.610 SBAY2 1 H 104 l l l l 50 81.29 91 PCT 10 P2 08H -.20 TEC TEH.610 SBAY2 1 H 109 l l l l 116 81.46 73 PCT 14 P2 VS2.91 TEH TEC.610 SBAY2 23 C 74 l l 116 81.49 56 PCT 15 P2 VS3 1.00 TEH TEC.610 SBAY2 23 C 74 l
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
l ROW COL VOLTS DEG IND PER CRLEN CHN LOCN INCH1 INCH2 BEGT ENDT PDIA PTYPE CAL L IDX UTIL1 UTIL2l
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
16 ST Max
SG - 32 Calls of Interest Palo Verde 3 U3R20 PVNGS3 20180401 04/20/2018 13:40:22
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
l ROW COL VOLTS DEG IND PER CRLEN CHN LOCN INCH1 INCH2 BEGT ENDT PDIA PTYPE CAL L IDX UTIL1 UTIL2l
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
l l l 118 81.32 88 PCT 11 P2 VS3 -.86 TEH TEC.610 SBAY2 23 C 75 l l l l 124 81.33 81 PCT 11 P2 VS1 -.73 TEH TEC.610 SBAY2 23 C 78 l l 124 81.23 38 PCT 9 P2 VS1 1.01 TEH TEC.610 SBAY2 23 C 78 l l l l 132 81.36 79 PCT 12 P2 VS1 -.71 TEH TEC.610 SBAY2 23 C 82 l l l l 168 81.30 65 PCT 11 P2 BW2.38 TEH TEC.610 SBAY2 21 C 130 l l l l 35 82.37 131 PCT 11 P2 BW1.30 TEC TEH.610 SBAY2 1 H 95 l l l l 45 82.32 88 PCT 10 P2 BW2 -1.26 TEC TEH.610 SBAY2 2 H 124 l l l l 47 82.32 150 PCT 10 P2 BW2.51 TEC TEH.610 SBAY2 2 H 123 l l l l 81 82.31 101 PCT 11 P2 VS3 -1.06 TEC TEH.610 SBAY2 5 H 199 l l l l 125 82.36 112 PCT 12 P2 VS3 -.72 TEH TEC.610 SBAY2 23 C 116 l l l l 153 82.29 132 PCT 10 P2 VS2 -1.23 TEH TEC.610 SBAY2 23 C 102 l l l l 36 83.44 115 PCT 13 P2 VS3 -.90 TEC TEH.610 SBAY2 1 H 96 l l l l 40 83.44 125 PCT 13 P2 08H.73 TEC TEH.610 SBAY2 2 H 90 l l l l 44 83.37 143 PCT 11 P2 08H.84 TEC TEH.610 SBAY2 2 H 130 l l l l 102 83 1.17 128 PCT 24 P2 VS3.77 TEC TEH.610 SBAY2 5 H 212 l l 102 83 1.74 306 WAR.65 P8 VS3.89 VS3 TEH.610 ZYAX2 27 H 62 l l l l 116 83.46 108 PCT 13 P2 VS3.73 TEC TEH.610 SBAY2 23 H 155 l l 116 83.39 128 PCT 12 P2 VS4.74 TEC TEH.610 SBAY2 23 H 155 l l l l 164 83.26 117 PCT 8 P2 VS1.88 TEC TEH.610 SBAY2 23 H 179 l l l l 166 83.66 119 PCT 17 P2 BW2 -.90 TEC TEH.610 SBAY2 23 H 180 l l l l 168 83.40 119 PCT 12 P2 VS4.62 TEC TEH.610 SBAY2 23 H 181 l l 168 83.34 105 PCT 11 P2 BW2 -.97 TEC TEH.610 SBAY2 23 H 181 l l l l 37 84 3.31 66 LNI P5 TSH -.16 TEC TEH.610 SBAY2 1 H 97 SR l l 37 84.50 127 PCT 14 P2 BW1.30 TEC TEH.610 SBAY2 1 H 97 l l 37 84.33 120 PCT 11 P2 08C.82 TEC TEH.610 SBAY2 1 H 97 l
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
l ROW COL VOLTS DEG IND PER CRLEN CHN LOCN INCH1 INCH2 BEGT ENDT PDIA PTYPE CAL L IDX UTIL1 UTIL2l
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
17 ST Max
SG - 32 Calls of Interest Palo Verde 3 U3R20 PVNGS3 20180401 04/20/2018 13:40:22
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
l ROW COL VOLTS DEG IND PER CRLEN CHN LOCN INCH1 INCH2 BEGT ENDT PDIA PTYPE CAL L IDX UTIL1 UTIL2l
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
l 37 84 NDF 202 TSH -.16 VS3 TEH.610 ZYAX2 27 H 36 l l l l 39 84.38 59 PCT 12 P2 BW1.40 TEC TEH.610 SBAY2 1 H 130 l l l l 43 84.81 116 PCT 19 P2 BW2 -1.19 TEC TEH.610 SBAY2 1 H 129 l l l l 51 84.41 104 PCT 12 P2 BW1.26 TEC TEH.610 SBAY2 1 H 125 l l l l 61 84.37 38 PCT 11 P2 VS3 -.65 TEC TEH.610 SBAY2 1 H 120 l l l l 63 84.39 125 PCT 12 P2 VS4.79 TEC TEH.610 SBAY2 1 H 119 l l l l 65 84.68 121 PCT 17 P2 09H.80 TEC TEH.610 SBAY2 1 H 118 l l l l 107 84.30 92 PCT 10 P2 09H.66 TEC TEH.610 SBAY2 22 H 148 l l l l 109 84.39 105 PCT 12 P2 VS3 -1.00 TEC TEH.610 SBAY2 22 H 147 l l l l 117 84.29 39 PCT 10 P2 BW1.42 TEC TEH.610 SBAY2 22 H 143 l l 117 84.42 128 PCT 13 P2 VS3 -1.06 TEC TEH.610 SBAY2 22 H 143 l l l l 121 84.31 137 PCT 10 P2 VS2 -.78 TEC TEH.610 SBAY2 22 H 141 l l l l 123 84.40 136 PCT 12 P2 10H.97 TEC TEH.610 SBAY2 22 H 140 l l l l 129 84.29 127 PCT 10 P2 VS2 -.88 TEC TEH.610 SBAY2 22 H 137 l l l l 143 84.29 149 PCT 10 P2 VS1.68 TEC TEH.610 SBAY2 22 H 130 l l l l 157 84.37 144 PCT 12 P2 VS1.70 TEC TEH.610 SBAY2 22 H 123 l l 157 84.46 136 PCT 14 P2 VS4.78 TEC TEH.610 SBAY2 22 H 123 l l l l 165 84.57 130 PCT 16 P2 VS5.74 TEC TEH.610 SBAY2 22 H 119 l l l l 44 85.37 121 PCT 12 P2 BW1.92 TEC TEH.610 SBAY2 1 H 132 l l l l 48 85.38 58 PCT 12 P2 BW2.76 TEC TEH.610 SBAY2 1 H 134 l l l l 104 85.47 122 PCT 13 P2 VS3.85 TEC TEH.610 SBAY2 6 H 211 l l l l 114 85.40 115 PCT 12 P2 VS3.73 TEC TEH.610 SBAY2 22 H 89 l l l l 118 85.59 111 PCT 16 P2 VS2 -.40 TEC TEH.610 SBAY2 22 H 91 l l l
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
l ROW COL VOLTS DEG IND PER CRLEN CHN LOCN INCH1 INCH2 BEGT ENDT PDIA PTYPE CAL L IDX UTIL1 UTIL2l
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
18 ST Max
SG - 32 Calls of Interest Palo Verde 3 U3R20 PVNGS3 20180401 04/20/2018 13:40:22
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
l ROW COL VOLTS DEG IND PER CRLEN CHN LOCN INCH1 INCH2 BEGT ENDT PDIA PTYPE CAL L IDX UTIL1 UTIL2l
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
l 120 85 1.18 122 PCT 24 P2 VS2.74 TEC TEH.610 SBAY2 22 H 92 l l 120 85.50 104 PCT 14 P2 VS4 -.91 TEC TEH.610 SBAY2 22 H 92 l l 120 85.75 119 PCT 19 P2 VS4.72 TEC TEH.610 SBAY2 22 H 92 l l 120 85 2.50 125 WAR.90 P31 VS2.74 VS3 TEH.610 ZYAX2 27 H 63 l l l l 124 85.33 83 PCT 11 P2 VS3.90 TEC TEH.610 SBAY2 22 H 94 l l l l 132 85.37 102 PCT 12 P2 VS1 -.70 TEC TEH.610 SBAY2 22 H 98 l l l l 154 85.31 107 PCT 10 P2 VS1.81 TEC TEH.610 SBAY2 22 H 109 l l l l 158 85.58 125 PCT 16 P2 VS1.77 TEC TEH.610 SBAY2 22 H 111 l l l l 39 86.88 124 PCT 20 P2 VS3.72 TEC TEH.610 SBAY2 1 H 99 l l 39 86.72 114 PCT 18 P2 BW2.40 TEC TEH.610 SBAY2 1 H 99 l l 39 86 1.47 93 WAR.40 P23 VS3.63 VS3 TEH.610 ZYAX2 27 H 35 l l l l 41 86.69 125 PCT 18 P2 VS3.76 TEC TEH.610 SBAY2 2 H 155 l l l l 51 86.41 136 PCT 12 P2 VS3.81 TEC TEH.610 SBAY2 2 H 151 l l l l 85 86.47 101 PCT 14 P2 BW1.82 TEC TEH.610 SBAY2 7 H 19 l l l l 87 86.55 57 PCT 16 P2 BW1.85 TEC TEH.610 SBAY2 7 H 20 l l l l 89 86.45 41 PCT 14 P2 BW1.67 TEC TEH.610 SBAY2 7 H 21 l l l l 119 86.28 118 PCT 9 P2 VS1 -.51 TEC TEH.610 SBAY2 23 H 142 l l l l 42 87.78 141 PCT 19 P2 BW1.80 TEC TEH.610 SBAY2 2 H 156 l l l l 52 87.44 110 PCT 13 P2 08H -.30 TEC TEH.610 SBAY2 2 H 159 l l l l 70 87.38 146 PCT 12 P2 VS2 -.37 TEC TEH.610 SBAY2 7 H 45 l l l l 94 87.33 126 PCT 11 P2 VS2 -.79 TEC TEH.610 SBAY2 7 H 34 l l l l 96 87.48 120 PCT 14 P2 VS3.70 TEC TEH.610 SBAY2 7 H 33 l l l l 120 87.61 116 PCT 16 P2 VS3.80 TEC TEH.610 SBAY2 23 H 94 l l l l 124 87.29 58 PCT 9 P2 VS3.96 TEC TEH.610 SBAY2 23 H 95 l l l l 41 88.94 109 PCT 21 P2 BW1 -.89 TEC TEH.610 SBAY2 5 H 117 l
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
l ROW COL VOLTS DEG IND PER CRLEN CHN LOCN INCH1 INCH2 BEGT ENDT PDIA PTYPE CAL L IDX UTIL1 UTIL2l
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
19 ST Max
SG - 32 Calls of Interest Palo Verde 3 U3R20 PVNGS3 20180401 04/20/2018 13:40:22
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
l ROW COL VOLTS DEG IND PER CRLEN CHN LOCN INCH1 INCH2 BEGT ENDT PDIA PTYPE CAL L IDX UTIL1 UTIL2l
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
l 41 88 1.76 294 WAR.33 P4 BW1 -.69 VS3 TEH.610 ZYAX2 27 H 34 l l l l 51 88.45 108 PCT 13 P2 BW2 -.25 TEC TEH.610 SBAY2 1 H 151 l l l l 53 88.40 102 PCT 12 P2 VS3 -.94 TEC TEH.610 SBAY2 1 H 150 l l l l 65 88.53 135 PCT 15 P2 09H.73 TEC TEH.610 SBAY2 1 H 144 l l l l 81 88.63 116 PCT 16 P2 VS3 -1.05 TEC TEH.610 SBAY2 8 H 16 l l l l 89 88.42 121 PCT 12 P2 VS3 -.70 TEC TEH.610 SBAY2 8 H 20 l l l l 115 88.29 102 PCT 10 P2 VS1 -1.05 TEC TEH.610 SBAY2 22 H 81 l l l l 125 88.34 42 PCT 11 P2 VS1.97 TEC TEH.610 SBAY2 22 H 76 l l l l 157 88.29 134 PCT 10 P2 VS5.81 TEC TEH.610 SBAY2 22 H 61 l l l l 42 89.41 122 PCT 13 P2 BW1 -.05 TEC TEH.610 SBAY2 1 H 100 l l 42 89 1.09 131 PCT 23 P2 BW1.87 TEC TEH.610 SBAY2 1 H 100 l l 42 89 1.66 296 WAR.37 P2 BW1.87 VS3 TEH.610 ZYAX2 27 H 33 l l l l 46 89.30 107 PCT 10 P2 BW2 1.00 TEC TEH.610 SBAY2 2 H 96 l l l l 48 89.41 76 PCT 13 P2 06H.80 TEC TEH.610 SBAY2 1 H 156 l l 48 89.56 109 PCT 15 P2 BW2.75 TEC TEH.610 SBAY2 1 H 156 l l l l 50 89.40 145 PCT 12 P2 08H.72 TEC TEH.610 SBAY2 1 H 157 l l 50 89.47 94 PCT 14 P2 BW2.73 TEC TEH.610 SBAY2 1 H 157 l l l l 68 89.30 88 PCT 10 P2 09H.73 TEC TEH.610 SBAY2 1 H 166 l l l l 88 89.49 131 PCT 14 P2 09H.80 TEC TEH.610 SBAY2 8 H 38 l l l l 94 89.50 84 PCT 14 P2 10H.68 TEC TEH.610 SBAY2 8 H 35 l l l l 96 89.43 139 PCT 12 P2 09H.69 TEC TEH.610 SBAY2 8 H 34 l l l l 114 89.37 132 PCT 12 P2 VS2.71 TEC TEH.610 SBAY2 22 H 26 l l l l 116 89.33 129 PCT 11 P2 VS4.80 TEC TEH.610 SBAY2 22 H 27 l l l l 118 89.41 98 PCT 13 P2 VS2 -.32 TEC TEH.610 SBAY2 22 H 28 l l l
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
l ROW COL VOLTS DEG IND PER CRLEN CHN LOCN INCH1 INCH2 BEGT ENDT PDIA PTYPE CAL L IDX UTIL1 UTIL2l
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
20 ST Max
SG - 32 Calls of Interest Palo Verde 3 U3R20 PVNGS3 20180401 04/20/2018 13:40:22
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
l ROW COL VOLTS DEG IND PER CRLEN CHN LOCN INCH1 INCH2 BEGT ENDT PDIA PTYPE CAL L IDX UTIL1 UTIL2l
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
l 120 89.33 107 PCT 11 P2 VS2.78 TEC TEH.610 SBAY2 22 H 29 l l 120 89.79 106 PCT 19 P2 VS3.84 TEC TEH.610 SBAY2 22 H 29 l l l l 124 89.44 114 PCT 13 P2 VS3.89 TEC TEH.610 SBAY2 22 H 31 l l l l 130 89.32 115 PCT 10 P2 VS1.81 TEC TEH.610 SBAY2 22 H 34 l l l l 132 89.39 111 PCT 12 P2 VS1 -.67 TEC TEH.610 SBAY2 22 H 35 l l 132 89.31 97 PCT 10 P2 VS1.85 TEC TEH.610 SBAY2 22 H 35 l l l l 136 89.29 114 PCT 10 P2 VS1 -1.00 TEC TEH.610 SBAY2 22 H 37 l l l l 146 89.34 133 PCT 11 P2 VS1.75 TEC TEH.610 SBAY2 22 H 42 l l l l 156 89.35 102 PCT 11 P2 BW1 -1.57 TEC TEH.610 SBAY2 22 H 47 l l 156 89.48 137 PCT 14 P2 VS1.73 TEC TEH.610 SBAY2 22 H 47 l l l l 158 89.32 108 PCT 10 P2 VS1.91 TEC TEH.610 SBAY2 22 H 48 l l 158 89.32 112 PCT 10 P2 VS2 -.93 TEC TEH.610 SBAY2 22 H 48 l l l l 160 89.30 91 PCT 10 P2 VS1 -1.01 TEC TEH.610 SBAY2 22 H 49 l l l l 170 89.39 112 PCT 12 P2 BW1 -.86 TEC TEH.610 SBAY2 22 H 54 l l l l 43 90.96 130 PCT 21 P2 VS3 -.82 TEC TEH.610 SBAY2 1 H 101 l l 43 90 1.52 298 WAR.44 P6 VS3 -.82 VS3 TEH.610 ZYAX2 27 H 32 l l l l 47 90.40 118 PCT 12 P2 BW2.39 TEC TEH.610 SBAY2 4 H 15 l l l l 49 90.33 120 PCT 10 P2 BW1 -.93 TEC TEH.610 SBAY2 4 H 12 l l 49 90.30 73 PCT 10 P2 BW2 -1.21 TEC TEH.610 SBAY2 4 H 12 l l l l 51 90.32 54 PCT 10 P2 BW2 -.80 TEC TEH.610 SBAY2 4 H 11 l l l l 69 90.48 100 PCT 13 P2 VS3 -1.03 TEC TEH.610 SBAY2 8 H 48 l l l l 81 90.32 135 PCT 11 P2 VS3 -1.06 TEC TEH.610 SBAY2 7 H 55 l l l l 109 90.38 114 PCT 11 P2 VS3.24 TEC TEH.610 SBAY2 23 H 85 l l l l 113 90.60 98 PCT 16 P2 VS4.89 TEC TEH.610 SBAY2 23 H 83 l l l l 117 90.73 114 PCT 18 P2 VS3 -1.15 TEC TEH.610 SBAY2 23 H 81 l l l
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
l ROW COL VOLTS DEG IND PER CRLEN CHN LOCN INCH1 INCH2 BEGT ENDT PDIA PTYPE CAL L IDX UTIL1 UTIL2l
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
21 ST Max
SG - 32 Calls of Interest Palo Verde 3 U3R20 PVNGS3 20180401 04/20/2018 13:40:22
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
l ROW COL VOLTS DEG IND PER CRLEN CHN LOCN INCH1 INCH2 BEGT ENDT PDIA PTYPE CAL L IDX UTIL1 UTIL2l
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
l 157 90.48 140 PCT 13 P2 VS1.70 TEC TEH.610 SBAY2 23 H 62 l l l l 159 90.45 143 PCT 13 P2 VS3 -.89 TEC TEH.610 SBAY2 23 H 61 l l l l 44 91.45 101 PCT 13 P2 08H.76 TEC TEH.610 SBAY2 1 H 102 l l l l 48 91.48 84 PCT 14 P2 BW1 -.02 TEC TEH.610 SBAY2 4 H 14 l l 48 91.45 142 PCT 13 P2 VS3.95 TEC TEH.610 SBAY2 4 H 14 l l 48 91.46 95 PCT 13 P2 BW2.81 TEC TEH.610 SBAY2 4 H 14 l l l l 96 91.43 62 PCT 13 P2 10H.76 TEC TEH.610 SBAY2 7 H 71 l l l l 102 91.56 96 PCT 16 P2 VS3.89 TEC TEH.610 SBAY2 7 H 68 l l l l 104 91.52 140 PCT 15 P2 VS2.71 TEC TEH.610 SBAY2 7 H 67 l l 104 91.36 101 PCT 12 P2 VS4 -.93 TEC TEH.610 SBAY2 7 H 67 l l l l 110 91.72 111 PCT 18 P2 VS3.87 TEC TEH.610 SBAY2 23 H 25 l l l l 118 91.30 148 PCT 10 P2 VS3.71 TEC TEH.610 SBAY2 23 H 29 l l 118 91.33 148 PCT 10 P2 VS4 -.80 TEC TEH.610 SBAY2 23 H 29 l l l l 134 91.58 123 PCT 15 P2 11H 1.19 TEC TEH.610 SBAY2 23 H 37 l l l l 51 92.39 30 PCT 12 P2 BW1.84 TEC TEH.610 SBAY2 3 H 12 l l 51 92.45 60 PCT 14 P2 BW2 -.72 TEC TEH.610 SBAY2 3 H 12 l l l l 55 92.44 67 PCT 13 P2 BW2 -1.26 TEC TEH.610 SBAY2 3 H 10 l l l l 103 92.33 117 PCT 10 P2 VS2 -.99 TEC TEH.610 SBAY2 8 H 70 l l 103 92.54 110 PCT 14 P2 VS3.54 TEC TEH.610 SBAY2 8 H 70 l l l l 105 92.72 123 PCT 17 P2 VS2 -.79 TEC TEH.610 SBAY2 8 H 71 l l 105 92.60 106 PCT 15 P2 VS3 -.86 TEC TEH.610 SBAY2 8 H 71 l l l l 107 92.32 149 PCT 10 P2 VS2 -.78 TEC TEH.610 SBAY2 22 H 22 l l l l 113 92.45 104 PCT 13 P2 VS2 -.89 TEC TEH.610 SBAY2 22 H 19 l l 113 92.68 132 PCT 18 P2 VS4 -.82 TEC TEH.610 SBAY2 22 H 19 l l l l 117 92.38 103 PCT 12 P2 VS1 -.87 TEC TEH.610 SBAY2 22 H 17 l l l l 157 92.28 148 PCT 10 P2 VS5.81 TEC TEH.610 SBAY2 20 H 275 l l l
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
l ROW COL VOLTS DEG IND PER CRLEN CHN LOCN INCH1 INCH2 BEGT ENDT PDIA PTYPE CAL L IDX UTIL1 UTIL2l
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
22 ST Max
SG - 32 Calls of Interest Palo Verde 3 U3R20 PVNGS3 20180401 04/20/2018 13:40:22
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
l ROW COL VOLTS DEG IND PER CRLEN CHN LOCN INCH1 INCH2 BEGT ENDT PDIA PTYPE CAL L IDX UTIL1 UTIL2l
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
l 165 92.28 148 PCT 10 P2 VS4.75 TEC TEH.610 SBAY2 20 H 271 l l 165 92.31 142 PCT 11 P2 VS5.72 TEC TEH.610 SBAY2 20 H 271 l l l l 167 92.33 313 PCT 11 P2 VS4.90 TEC TEH.610 SBAY2 20 H 270 l l 167 92.31 310 PCT 11 P2 VS5.91 TEC TEH.610 SBAY2 20 H 270 l l l l 169 92.28 304 PCT 10 P2 VS4.98 TEC TEH.610 SBAY2 20 H 269 l l l l 48 93.70 98 PCT 18 P2 VS3 -.82 TEC TEH.610 SBAY2 3 H 23 l l 48 93.33 100 PCT 11 P2 VS3.90 TEC TEH.610 SBAY2 3 H 23 l l 48 93.96 105 PCT 22 P2 BW2 -.80 TEC TEH.610 SBAY2 3 H 23 l l 48 93.89 126 PCT 21 P2 BW2 -.12 TEC TEH.610 SBAY2 3 H 23 l l 48 93.76 93 PCT 19 P2 BW2.82 TEC TEH.610 SBAY2 3 H 23 l l 48 93 1.20 280 WAR.31 P12 BW2 -1.01 VS3 TEC.610 ZYAX2 227 C 48 l l 48 93.96 105 WAR.35 P12 BW2.09 VS3 TEC.610 ZYAX2 227 C 48 l l 48 93 1.02 110 WAR.44 P12 BW2.66 VS3 TEC.610 ZYAX2 227 C 48 l l l l 50 93.34 84 PCT 11 P2 BW1 -.88 TEC TEH.610 SBAY2 4 H 16 l l 50 93.42 132 PCT 12 P2 VS3 -.82 TEC TEH.610 SBAY2 4 H 16 l l l l 52 93.45 121 PCT 13 P2 VS3 -.89 TEC TEH.610 SBAY2 4 H 24 l l l l 96 93.43 115 PCT 12 P2 09H.74 TEC TEH.610 SBAY2 8 H 77 l l l l 102 93.48 130 PCT 13 P2 VS3.45 TEC TEH.610 SBAY2 8 H 74 l l l l 110 93.36 160 PCT 12 P2 VS2.65 TEC TEH.610 SBAY2 20 H 238 l l l l 118 93.67 93 PCT 18 P2 VS2.91 TEC TEH.610 SBAY2 20 H 242 l l 118 93.70 120 PCT 18 P2 VS3.74 TEC TEH.610 SBAY2 20 H 242 l l l l 130 93.28 156 PCT 10 P2 VS2.69 TEC TEH.610 SBAY2 20 H 248 l l l l 132 93.29 151 PCT 10 P2 VS5.79 TEC TEH.610 SBAY2 20 H 249 l l l l 134 93.28 162 PCT 10 P2 VS5.77 TEC TEH.610 SBAY2 20 H 250 l l l l 140 93.28 143 PCT 10 P2 VS5.69 TEC TEH.610 SBAY2 20 H 253 l l l l 152 93.32 121 PCT 11 P2 VS2.76 TEC TEH.610 SBAY2 20 H 259 l l l l 164 93.40 136 PCT 13 P2 VS1 -.88 TEC TEH.610 SBAY2 20 H 265 l l l l 168 93.30 120 PCT 10 P2 BW1 -.52 TEC TEH.610 SBAY2 20 H 267 l
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
l ROW COL VOLTS DEG IND PER CRLEN CHN LOCN INCH1 INCH2 BEGT ENDT PDIA PTYPE CAL L IDX UTIL1 UTIL2l
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
23 ST Max
SG - 32 Calls of Interest Palo Verde 3 U3R20 PVNGS3 20180401 04/20/2018 13:40:22
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
l ROW COL VOLTS DEG IND PER CRLEN CHN LOCN INCH1 INCH2 BEGT ENDT PDIA PTYPE CAL L IDX UTIL1 UTIL2l
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
l l l 47 94 1.26 114 PCT 25 P2 BW1 -.75 TEC TEH.610 SBAY2 3 H 14 l l 47 94.45 114 PCT 14 P2 BW1 -.28 TEC TEH.610 SBAY2 3 H 14 l l 47 94.30 56 PCT 10 P2 VS3 -1.10 TEC TEH.610 SBAY2 3 H 14 l l 47 94.40 127 PCT 12 P2 VS3.60 TEC TEH.610 SBAY2 3 H 14 l l 47 94 1.19 126 PCT 24 P2 BW2.84 TEC TEH.610 SBAY2 3 H 14 l l 47 94 TBP P2 BW1 -.75 TEC TEH.610 SBAY2 24 H 12 l l 47 94 1.82 276 WAR.53 P19 BW1 -.75 VS3 TEH.610 ZYAX2 27 H 27 l l 47 94 1.80 271 WAR.24 P12 BW2 1.29 VS3 TEC.610 ZYAX2 227 C 47 l l l l 49 94.88 119 PCT 21 P2 09H -1.65 TEC TEH.610 SBAY2 3 H 24 l l 49 94.31 114 PCT 10 P2 BW1 -.50 TEC TEH.610 SBAY2 3 H 24 l l 49 94 1.51 103 WAR.26 P25 09H -1.69 09H TEH.610 ZYAX2 27 H 26 l l l l 51 94.48 126 PCT 13 P2 BW1 -.83 TEC TEH.610 SBAY2 4 H 17 l l l l 77 94.32 100 PCT 11 P2 VS2.73 TEC TEH.610 SBAY2 7 H 86 l l l l 95 94.32 88 PCT 11 P2 VS4.87 TEC TEH.610 SBAY2 7 H 95 l l l l 99 94.37 117 PCT 12 P2 VS4 -.86 TEC TEH.610 SBAY2 7 H 97 l l l l 48 95.51 125 PCT 15 P2 BW1.50 TEC TEH.610 SBAY2 3 H 15 l l 48 95.97 109 PCT 22 P2 BW2.96 TEC TEH.610 SBAY2 3 H 15 l l 48 95 1.28 107 WAR.70 P12 BW2.66 VS3 TEC.610 ZYAX2 227 C 46 l l l l 74 95.42 131 PCT 13 P2 VS4.67 TEC TEH.610 SBAY2 7 H 115 l l l l 84 95.36 139 PCT 12 P2 VS3.72 TEC TEH.610 SBAY2 7 H 110 l l l l 94 95.88 108 PCT 21 P2 10H.75 TEC TEH.610 SBAY2 7 H 105 l l 94 95 1.44 108 WAR.33 P6 10H.76 10H TEH.610 ZYAX2 26 H 35 l l l l 98 95.52 80 PCT 15 P2 VS2 -.94 TEC TEH.610 SBAY2 7 H 103 l l l l 112 95.46 134 PCT 13 P2 VS2.82 TEC TEH.610 SBAY2 21 H 247 l l l l 118 95.99 111 PCT 21 P2 VS3 -.94 TEC TEH.610 SBAY2 21 H 250 l l 118 95.49 130 PCT 13 P2 VS4 -.81 TEC TEH.610 SBAY2 21 H 250 l l 118 95 2.20 304 WAR.46 P32 VS3 -.70 VS3 TEH.610 ZYAX2 27 H 7 l l l l 120 95.34 115 PCT 10 P2 VS1.91 TEC TEH.610 SBAY2 21 H 251 l l 120 95 1.68 112 PCT 29 P2 VS3 -.88 TEC TEH.610 SBAY2 21 H 251 l l 120 95 1.17 112 PCT 23 P2 VS3.88 TEC TEH.610 SBAY2 21 H 251 l
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
l ROW COL VOLTS DEG IND PER CRLEN CHN LOCN INCH1 INCH2 BEGT ENDT PDIA PTYPE CAL L IDX UTIL1 UTIL2l
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
24 ST Max
SG - 32 Calls of Interest Palo Verde 3 U3R20 PVNGS3 20180401 04/20/2018 13:40:22
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
l ROW COL VOLTS DEG IND PER CRLEN CHN LOCN INCH1 INCH2 BEGT ENDT PDIA PTYPE CAL L IDX UTIL1 UTIL2l
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
l 120 95.37 132 PCT 11 P2 VS4.76 TEC TEH.610 SBAY2 21 H 251 l l 120 95 3.64 303 WAR.49 P32 VS3 -.86 VS3 TEH.610 ZYAX2 27 H 6 l l 120 95 2.70 113 WAR.71 P9 VS3.96 VS3 TEH.610 ZYAX2 27 H 6 l l l l 134 95.90 130 PCT 20 P2 11H 1.00 TEC TEH.610 SBAY2 21 H 258 l l 134 95 1.60 127 WAR.32 P32 11H 1.00 11H TEH.610 ZYAX2 27 H 5 l l l l 136 95.35 60 PCT 11 P2 BW1 -1.08 TEC TEH.610 SBAY2 21 H 259 l l l l 152 95.45 128 PCT 13 P2 VS1.86 TEC TEH.610 SBAY2 21 H 267 l l l l 168 95.32 119 PCT 10 P2 VS5.87 TEC TEH.610 SBAY2 21 H 275 l l l l 47 96 1.82 107 PCT 30 P2 BW1 -.25 TEC TEH.610 SBAY2 3 H 80 l l 47 96 3.26 100 PCT 38 P2 BW1.86 TEC TEH.610 SBAY2 3 H 80 l l 47 96 1.25 126 PCT 25 P2 VS3.70 TEC TEH.610 SBAY2 3 H 80 l l 47 96.78 107 PCT 19 P2 BW2.62 TEC TEH.610 SBAY2 3 H 80 l l 47 96 TBP P2 BW1.86 TEC TEH.610 SBAY2 24 H 15 l l 47 96 2.41 70 WAR.44 P18 BW1 -.25 VS3 TEH.610 ZYAX2 27 H 25 l l 47 96 3.34 261 WAR.44 P16 BW1.86 VS3 TEH.610 ZYAX2 27 H 25 l l 47 96 1.81 98 WAR.69 P23 VS3.60 VS3 TEH.610 ZYAX2 27 H 25 l l l l 49 96 2.12 107 PCT 32 P2 BW1 -1.22 TEC TEH.610 SBAY2 3 H 16 l l 49 96.87 113 PCT 20 P2 BW1 -.54 TEC TEH.610 SBAY2 3 H 16 l l 49 96.71 95 PCT 18 P2 BW2 -1.16 TEC TEH.610 SBAY2 3 H 16 l l 49 96.51 82 PCT 15 P2 BW2.31 TEC TEH.610 SBAY2 3 H 16 l l 49 96 TBP P2 BW1 -.54 TEC TEH.610 SBAY2 24 H 14 l l 49 96 4.21 136 WAR.63 P2 BW1 -1.19 VS3 TEH.610 ZYAX2 27 H 24 l l 49 96 1.80 145 WAR.61 P2 BW1 -.54 VS3 TEH.610 ZYAX2 27 H 24 l l l l 75 96.60 121 PCT 15 P2 VS2.70 TEC TEH.610 SBAY2 8 H 90 l l l l 81 96.36 137 PCT 11 P2 VS2.82 TEC TEH.610 SBAY2 8 H 93 l l l l 111 96.42 148 PCT 13 P2 VS2 -.81 TEC TEH.610 SBAY2 20 H 234 l l 111 96.31 147 PCT 11 P2 VS4.85 TEC TEH.610 SBAY2 20 H 234 l l l l 157 96.28 50 PCT 10 P2 BW1.36 TEC TEH.610 SBAY2 20 H 211 l l l l 163 96.28 151 PCT 10 P2 VS5.87 TEC TEH.610 SBAY2 20 H 208 l l l l 48 97.92 118 PCT 21 P2 VS3 -.84 TEC TEH.610 SBAY2 3 H 81 l l 48 97 1.75 277 WAR.52 P23 VS3 -.84 VS3 TEH.610 ZYAX2 27 H 23 l l l
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
l ROW COL VOLTS DEG IND PER CRLEN CHN LOCN INCH1 INCH2 BEGT ENDT PDIA PTYPE CAL L IDX UTIL1 UTIL2l
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
25 ST Max
SG - 32 Calls of Interest Palo Verde 3 U3R20 PVNGS3 20180401 04/20/2018 13:40:22
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
l ROW COL VOLTS DEG IND PER CRLEN CHN LOCN INCH1 INCH2 BEGT ENDT PDIA PTYPE CAL L IDX UTIL1 UTIL2l
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
l 54 97.32 133 PCT 10 P2 VS3 -.82 TEC TEH.610 SBAY2 4 H 20 l l l l 78 97.58 104 PCT 15 P2 VS2 -.70 TEC TEH.610 SBAY2 8 H 120 l l l l 92 97.58 131 PCT 15 P2 10H.94 TEC TEH.610 SBAY2 8 H 113 l l l l 110 97.27 123 PCT 9 P2 VS2.86 TEC TEH.610 SBAY2 21 H 177 l l l l 47 98.65 140 PCT 17 P2 BW1.86 TEC TEH.610 SBAY2 3 H 82 l l 47 98.62 94 PCT 17 P2 BW2 -1.21 TEC TEH.610 SBAY2 3 H 82 l l l l 51 98.40 92 PCT 12 P2 BW1 -.77 TEC TEH.610 SBAY2 3 H 18 l l l l 53 98.47 84 PCT 14 P2 BW1 -.99 TEC TEH.610 SBAY2 3 H 28 l l l l 55 98.31 141 PCT 10 P2 BW1 -1.10 TEC TEH.610 SBAY2 4 H 21 l l l l 67 98.53 60 PCT 15 P2 VS2 -1.03 TEC TEH.610 SBAY2 3 H 64 l l l l 69 98.65 83 PCT 16 P2 BW1 1.02 TEC TEH.610 SBAY2 8 H 126 l l 69 98.80 77 PCT 19 P2 VS4.80 TEC TEH.610 SBAY2 8 H 126 l l l l 89 98.28 101 PCT 9 P2 VS4.94 TEC TEH.610 SBAY2 8 H 136 l l l l 103 98.73 107 PCT 18 P2 VS3.72 TEC TEH.610 SBAY2 8 H 143 l l l l 111 98.30 144 PCT 9 P2 VS2 -.82 TEC TEH.610 SBAY2 21 H 240 l l l l 48 99 1.71 108 PCT 29 P2 BW1 -.87 TEC TEH.610 SBAY2 3 H 83 l l 48 99.68 129 PCT 18 P2 VS3 -.71 TEC TEH.610 SBAY2 3 H 83 l l 48 99 1.18 115 PCT 24 P2 BW2.68 TEC TEH.610 SBAY2 3 H 83 l l 48 99 TBP P2 BW1 -.87 TEC TEH.610 SBAY2 24 H 17 l l 48 99 2.25 125 WAR.49 P3 BW1 -.92 VS3 TEH.610 ZYAX2 27 H 21 l l 48 99 1.23 93 WAR.44 P23 VS3 -.54 VS3 TEH.610 ZYAX2 27 H 21 l l 48 99 1.87 109 WAR.30 P12 BW2.85 VS3 TEC.610 ZYAX2 227 C 49 l l l l 58 99.39 140 PCT 12 P2 BW1 -.38 TEC TEH.610 SBAY2 4 H 30 l l l l 62 99 1.07 112 PCT 23 P2 VS3 -.77 TEC TEH.610 SBAY2 3 H 59 l l 62 99 1.66 89 WAR.50 P23 VS3 -.62 VS3 TEH.610 ZYAX2 27 H 22 l l l l 74 99.39 137 PCT 11 P2 09H.79 TEC TEH.610 SBAY2 8 H 159 l l 74 99.45 131 PCT 13 P2 VS2 -.72 TEC TEH.610 SBAY2 8 H 159 l l l
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
l ROW COL VOLTS DEG IND PER CRLEN CHN LOCN INCH1 INCH2 BEGT ENDT PDIA PTYPE CAL L IDX UTIL1 UTIL2l
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
26 ST Max
SG - 32 Calls of Interest Palo Verde 3 U3R20 PVNGS3 20180401 04/20/2018 13:40:22
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
l ROW COL VOLTS DEG IND PER CRLEN CHN LOCN INCH1 INCH2 BEGT ENDT PDIA PTYPE CAL L IDX UTIL1 UTIL2l
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
l 76 99.37 133 PCT 11 P2 VS3.87 TEC TEH.610 SBAY2 8 H 158 l l l l 92 99.36 144 PCT 11 P2 10H 1.12 TEC TEH.610 SBAY2 8 H 150 l l l l 94 99.47 131 PCT 13 P2 VS2 -.79 TEC TEH.610 SBAY2 8 H 149 l l l l 98 99.56 119 PCT 15 P2 VS2 -.82 TEC TEH.610 SBAY2 8 H 147 l l l l 106 99.30 142 PCT 10 P2 VS2.78 TEC TEH.610 SBAY2 20 H 172 l l 106 99.30 135 PCT 10 P2 VS3.80 TEC TEH.610 SBAY2 20 H 172 l l l l 114 99.29 39 PCT 10 P2 VS4 -.64 TEC TEH.610 SBAY2 20 H 176 l l l l 118 99.34 149 PCT 11 P2 VS2.84 TEC TEH.610 SBAY2 20 H 178 l l l l 120 99.28 42 PCT 10 P2 BW1 -1.36 TEC TEH.610 SBAY2 20 H 179 l l l l 130 99.30 137 PCT 10 P2 VS3.77 TEC TEH.610 SBAY2 20 H 184 l l 130 99.31 150 PCT 11 P2 VS5.85 TEC TEH.610 SBAY2 20 H 184 l l l l 134 99.33 49 PCT 11 P2 BW2 -1.27 TEC TEH.610 SBAY2 20 H 186 l l l l 136 99.61 127 PCT 16 P2 VS1 -1.01 TEC TEH.610 SBAY2 24 H 53 l l l l 144 99.29 50 PCT 10 P2 VS1 -1.01 TEC TEH.610 SBAY2 20 H 190 l l 144 99.27 157 PCT 10 P2 VS5.80 TEC TEH.610 SBAY2 20 H 190 l l l l 158 99.29 142 PCT 10 P2 VS5.82 TEC TEH.610 SBAY2 20 H 197 l l l l 160 99.29 135 PCT 10 P2 VS5.73 TEC TEH.610 SBAY2 20 H 198 l l l l 168 99.99 110 PCT 22 P2 01C -.14 TEC TEH.610 SBAY2 20 H 202 l l 168 99 1.16 60 WAR.37 P47 01C -.14 01C TEC.610 ZYAX2 227 C 27 l l l l 170 99.89 95 PCT 21 P2 01C -.99 TEC TEH.610 SBAY2 20 H 203 l l 170 99 2.01 282 WAR.77 P17 01C -.85 01C TEC.610 ZYAX2 227 C 28 l l l l 47 100 1.54 117 PCT 28 P2 BW1.58 TEC TEH.610 SBAY2 5 H 115 l l 47 100.30 40 PCT 10 P2 BW2 -.58 TEC TEH.610 SBAY2 5 H 115 l l 47 100.52 88 PCT 15 P2 BW2 1.05 TEC TEH.610 SBAY2 5 H 115 l l 47 100 TBP P2 BW1.58 TEC TEH.610 SBAY2 24 H 18 l l 47 100 1.91 68 WAR.47 P17 BW1.80 VS3 TEH.610 ZYAX2 27 H 20 l l l l 87 100.47 131 PCT 14 P2 09H.67 TEC TEH.610 SBAY2 7 H 127 l
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
l ROW COL VOLTS DEG IND PER CRLEN CHN LOCN INCH1 INCH2 BEGT ENDT PDIA PTYPE CAL L IDX UTIL1 UTIL2l
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
27 ST Max
SG - 32 Calls of Interest Palo Verde 3 U3R20 PVNGS3 20180401 04/20/2018 13:40:22
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
l ROW COL VOLTS DEG IND PER CRLEN CHN LOCN INCH1 INCH2 BEGT ENDT PDIA PTYPE CAL L IDX UTIL1 UTIL2l
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
l l l 95 100.35 113 PCT 11 P2 VS4.95 TEC TEH.610 SBAY2 7 H 131 l l l l 103 100.34 120 PCT 11 P2 BW1 -1.02 TEC TEH.610 SBAY2 7 H 135 l l l l 171 100.30 137 PCT 9 P2 11H.75 TEC TEH.610 SBAY2 21 H 142 l l l l 52 101.81 105 PCT 19 P2 VS3 -.92 TEC TEH.610 SBAY2 4 H 96 l l l l 54 101.41 50 PCT 13 P2 09H -1.01 TEC TEH.610 SBAY2 3 H 21 l l 54 101.68 120 PCT 18 P2 VS3 -.72 TEC TEH.610 SBAY2 3 H 21 l l l l 64 101.64 121 PCT 17 P2 BW1 -.75 TEC TEH.610 SBAY2 3 H 61 l l l l 72 101.37 83 PCT 12 P2 09H.94 TEC TEH.610 SBAY2 7 H 154 l l l l 86 101.45 71 PCT 14 P2 VS2 -.80 TEC TEH.610 SBAY2 7 H 147 l l l l 100 101.98 113 PCT 22 P2 VS3.86 TEC TEH.610 SBAY2 7 H 140 l l 100 101 1.95 311 WAR.42 P32 VS3.86 VS3 TEH.610 ZYAX2 27 H 8 l l l l 144 101.45 82 PCT 13 P2 VS1 -.93 TEC TEH.610 SBAY2 21 H 128 l l l l 166 101.34 115 PCT 10 P2 VS5.82 TEC TEH.610 SBAY2 21 H 139 l l l l 168 101 1.02 90 PCT 22 P2 01C -.93 TEC TEH.610 SBAY2 21 H 140 l l 168 101 1.98 285 WAR.42 P16 01C -.87 01C TEC.610 ZYAX2 227 C 30 l l l l 51 102 1.64 121 PCT 29 P2 BW1 -.84 TEC TEH.610 SBAY2 3 H 85 l l 51 102 TBP P2 BW1 -.84 TEC TEH.610 SBAY2 24 H 20 l l 51 102 2.70 93 WAR.50 P19 BW1 -1.05 VS3 TEH.610 ZYAX2 27 H 18 l l l l 53 102 1.27 111 PCT 25 P2 VS3.83 TEC TEH.610 SBAY2 4 H 95 l l 53 102 TBP P2 VS3.83 TEC TEH.610 SBAY2 24 H 19 l l 53 102 2.04 92 WAR.52 P23 VS3.61 VS3 TEH.610 ZYAX2 27 H 19 l l l l 55 102.31 91 PCT 10 P2 BW2 -.98 TEC TEH.610 SBAY2 4 H 83 l l l l 65 102.55 88 PCT 15 P2 VS4.91 TEC TEH.610 SBAY2 3 H 62 l l l l 79 102 1.16 124 PCT 23 P2 09H.80 TEC TEH.610 SBAY2 8 H 166 l l 79 102 1.64 106 WAR.24 P22 09H.58 09H TEH.610 ZYAX2 26 H 40 l l l l 93 102.78 109 PCT 18 P2 VS2.84 TEC TEH.610 SBAY2 8 H 173 l
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
l ROW COL VOLTS DEG IND PER CRLEN CHN LOCN INCH1 INCH2 BEGT ENDT PDIA PTYPE CAL L IDX UTIL1 UTIL2l
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
28 ST Max
SG - 32 Calls of Interest Palo Verde 3 U3R20 PVNGS3 20180401 04/20/2018 13:40:22
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
l ROW COL VOLTS DEG IND PER CRLEN CHN LOCN INCH1 INCH2 BEGT ENDT PDIA PTYPE CAL L IDX UTIL1 UTIL2l
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
l l l 109 102.40 122 PCT 13 P2 VS2 -1.00 TEC TEH.610 SBAY2 20 H 171 l l 109 102.40 139 PCT 13 P2 VS4.97 TEC TEH.610 SBAY2 20 H 171 l l l l 135 102.31 90 PCT 11 P2 VS1.67 TEC TEH.610 SBAY2 20 H 158 l l l l 159 102.32 109 PCT 11 P2 11H.53 TEC TEH.610 SBAY2 20 H 147 l l l l 165 102.33 125 PCT 11 P2 VS2 -.92 TEC TEH.610 SBAY2 20 H 144 l l 165 102.38 129 PCT 12 P2 VS4.83 TEC TEH.610 SBAY2 20 H 144 l l l l 169 102.83 101 PCT 20 P2 01C.91 TEC TEH.610 SBAY2 20 H 142 l l 169 102 1.96 113 WAR.24 P1 01C.64 01C TEC.610 ZYAX2 227 C 31 l l l l 171 102.58 135 PCT 16 P2 01C.96 TEC TEH.610 SBAY2 20 H 141 l l l l 50 103.79 118 PCT 19 P2 BW1 -.77 TEC TEH.610 SBAY2 3 H 95 l l 50 103.65 94 PCT 17 P2 BW1.82 TEC TEH.610 SBAY2 3 H 95 l l 50 103.87 104 PCT 20 P2 VS3 -1.01 TEC TEH.610 SBAY2 3 H 95 l l 50 103.73 117 PCT 18 P2 BW2 -.83 TEC TEH.610 SBAY2 3 H 95 l l 50 103 1.52 120 WAR.26 P31 VS3 -.61 VS3 TEH.610 ZYAX2 27 H 17 l l l l 52 103.79 86 PCT 19 P2 BW1 -.84 TEC TEH.610 SBAY2 3 H 86 l l 52 103.38 120 PCT 12 P2 BW1.66 TEC TEH.610 SBAY2 3 H 86 l l 52 103.36 111 PCT 12 P2 VS3 -.84 TEC TEH.610 SBAY2 3 H 86 l l l l 54 103.54 111 PCT 15 P2 VS3 -.88 TEC TEH.610 SBAY2 4 H 94 l l l l 66 103 1.04 125 PCT 23 P2 BW1 -.81 TEC TEH.610 SBAY2 3 H 63 l l 66 103 1.45 83 WAR.32 P19 BW1 -.83 VS3 TEH.610 ZYAX2 27 H 13 l l l l 78 103.34 151 PCT 12 P2 09H.95 TEC TEH.610 SBAY2 8 H 195 l l l l 98 103.49 86 PCT 14 P2 VS3.99 TEC TEH.610 SBAY2 8 H 185 l l l l 102 103.75 112 PCT 18 P2 VS3.97 TEC TEH.610 SBAY2 8 H 183 l l l l 116 103.31 47 PCT 11 P2 VS4 -.86 TEC TEH.610 SBAY2 20 H 113 l l l l 134 103.29 145 PCT 10 P2 VS1.73 TEC TEH.610 SBAY2 20 H 122 l l l l 162 103.29 110 PCT 10 P2 BW1.75 TEC TEH.610 SBAY2 20 H 136 l l l l 164 103.27 76 PCT 10 P2 BW1 -1.27 TEC TEH.610 SBAY2 20 H 137 l
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
l ROW COL VOLTS DEG IND PER CRLEN CHN LOCN INCH1 INCH2 BEGT ENDT PDIA PTYPE CAL L IDX UTIL1 UTIL2l
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
29 ST Max
SG - 32 Calls of Interest Palo Verde 3 U3R20 PVNGS3 20180401 04/20/2018 13:40:22
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
l ROW COL VOLTS DEG IND PER CRLEN CHN LOCN INCH1 INCH2 BEGT ENDT PDIA PTYPE CAL L IDX UTIL1 UTIL2l
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
l l l 166 103.43 122 PCT 14 P2 VS5 -.93 TEC TEH.610 SBAY2 20 H 138 l l l l 170 103.33 143 PCT 11 P2 11H.73 TEC TEH.610 SBAY2 20 H 140 l l l l 47 104 1.16 106 PCT 24 P2 BW1 -.33 TEC TEH.610 SBAY2 3 H 96 l l 47 104 1.80 114 PCT 30 P2 VS3 -.76 TEC TEH.610 SBAY2 3 H 96 l l 47 104.42 107 PCT 13 P2 VS3.84 TEC TEH.610 SBAY2 3 H 96 l l 47 104 1.96 102 PCT 31 P2 BW2.99 TEC TEH.610 SBAY2 3 H 96 l l 47 104 TBP P2 VS3 -.76 TEC TEH.610 SBAY2 24 H 24 l l 47 104 1.04 133 WAR.39 P3 BW1 -.26 VS3 TEH.610 ZYAX2 27 H 16 l l 47 104 3.37 131 WAR.53 P7 VS3 -.59 VS3 TEH.610 ZYAX2 27 H 16 l l 47 104.62 108 WAR.13 P30 VS3 -.54 VS3 TEC.610 ZYAX2 227 C 44 l l 47 104 2.27 273 WAR.32 P13 BW2 1.47 VS3 TEC.610 ZYAX2 227 C 44 l l l l 51 104.94 142 PCT 21 P2 BW1 -.93 TEC TEH.610 SBAY2 3 H 94 l l 51 104 1.07 290 WAR.37 P19 BW1 -.88 VS3 TEH.610 ZYAX2 27 H 15 l l l l 81 104 1.01 128 PCT 22 P2 09H.79 TEC TEH.610 SBAY2 7 H 162 l l 81 104 1.17 99 WAR.31 P16 09H.58 09H TEH.610 ZYAX2 26 H 44 l l l l 87 104.38 116 PCT 12 P2 BW1 1.33 TEC TEH.610 SBAY2 7 H 165 l l l l 99 104.35 126 PCT 12 P2 VS3.85 TEC TEH.610 SBAY2 7 H 171 l l l l 103 104.41 118 PCT 13 P2 VS2 -.85 TEC TEH.610 SBAY2 7 H 173 l l l l 135 104.36 141 PCT 11 P2 VS1.78 TEC TEH.610 SBAY2 21 H 96 l l l l 50 105.74 90 PCT 19 P2 BW1.71 TEC TEH.610 SBAY2 3 H 97 l l l l 54 105.46 136 PCT 14 P2 VS3 -.82 TEC TEH.610 SBAY2 3 H 88 l l l l 58 105.98 121 PCT 22 P2 BW1.79 TEC TEH.610 SBAY2 4 H 88 l l 58 105 2.31 130 WAR.29 P31 BW1 1.00 VS3 TEH.610 ZYAX2 27 H 14 l l l l 60 105.40 111 PCT 12 P2 VS2 1.02 TEC TEH.610 SBAY2 3 H 35 l l l l 74 105.38 125 PCT 12 P2 VS4.68 TEC TEH.610 SBAY2 7 H 193 l l l l 84 105.32 140 PCT 11 P2 VS3.98 TEC TEH.610 SBAY2 7 H 188 l l l l 90 105.32 131 PCT 11 P2 VS2 1.08 TEC TEH.610 SBAY2 7 H 185 l l l
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
l ROW COL VOLTS DEG IND PER CRLEN CHN LOCN INCH1 INCH2 BEGT ENDT PDIA PTYPE CAL L IDX UTIL1 UTIL2l
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
30 ST Max
SG - 32 Calls of Interest Palo Verde 3 U3R20 PVNGS3 20180401 04/20/2018 13:40:22
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
l ROW COL VOLTS DEG IND PER CRLEN CHN LOCN INCH1 INCH2 BEGT ENDT PDIA PTYPE CAL L IDX UTIL1 UTIL2l
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
l 102 105.43 107 PCT 13 P2 VS3.97 TEC TEH.610 SBAY2 7 H 179 l l l l 138 105.33 150 PCT 10 P2 BW1 -1.33 TEC TEH.610 SBAY2 21 H 61 l l l l 140 105.32 67 PCT 10 P2 VS1 -.99 TEC TEH.610 SBAY2 21 H 62 l l l l 49 106.53 132 PCT 15 P2 BW2 1.01 TEC TEH.610 SBAY2 3 H 98 l l l l 53 106.37 94 PCT 12 P2 BW1 -.56 TEC TEH.610 SBAY2 3 H 92 l l 53 106.80 123 PCT 19 P2 VS3 -.90 TEC TEH.610 SBAY2 3 H 92 l l l l 75 106.48 112 PCT 13 P2 VS2.68 TEC TEH.610 SBAY2 8 H 202 l l l l 87 106.73 128 PCT 18 P2 09H.71 TEC TEH.610 SBAY2 8 H 208 l l l l 89 106.52 122 PCT 14 P2 VS3 -.82 TEC TEH.610 SBAY2 8 H 209 l l 89 106.56 103 PCT 15 P2 VS4.91 TEC TEH.610 SBAY2 8 H 209 l l l l 91 106.28 79 PCT 9 P2 BW1.77 TEC TEH.610 SBAY2 8 H 210 l l l l 103 106.54 133 PCT 14 P2 VS3.82 TEC TEH.610 SBAY2 8 H 216 l l l l 107 106.28 154 PCT 10 P2 VS4.81 TEC TEH.610 SBAY2 20 H 106 l l l l 111 106.28 140 PCT 10 P2 VS2 -.93 TEC TEH.610 SBAY2 20 H 104 l l l l 115 106.28 20 PCT 10 P2 BW1.42 TEC TEH.610 SBAY2 20 H 102 l l l l 117 106.30 142 PCT 10 P2 VS2 -1.09 TEC TEH.610 SBAY2 20 H 101 l l l l 119 106.29 49 PCT 10 P2 BW1.79 TEC TEH.610 SBAY2 20 H 100 l l 119 106.33 157 PCT 11 P2 VS4 -.79 TEC TEH.610 SBAY2 20 H 100 l l l l 121 106.38 127 PCT 12 P2 VS3 -.85 TEC TEH.610 SBAY2 20 H 99 l l l l 129 106.32 147 PCT 11 P2 VS2.77 TEC TEH.610 SBAY2 20 H 95 l l l l 133 106.27 47 PCT 10 P2 BW1.80 TEC TEH.610 SBAY2 20 H 93 l l l l 145 106.50 92 PCT 15 P2 VS1.32 TEC TEH.610 SBAY2 20 H 87 l l l l 147 106.29 143 PCT 10 P2 VS1.71 TEC TEH.610 SBAY2 20 H 86 l l l l 155 106.27 155 PCT 10 P2 VS1.85 TEC TEH.610 SBAY2 20 H 82 l
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
l ROW COL VOLTS DEG IND PER CRLEN CHN LOCN INCH1 INCH2 BEGT ENDT PDIA PTYPE CAL L IDX UTIL1 UTIL2l
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
31 ST Max
SG - 32 Calls of Interest Palo Verde 3 U3R20 PVNGS3 20180401 04/20/2018 13:40:22
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
l ROW COL VOLTS DEG IND PER CRLEN CHN LOCN INCH1 INCH2 BEGT ENDT PDIA PTYPE CAL L IDX UTIL1 UTIL2l
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
l 155 106.29 142 PCT 10 P2 VS2.86 TEC TEH.610 SBAY2 20 H 82 l l l l 165 106.28 139 PCT 10 P2 VS4.76 TEC TEH.610 SBAY2 20 H 77 l l l l 48 107 1.16 91 PCT 24 P2 BW1 -.79 TEC TEH.610 SBAY2 3 H 100 l l 48 107 1.53 119 WAR.32 P2 BW1 -.86 VS3 TEH.610 ZYAX2 26 H 21 l l l l 50 107.67 87 PCT 18 P2 BW2 -.85 TEC TEH.610 SBAY2 3 H 99 l l l l 54 107.40 140 PCT 12 P2 VS3 -.85 TEC TEH.610 SBAY2 3 H 91 l l l l 56 107.64 123 PCT 17 P2 VS3 -.87 TEC TEH.610 SBAY2 3 H 90 l l l l 88 107.39 134 PCT 11 P2 VS2 -.80 TEC TEH.610 SBAY2 8 H 225 l l l l 96 107.51 69 PCT 14 P2 10H.78 TEC TEH.610 SBAY2 8 H 221 l l l l 106 107.40 142 PCT 13 P2 VS4 -.73 TEC TEH.610 SBAY2 20 H 41 l l l l 116 107.27 155 PCT 10 P2 VS2.75 TEC TEH.610 SBAY2 20 H 46 l l l l 122 107.27 127 PCT 10 P2 VS1.64 TEC TEH.610 SBAY2 20 H 49 l l l l 124 107.28 101 PCT 10 P2 VS2.74 TEC TEH.610 SBAY2 20 H 50 l l l l 126 107.71 77 PCT 19 P2 VS1 -1.01 TEC TEH.610 SBAY2 20 H 51 l l l l 128 107.30 85 PCT 10 P2 VS5.83 TEC TEH.610 SBAY2 20 H 52 l l l l 134 107.45 70 PCT 14 P2 VS1 -.84 TEC TEH.610 SBAY2 20 H 55 l l l l 152 107.28 125 PCT 10 P2 VS1.78 TEC TEH.610 SBAY2 20 H 64 l l 152 107.32 145 PCT 11 P2 VS2.75 TEC TEH.610 SBAY2 20 H 64 l l l l 162 107.27 144 PCT 10 P2 VS5.89 TEC TEH.610 SBAY2 20 H 69 l l l l 166 107.29 141 PCT 10 P2 VS2.75 TEC TEH.610 SBAY2 20 H 71 l l l l 168 107.28 141 PCT 10 P2 VS2.77 TEC TEH.610 SBAY2 20 H 72 l l l l 170 107.67 132 PCT 18 P2 VS4.68 TEC TEH.610 SBAY2 20 H 73 l l 170 107.74 107 PCT 19 P2 VS5.84 TEC TEH.610 SBAY2 20 H 73 l l l l 51 108 1.01 112 PCT 22 P2 BW1 -.37 TEC TEH.610 SBAY2 4 H 100 l
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
l ROW COL VOLTS DEG IND PER CRLEN CHN LOCN INCH1 INCH2 BEGT ENDT PDIA PTYPE CAL L IDX UTIL1 UTIL2l
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
32 ST Max
SG - 32 Calls of Interest Palo Verde 3 U3R20 PVNGS3 20180401 04/20/2018 13:40:22
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
l ROW COL VOLTS DEG IND PER CRLEN CHN LOCN INCH1 INCH2 BEGT ENDT PDIA PTYPE CAL L IDX UTIL1 UTIL2l
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
l 51 108.64 80 PCT 16 P2 BW2.36 TEC TEH.610 SBAY2 4 H 100 l l 51 108 1.90 125 WAR.36 P18 BW1 -1.07 VS3 TEH.610 ZYAX2 26 H 20 l l l l 57 108.36 136 PCT 11 P2 VS3.74 TEC TEH.610 SBAY2 3 H 118 l l 57 108.44 118 PCT 13 P2 BW2 -.91 TEC TEH.610 SBAY2 3 H 118 l l l l 75 108.36 89 PCT 12 P2 VS3 -.83 TEC TEH.610 SBAY2 7 H 200 l l l l 81 108 1.12 127 PCT 24 P2 09H.91 TEC TEH.610 SBAY2 7 H 203 l l 81 108 1.07 92 WAR.35 P17 09H.88 VS3 TEH.610 ZYAX2 27 H 10 l l 81 108 NDF P9 09H 13.37 20.12 VS3 TEH.610 ZYAX2 27 H 10 l l l l 89 108.35 85 PCT 12 P2 VS2 -.86 TEC TEH.610 SBAY2 7 H 207 l l l l 97 108.43 133 PCT 13 P2 09H.66 TEC TEH.610 SBAY2 7 H 211 l l l l 171 108.37 86 PCT 11 P2 01C -1.01 TEC TEH.610 SBAY2 21 H 14 l l l l 54 109.54 135 PCT 15 P2 VS3.77 TEC TEH.610 SBAY2 4 H 101 l l l l 62 109.40 95 PCT 12 P2 VS3 -.86 TEC TEH.610 SBAY2 3 H 125 l l l l 64 109.31 140 PCT 10 P2 VS3.83 TEC TEH.610 SBAY2 3 H 124 l l l l 74 109.52 96 PCT 15 P2 VS2.78 TEC TEH.610 SBAY2 7 H 232 l l l l 76 109.42 125 PCT 13 P2 VS3.95 TEC TEH.610 SBAY2 7 H 231 l l l l 78 109.34 80 PCT 11 P2 VS2.83 TEC TEH.610 SBAY2 7 H 230 l l l l 86 109.31 102 PCT 11 P2 VS2.69 TEC TEH.610 SBAY2 7 H 226 l l l l 100 109.32 127 PCT 11 P2 VS2.75 TEC TEH.610 SBAY2 7 H 219 l l l l 112 109.37 126 PCT 11 P2 VS4 -.89 TEC TEH.610 SBAY2 19 H 142 l l l l 130 109.43 135 PCT 13 P2 VS1 -.99 TEC TEH.610 SBAY2 19 H 151 l l l l 49 110.47 80 PCT 14 P2 BW1 -.77 TEC TEH.610 SBAY2 3 H 102 l l 49 110.37 89 PCT 12 P2 VS3 -.94 TEC TEH.610 SBAY2 3 H 102 l l 49 110.74 100 PCT 19 P2 BW2 -.77 TEC TEH.610 SBAY2 3 H 102 l l 49 110 1.64 106 PCT 29 P2 BW2.97 TEC TEH.610 SBAY2 3 H 102 l l 49 110.56 110 PCT 16 P2 09C -1.84 TEC TEH.610 SBAY2 3 H 102 l l 49 110 TBP P2 BW2.97 TEC TEH.610 SBAY2 24 H 28 l
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
l ROW COL VOLTS DEG IND PER CRLEN CHN LOCN INCH1 INCH2 BEGT ENDT PDIA PTYPE CAL L IDX UTIL1 UTIL2l
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
33 ST Max
SG - 32 Calls of Interest Palo Verde 3 U3R20 PVNGS3 20180401 04/20/2018 13:40:22
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
l ROW COL VOLTS DEG IND PER CRLEN CHN LOCN INCH1 INCH2 BEGT ENDT PDIA PTYPE CAL L IDX UTIL1 UTIL2l
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
l 49 110 1.19 272 WAR.34 P39 BW2.96 VS3 TEC.610 ZYAX2 227 C 41 l l l l 53 110.30 98 PCT 10 P2 06C -1.05 TEC TEH.610 SBAY2 4 H 102 l l l l 65 110.33 133 PCT 10 P2 VS3 -.84 TEC TEH.610 SBAY2 4 H 125 l l l l 95 110.80 112 PCT 19 P2 VS3 -.67 TEC TEH.610 SBAY2 13 H 10 l l l l 127 110.35 137 PCT 12 P2 VS2 -.89 TEC TEH.610 SBAY2 20 H 32 l l l l 129 110.81 136 PCT 20 P2 VS1.71 TEC TEH.610 SBAY2 20 H 31 l l 129 110 1.55 94 WAR.36 P22 VS1.71 VS3 TEH.610 ZYAX2 27 H 4 l l l l 131 110.13 122 NQI 3 VS3 15.51 TEC TEH.610 SBAY2 20 H 30 l l 131 110.12 125 NQI 3 VS3 15.73 TEC TEH.610 SBAY2 20 H 30 l l 131 110.09 124 NQI 3 10C 24.25 TEC TEH.610 SBAY2 20 H 30 l l 131 110.12 60 NQI 3 10C 24.45 TEC TEH.610 SBAY2 20 H 30 l l 131 110 NDF P1 VS3 15.51 VS3 TEC.610 ZYAX2 228 C 9 l l 131 110 NDF P1 VS3 15.73 VS3 TEC.610 ZYAX2 228 C 9 l l 131 110 NDF P1 10C 24.25 VS3 TEC.610 ZYAX2 228 C 9 l l 131 110 NDF P1 10C 24.45 VS3 TEC.610 ZYAX2 228 C 9 l l l l 133 110.27 72 PCT 10 P2 VS5.89 TEC TEH.610 SBAY2 20 H 29 l l l l 151 110.37 138 PCT 12 P2 VS1.73 TEC TEH.610 SBAY2 20 H 20 l l l l 157 110.32 135 PCT 11 P2 VS2.75 TEC TEH.610 SBAY2 20 H 17 l l l l 54 111.40 88 PCT 12 P2 BW2 1.36 TEC TEH.610 SBAY2 4 H 134 l l l l 56 111.67 117 PCT 17 P2 VS3 -.81 TEC TEH.610 SBAY2 4 H 133 l l l l 90 111 1.02 126 PCT 22 P2 09H.75 TEC TEH.610 SBAY2 13 H 26 l l 90 111 1.24 108 WAR.23 P16 09H.75 10H TEH.610 ZYAX2 26 H 46 l l l l 138 111.35 99 PCT 11 P2 VS1 -1.08 TEC TEH.610 SBAY2 18 H 145 l l l l 140 111.51 101 PCT 14 P2 VS1 -.85 TEC TEH.610 SBAY2 18 H 146 l l l l 156 111.29 141 PCT 10 P2 VS5.75 TEC TEH.610 SBAY2 20 H 6 l l l l 47 112 1.23 114 PCT 25 P2 BW1 -.99 TEC TEH.610 SBAY2 3 H 104 l l 47 112.82 103 PCT 20 P2 BW1.00 TEC TEH.610 SBAY2 3 H 104 l l 47 112.47 132 PCT 14 P2 VS3.70 TEC TEH.610 SBAY2 3 H 104 l
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
l ROW COL VOLTS DEG IND PER CRLEN CHN LOCN INCH1 INCH2 BEGT ENDT PDIA PTYPE CAL L IDX UTIL1 UTIL2l
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
34 ST Max
SG - 32 Calls of Interest Palo Verde 3 U3R20 PVNGS3 20180401 04/20/2018 13:40:22
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
l ROW COL VOLTS DEG IND PER CRLEN CHN LOCN INCH1 INCH2 BEGT ENDT PDIA PTYPE CAL L IDX UTIL1 UTIL2l
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
l 47 112.35 50 PCT 11 P2 BW2 -.73 TEC TEH.610 SBAY2 3 H 104 l l 47 112 TBP P2 BW1 -.99 TEC TEH.610 SBAY2 24 H 29 l l 47 112 2.06 114 WAR.37 P2 BW1 -.94 VS3 TEH.610 ZYAX2 26 H 4 l l 47 112 1.84 146 WAR.47 P3 BW1.03 VS3 TEH.610 ZYAX2 26 H 4 l l l l 49 112.31 117 PCT 10 P2 BW1.24 TEC TEH.610 SBAY2 3 H 130 l l 49 112.39 109 PCT 12 P2 BW2 -.83 TEC TEH.610 SBAY2 3 H 130 l l l l 59 112.43 30 PCT 13 P2 BW1.77 TEC TEH.610 SBAY2 3 H 134 l l l l 61 112.34 29 PCT 11 P2 BW1.51 TEC TEH.610 SBAY2 3 H 135 l l l l 63 112.31 121 PCT 10 P2 BW2 1.07 TEC TEH.610 SBAY2 3 H 136 l l l l 89 112.38 86 PCT 12 P2 BW2.95 TEC TEH.610 SBAY2 11 H 7 l l l l 95 112.70 114 PCT 18 P2 VS3 -.56 TEC TEH.610 SBAY2 11 H 12 l l l l 121 112.54 119 PCT 15 P2 VS2.83 TEC TEH.610 SBAY2 19 H 135 l l l l 133 112.39 134 PCT 12 P2 VS1.50 TEC TEH.610 SBAY2 19 H 129 l l l l 44 113.36 85 PCT 11 P2 08H.08 TEC TEH.610 SBAY2 5 H 113 l l 44 113.96 122 PCT 21 P2 BW1 -1.02 TEC TEH.610 SBAY2 5 H 113 l l 44 113 1.72 132 WAR.42 P2 BW1 -.84 VS3 TEH.610 ZYAX2 26 H 19 l l l l 96 113 1.02 59 PCT 23 P2 VS2 -.76 TEC TEH.610 SBAY2 11 H 28 l l 96 113 1.44 277 WAR.47 P23 VS2 -.87 VS3 TEH.610 ZYAX2 27 H 9 l l l l 114 113.39 145 PCT 12 P2 VS2.84 TEC TEH.610 SBAY2 19 H 86 l l l l 138 113.31 140 PCT 11 P2 VS1 -.82 TEC TEH.610 SBAY2 19 H 99 l l l l 45 114.54 128 PCT 15 P2 VS3.71 TEC TEH.610 SBAY2 3 H 106 l l l l 47 114.51 123 PCT 14 P2 VS3.79 TEC TEH.610 SBAY2 4 H 138 l l 47 114.50 128 PCT 14 P2 BW2.57 TEC TEH.610 SBAY2 4 H 138 l l l l 49 114.38 123 PCT 11 P2 VS3.78 TEC TEH.610 SBAY2 4 H 106 l l l l 57 114.40 139 PCT 12 P2 BW1 -1.98 TEC TEH.610 SBAY2 4 H 142 l l l l 67 114.89 110 PCT 20 P2 09H.78 TEC TEH.610 SBAY2 4 H 147 l l 67 114 1.54 100 WAR.33 P18 09H.82 09H TEH.610 ZYAX2 25 H 38 l
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
l ROW COL VOLTS DEG IND PER CRLEN CHN LOCN INCH1 INCH2 BEGT ENDT PDIA PTYPE CAL L IDX UTIL1 UTIL2l
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
35 ST Max
SG - 32 Calls of Interest Palo Verde 3 U3R20 PVNGS3 20180401 04/20/2018 13:40:22
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
l ROW COL VOLTS DEG IND PER CRLEN CHN LOCN INCH1 INCH2 BEGT ENDT PDIA PTYPE CAL L IDX UTIL1 UTIL2l
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
l l l 75 114.36 120 PCT 11 P2 VS3.65 TEC TEH.610 SBAY2 13 H 37 l l l l 89 114.36 80 PCT 11 P2 BW1.89 TEC TEH.610 SBAY2 13 H 44 l l l l 113 114.48 118 PCT 14 P2 VS2.74 TEC TEH.610 SBAY2 18 H 130 l l l l 157 114.35 129 PCT 11 P2 VS1.61 TEC TEH.610 SBAY2 18 H 108 l l l l 44 115.88 80 PCT 21 P2 BW2 -.78 TEC TEH.610 SBAY2 3 H 107 l l 44 115 1.29 276 WAR.23 P13 BW2 -.81 VS3 TEC.610 ZYAX2 227 C 43 l l l l 88 115.30 87 PCT 10 P2 09C -1.08 TEC TEH.610 SBAY2 14 H 118 l l l l 102 115.47 135 PCT 13 P2 VS3 -.95 TEC TEH.610 SBAY2 13 H 57 l l l l 112 115.34 83 PCT 11 P2 VS4 -.86 TEC TEH.610 SBAY2 18 H 77 l l l l 170 115.30 95 PCT 10 P2 BW2 -.87 TEC TEH.610 SBAY2 18 H 42 l l l l 45 116.39 133 PCT 12 P2 BW2 -.88 TEC TEH.610 SBAY2 3 H 147 l l l l 49 116.31 57 PCT 10 P2 BW2 -.88 TEC TEH.610 SBAY2 3 H 148 l l l l 131 116.06 85 NQI 3 VS3 14.94 TEC TEH.610 SBAY2 19 H 75 l l 131 116.12 73 NQI 3 VS3 17.91 TEC TEH.610 SBAY2 19 H 75 l l 131 116.11 63 NQI 3 10C 22.65 TEC TEH.610 SBAY2 19 H 75 l l 131 116 NDF P3 VS3 14.94 VS3 TEC.610 ZYAX2 228 C 10 l l 131 116 NDF P3 VS3 17.91 VS3 TEC.610 ZYAX2 228 C 10 l l 131 116 NDF P3 10C 22.65 VS3 TEC.610 ZYAX2 228 C 10 l l l l 147 116.45 118 PCT 13 P2 VS1 -1.29 TEC TEH.610 SBAY2 19 H 67 l l l l 155 116 1.15 120 PCT 23 P2 VS1 -.91 TEC TEH.610 SBAY2 19 H 63 l l 155 116 2.80 107 WAR.46 P30 VS1 -.77 VS3 TEH.610 ZYAX2 26 H 59 l l l l 167 116.82 114 PCT 19 P2 BW2 -.93 TEC TEH.610 SBAY2 19 H 45 l l l l 169 116.37 124 PCT 11 P2 VS1 -.83 TEC TEH.610 SBAY2 18 H 41 l l l l 40 117 1.33 112 PCT 26 P2 BW1 -.88 TEC TEH.610 SBAY2 3 H 110 l l 40 117 TBP P2 BW1 -.88 TEC TEH.610 SBAY2 24 H 35 l l 40 117 1.60 94 WAR.72 P3 BW1 -.89 VS3 TEH.610 ZYAX2 26 H 5 l l l
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
l ROW COL VOLTS DEG IND PER CRLEN CHN LOCN INCH1 INCH2 BEGT ENDT PDIA PTYPE CAL L IDX UTIL1 UTIL2l
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
36 ST Max
SG - 32 Calls of Interest Palo Verde 3 U3R20 PVNGS3 20180401 04/20/2018 13:40:22
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
l ROW COL VOLTS DEG IND PER CRLEN CHN LOCN INCH1 INCH2 BEGT ENDT PDIA PTYPE CAL L IDX UTIL1 UTIL2l
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
l 42 117.85 126 PCT 20 P2 BW1 -.88 TEC TEH.610 SBAY2 3 H 109 l l 42 117.41 113 PCT 13 P2 BW1 -.10 TEC TEH.610 SBAY2 3 H 109 l l 42 117.32 45 PCT 11 P2 BW1.81 TEC TEH.610 SBAY2 3 H 109 l l 42 117.70 128 WAR.25 P3 BW1 -.84 VS3 TEH.610 ZYAX2 26 H 18 l l l l 44 117.74 114 PCT 19 P2 BW1 -1.00 TEC TEH.610 SBAY2 3 H 167 l l l l 48 117.53 133 PCT 15 P2 BW1.78 TEC TEH.610 SBAY2 3 H 166 l l l l 50 117.37 54 PCT 12 P2 BW1.75 TEC TEH.610 SBAY2 3 H 165 l l l l 60 117.39 87 PCT 12 P2 VS4 -.89 TEC TEH.610 SBAY2 3 H 160 l l l l 74 117.54 74 PCT 16 P2 VS3 1.12 TEC TEH.610 SBAY2 11 H 76 l l l l 84 117.41 74 PCT 13 P2 VS2.77 TEC TEH.610 SBAY2 11 H 71 l l l l 88 117.40 65 PCT 13 P2 VS4 -.94 TEC TEH.610 SBAY2 11 H 69 l l 88 117.28 27 PCT 10 P2 VS4.77 TEC TEH.610 SBAY2 11 H 69 l l l l 96 117.42 113 PCT 13 P2 09H.79 TEC TEH.610 SBAY2 11 H 66 l l 96 117.45 114 PCT 14 P2 10H.62 TEC TEH.610 SBAY2 11 H 66 l l l l 116 117.60 94 PCT 17 P2 VS2.80 TEC TEH.610 SBAY2 17 H 58 l l l l 120 117.36 128 PCT 11 P2 VS2.84 TEC TEH.610 SBAY2 19 H 23 l l l l 166 117.91 128 PCT 20 P2 BW2 -.97 TEC TEH.610 SBAY2 19 H 44 l l 166 117 1.12 115 WAR.31 P27 BW2 -.97 VS3 TEC.610 ZYAX2 228 C 21 l l l l 39 118 1.31 115 PCT 26 P2 BW1 -.93 TEC TEH.610 SBAY2 3 H 111 l l 39 118.41 124 PCT 13 P2 BW1.13 TEC TEH.610 SBAY2 3 H 111 l l 39 118.61 118 PCT 16 P2 VS3 -.78 TEC TEH.610 SBAY2 3 H 111 l l 39 118.35 138 PCT 11 P2 VS3.80 TEC TEH.610 SBAY2 3 H 111 l l 39 118 TBP P2 BW1 -.93 TEC TEH.610 SBAY2 24 H 36 l l 39 118 2.68 131 WAR.48 P3 BW1 -.89 VS3 TEH.610 ZYAX2 26 H 6 l l l l 41 118.54 125 PCT 15 P2 08H.75 TEC TEH.610 SBAY2 3 H 116 l l l l 61 118.70 116 PCT 17 P2 VS3.79 TEC TEH.610 SBAY2 4 H 167 l l l l 89 118.43 115 PCT 13 P2 VS3 -.86 TEC TEH.610 SBAY2 13 H 84 l l l l 117 118.29 107 PCT 9 P2 VS4 -.91 TEC TEH.610 SBAY2 18 H 72 l
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
l ROW COL VOLTS DEG IND PER CRLEN CHN LOCN INCH1 INCH2 BEGT ENDT PDIA PTYPE CAL L IDX UTIL1 UTIL2l
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
37 ST Max
SG - 32 Calls of Interest Palo Verde 3 U3R20 PVNGS3 20180401 04/20/2018 13:40:22
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
l ROW COL VOLTS DEG IND PER CRLEN CHN LOCN INCH1 INCH2 BEGT ENDT PDIA PTYPE CAL L IDX UTIL1 UTIL2l
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
l l l 121 118.38 81 PCT 12 P2 10H -1.02 TEC TEH.610 SBAY2 18 H 70 l l l l 125 118.40 138 PCT 12 P2 VS1.74 TEC TEH.610 SBAY2 18 H 68 l l l l 127 118.39 134 PCT 12 P2 VS1 -.97 TEC TEH.610 SBAY2 18 H 67 l l l l 129 118.34 123 PCT 11 P2 VS1.79 TEC TEH.610 SBAY2 18 H 66 l l l l 137 118.40 39 PCT 12 P2 BW1.79 TEC TEH.610 SBAY2 18 H 62 l l l l 96 119.40 98 PCT 12 P2 10H.78 TEC TEH.610 SBAY2 13 H 101 l l l l 138 119.46 109 PCT 13 P2 VS1 -.74 TEC TEH.610 SBAY2 18 H 25 l l l l 140 119.31 97 PCT 10 P2 BW1 -.86 TEC TEH.610 SBAY2 18 H 26 l l l l 37 120 2.08 120 PCT 32 P2 BW1 -.89 TEC TEH.610 SBAY2 3 H 113 l l 37 120.28 150 PCT 10 P2 BW2 -.84 TEC TEH.610 SBAY2 3 H 113 l l 37 120 TBP P2 BW1 -.89 TEC TEH.610 SBAY2 24 H 38 l l 37 120 2.80 115 WAR.33 P3 BW1 -.74 VS3 TEH.610 ZYAX2 26 H 7 l l l l 39 120.42 144 PCT 13 P2 BW1 -.88 TEC TEH.610 SBAY2 3 H 114 l l l l 43 120 1.20 117 PCT 24 P2 BW1 -.83 TEC TEH.610 SBAY2 4 H 117 l l 43 120.38 95 PCT 11 P2 BW2 -1.21 TEC TEH.610 SBAY2 4 H 117 l l 43 120 2.71 125 WAR.28 P2 BW1 -.69 VS3 TEH.610 ZYAX2 26 H 12 l l l l 47 120.67 120 PCT 17 P2 BW2.50 TEC TEH.610 SBAY2 5 H 13 l l l l 51 120.43 100 PCT 13 P2 09H -.43 TEC TEH.610 SBAY2 5 H 11 l l l l 63 120.57 127 PCT 16 P2 VS3.73 TEC TEH.610 SBAY2 5 H 5 l l l l 77 120.57 95 PCT 16 P2 VS2.71 TEC TEH.610 SBAY2 11 H 85 l l l l 135 120.35 145 PCT 12 P2 VS1.84 TEC TEH.610 SBAY2 17 H 44 l l l l 165 120.70 102 PCT 17 P2 BW2 -.89 TEC TEH.610 SBAY2 15 H 135 l l l l 167 120.33 151 PCT 10 P2 BW2 1.04 TEC TEH.610 SBAY2 15 H 132 l l l l 38 121.20 145 PCT 10 P2 05C -.23 TEC TEH.610 SBAY2 5 H 14 l l l
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
l ROW COL VOLTS DEG IND PER CRLEN CHN LOCN INCH1 INCH2 BEGT ENDT PDIA PTYPE CAL L IDX UTIL1 UTIL2l
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
38 ST Max
SG - 32 Calls of Interest Palo Verde 3 U3R20 PVNGS3 20180401 04/20/2018 13:40:22
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
l ROW COL VOLTS DEG IND PER CRLEN CHN LOCN INCH1 INCH2 BEGT ENDT PDIA PTYPE CAL L IDX UTIL1 UTIL2l
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
l 42 121.87 119 PCT 20 P2 BW1 -.80 TEC TEH.610 SBAY2 4 H 116 l l 42 121 2.91 128 WAR.73 P2 BW1 -.89 VS3 TEH.610 ZYAX2 26 H 13 l l l l 44 121.86 104 PCT 20 P2 BW1 -.72 TEC TEH.610 SBAY2 5 H 15 l l 44 121 1.58 102 WAR.58 P1 BW1 -.81 VS3 TEH.610 ZYAX2 26 H 14 l l l l 58 121.50 134 PCT 14 P2 VS3 -.88 TEC TEH.610 SBAY2 5 H 22 l l l l 66 121.91 102 PCT 21 P2 09H -.15 TEC TEH.610 SBAY2 5 H 26 l l 66 121 1.24 92 WAR.19 P17 09H -.23 09H TEH.610 ZYAX2 25 H 34 l l l l 86 121.32 129 PCT 11 P2 VS3.92 TEC TEH.610 SBAY2 11 H 115 l l l l 88 121.51 91 PCT 15 P2 VS3.90 TEC TEH.610 SBAY2 11 H 114 l l l l 92 121.50 90 PCT 15 P2 VS4 -.68 TEC TEH.610 SBAY2 11 H 112 l l l l 94 121.28 53 PCT 10 P2 VS3.96 TEC TEH.610 SBAY2 11 H 111 l l l l 100 121.70 93 PCT 18 P2 VS2.77 TEC TEH.610 SBAY2 11 H 108 l l l l 162 121.48 85 PCT 14 P2 BW2.86 TEC TEH.610 SBAY2 17 H 29 l l l l 164 121.44 112 PCT 13 P2 BW2 -1.36 TEC TEH.610 SBAY2 15 H 134 l l l l 166 121.32 41 PCT 10 P2 BW2.46 TEC TEH.610 SBAY2 15 H 131 l l l l 168 121.63 145 PCT 16 P2 BW2 -1.09 TEC TEH.610 SBAY2 14 H 172 l l l l 35 122.44 118 PCT 13 P2 05H.80 TEC TEH.610 SBAY2 5 H 111 l l 35 122 2.83 105 PCT 36 P2 BW1 -.93 TEC TEH.610 SBAY2 5 H 111 l l 35 122 TBP P2 BW1 -.93 TEC TEH.610 SBAY2 24 H 42 l l 35 122 2.79 97 WAR.38 P2 BW1 -.81 VS3 TEH.610 ZYAX2 26 H 8 l l l l 37 122 2.25 110 PCT 33 P2 BW1.65 TEC TEH.610 SBAY2 6 H 17 l l 37 122 TBP P2 BW1.65 TEC TEH.610 SBAY2 24 H 41 l l 37 122 3.37 76 WAR.59 P17 BW1.77 VS3 TEH.610 ZYAX2 26 H 9 l l l l 43 122.36 85 PCT 11 P2 BW2 -.75 TEC TEH.610 SBAY2 6 H 16 l l l l 45 122.37 138 PCT 11 P2 08H.81 TEC TEH.610 SBAY2 6 H 15 l l 45 122.31 39 PCT 10 P2 BW1.84 TEC TEH.610 SBAY2 6 H 15 l l l l 47 122.68 111 PCT 17 P2 BW1 -.93 TEC TEH.610 SBAY2 6 H 14 l
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
l ROW COL VOLTS DEG IND PER CRLEN CHN LOCN INCH1 INCH2 BEGT ENDT PDIA PTYPE CAL L IDX UTIL1 UTIL2l
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
39 ST Max
SG - 32 Calls of Interest Palo Verde 3 U3R20 PVNGS3 20180401 04/20/2018 13:40:22
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
l ROW COL VOLTS DEG IND PER CRLEN CHN LOCN INCH1 INCH2 BEGT ENDT PDIA PTYPE CAL L IDX UTIL1 UTIL2l
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
l l l 51 122 1.00 108 PCT 21 P2 BW1.82 TEC TEH.610 SBAY2 6 H 12 l l 51 122 3.52 177 WAR.28 P16 BW1 1.29 VS3 TEH.610 ZYAX2 26 H 15 l l l l 57 122.41 145 PCT 12 P2 VS3.72 TEC TEH.610 SBAY2 6 H 9 l l l l 71 122.40 132 PCT 12 P2 VS3 -.70 TEC TEH.610 SBAY2 13 H 119 l l l l 101 122.22 147 PCT 8 P2 VS2.74 TEC TEH.610 SBAY2 13 H 134 l l l l 167 122.52 129 PCT 14 P2 BW2.99 TEC TEH.610 SBAY2 14 H 169 l l l l 34 123.28 72 PCT 10 P2 07H -1.05 TEC TEH.610 SBAY2 5 H 110 l l l l 118 123.81 88 PCT 19 P2 VS1.82 TEC TEH.610 SBAY2 16 H 8 l l 118 123.30 60 PCT 10 P2 VS2.91 TEC TEH.610 SBAY2 16 H 8 l l l l 132 123.37 119 PCT 12 P2 VS3.77 TEC TEH.610 SBAY2 16 H 15 l l l l 138 123.39 59 PCT 12 P2 VS1.72 TEC TEH.610 SBAY2 16 H 18 l l l l 140 123.44 137 PCT 13 P2 06H.78 TEC TEH.610 SBAY2 16 H 19 l l l l 168 123.84 119 PCT 20 P2 VS1.71 TEC TEH.610 SBAY2 14 H 164 l l 168 123 2.20 106 PCT 32 P2 BW2 -1.07 TEC TEH.610 SBAY2 14 H 164 l l 168 123 TBP P2 BW2 -1.07 TEC TEH.610 SBAY2 24 H 48 l l 168 123 1.57 99 WAR.37 P6 VS1.89 VS3 TEH.610 ZYAX2 26 H 57 l l 168 123 2.40 276 WAR.41 P27 BW2 -1.07 VS3 TEC.610 ZYAX2 228 C 20 l l l l 35 124 1.15 99 PCT 24 P2 BW2.40 TEC TEH.610 SBAY2 5 H 43 l l 35 124 1.80 108 WAR.33 P12 BW2.86 VS3 TEC.610 ZYAX2 227 C 50 l l l l 39 124.35 82 PCT 11 P2 05C -1.00 TEC TEH.610 SBAY2 5 H 42 l l l l 47 124.54 95 PCT 15 P2 BW2.41 TEC TEH.610 SBAY2 5 H 38 l l l l 49 124.67 81 PCT 17 P2 BW2 -1.17 TEC TEH.610 SBAY2 5 H 37 l l l l 57 124.45 128 PCT 13 P2 VS3.74 TEC TEH.610 SBAY2 5 H 31 l l l l 59 124.43 138 PCT 13 P2 VS3.66 TEC TEH.610 SBAY2 5 H 30 l l l l 69 124 1.17 123 PCT 24 P2 VS3 -.76 TEC TEH.610 SBAY2 11 H 126 l l 69 124 1.38 97 WAR.31 P7 VS3 -.60 VS3 TEH.610 ZYAX2 25 H 32 l
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
l ROW COL VOLTS DEG IND PER CRLEN CHN LOCN INCH1 INCH2 BEGT ENDT PDIA PTYPE CAL L IDX UTIL1 UTIL2l
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
40 ST Max
SG - 32 Calls of Interest Palo Verde 3 U3R20 PVNGS3 20180401 04/20/2018 13:40:22
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
l ROW COL VOLTS DEG IND PER CRLEN CHN LOCN INCH1 INCH2 BEGT ENDT PDIA PTYPE CAL L IDX UTIL1 UTIL2l
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
l l l 93 124.32 51 PCT 11 P2 10H -.88 TEC TEH.610 SBAY2 11 H 138 l l l l 97 124.28 82 PCT 10 P2 VS3.88 TEC TEH.610 SBAY2 11 H 140 l l l l 127 124.31 100 PCT 10 P2 VS1.80 TEC TEH.610 SBAY2 15 H 204 l l l l 163 124.30 115 PCT 10 P2 BW2.94 TEC TEH.610 SBAY2 15 H 128 l l l l 167 124 1.60 79 PCT 28 P2 BW2.99 TEC TEH.610 SBAY2 14 H 163 l l 167 124 2.12 92 WAR.43 P11 BW2.99 VS3 TEC.610 ZYAX2 228 C 19 l l l l 28 125.35 109 PCT 11 P2 BW1.52 TEC TEH.610 SBAY2 5 H 46 l l 28 125.38 73 PCT 12 P2 BW2.94 TEC TEH.610 SBAY2 5 H 46 l l l l 70 125.41 79 PCT 13 P2 VS3.79 TEC TEH.610 SBAY2 11 H 168 l l l l 90 125.34 91 PCT 11 P2 09H.99 TEC TEH.610 SBAY2 11 H 158 l l l l 120 125.34 84 PCT 10 P2 VS2 1.09 TEC TEH.610 SBAY2 15 H 166 l l l l 162 125.87 127 PCT 20 P2 BW2 -.97 TEC TEH.610 SBAY2 15 H 127 l l 162 125 1.42 113 WAR.30 P27 BW2 -.97 VS3 TEC.610 ZYAX2 228 C 18 l l l l 25 126.29 83 PCT 9 P2 07H -1.01 TEC TEH.610 SBAY2 6 H 59 l l l l 31 126.45 127 PCT 13 P2 08H.90 TEC TEH.610 SBAY2 6 H 56 l l 31 126.72 99 PCT 17 P2 BW2.91 TEC TEH.610 SBAY2 6 H 56 l l l l 37 126.52 136 PCT 14 P2 BW1 -.92 TEC TEH.610 SBAY2 6 H 53 l l l l 69 126.60 126 PCT 16 P2 VS3 -.78 TEC TEH.610 SBAY2 13 H 157 l l l l 75 126.43 137 PCT 13 P2 BW1 -.97 TEC TEH.610 SBAY2 13 H 160 l l l l 95 126.44 128 PCT 13 P2 10H -.83 TEC TEH.610 SBAY2 13 H 170 l l l l 103 126.32 148 PCT 10 P2 VS2.66 TEC TEH.610 SBAY2 13 H 174 l l l l 115 126.70 142 PCT 18 P2 VS3 -.92 TEC TEH.610 SBAY2 14 H 252 l l l l 121 126.39 125 PCT 12 P2 VS3 -.79 TEC TEH.610 SBAY2 14 H 249 l l l l 145 126.31 145 PCT 10 P2 VS4.74 TEC TEH.610 SBAY2 14 H 237 l
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
l ROW COL VOLTS DEG IND PER CRLEN CHN LOCN INCH1 INCH2 BEGT ENDT PDIA PTYPE CAL L IDX UTIL1 UTIL2l
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
41 ST Max
SG - 32 Calls of Interest Palo Verde 3 U3R20 PVNGS3 20180401 04/20/2018 13:40:22
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
l ROW COL VOLTS DEG IND PER CRLEN CHN LOCN INCH1 INCH2 BEGT ENDT PDIA PTYPE CAL L IDX UTIL1 UTIL2l
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
l l l 161 126.38 112 PCT 11 P2 BW2.97 TEC TEH.610 SBAY2 15 H 126 l l l l 165 126.35 145 PCT 11 P2 VS4.82 TEC TEH.610 SBAY2 14 H 161 l l 165 126.30 111 PCT 10 P2 VS5.76 TEC TEH.610 SBAY2 14 H 161 l l l l 58 127.44 137 PCT 12 P2 VS3 -1.03 TEC TEH.610 SBAY2 6 H 76 l l l l 124 127.63 65 PCT 16 P2 VS1.91 TEC TEH.610 SBAY2 14 H 208 l l l l 140 127.30 136 PCT 10 P2 VS5.83 TEC TEH.610 SBAY2 14 H 216 l l l l 164 127 2.02 113 PCT 31 P2 BW2.79 TEC TEH.610 SBAY2 14 H 160 l l 164 127 TBP P2 BW2.79 TEC TEH.610 SBAY2 24 H 49 l l 164 127 2.95 96 WAR.40 P11 BW2.79 VS3 TEC.610 ZYAX2 228 C 17 l l l l 51 128.56 146 PCT 16 P2 BW1 -.96 TEC TEH.610 SBAY2 5 H 73 l l l l 71 128.42 71 PCT 13 P2 VS3 -.98 TEC TEH.610 SBAY2 11 H 172 l l l l 109 128.33 109 PCT 11 P2 VS3 -.68 TEC TEH.610 SBAY2 11 H 191 l l l l 163 128 1.13 106 PCT 23 P2 BW2.94 TEC TEH.610 SBAY2 15 H 119 l l 163 128 1.90 87 WAR.30 P4 BW2.94 VS3 TEC.610 ZYAX2 228 C 14 l l l l 165 128 2.38 93 PCT 34 P2 BW2.89 TEC TEH.610 SBAY2 14 H 157 l l 165 128 TBP P2 BW2.89 TEC TEH.610 SBAY2 24 H 50 l l 165 128 2.99 77 WAR.44 P4 BW2.89 VS3 TEC.610 ZYAX2 228 C 15 l l l l 50 129.58 122 PCT 16 P2 VS3 -.30 TEC TEH.610 SBAY2 5 H 101 l l l l 70 129.35 148 PCT 11 P2 VS3.92 TEC TEH.610 SBAY2 14 H 16 l l l l 158 129.61 110 PCT 16 P2 BW2.53 TEC TEH.610 SBAY2 15 H 116 l l l l 160 129.30 133 PCT 10 P2 BW2 -1.35 TEC TEH.610 SBAY2 15 H 117 l l l l 162 129.60 125 PCT 16 P2 BW2.61 TEC TEH.610 SBAY2 15 H 118 l l l l 164 129.54 71 PCT 15 P2 BW2.41 TEC TEH.610 SBAY2 14 H 154 l l l l 9 130.63 142 PCT 19 P2 BW1 1.40 TEH TEC.610 SBAY2 225 C 182 l l l l 15 130.24 117 PCT 10 P2 BW1.54 TEH TEC.610 SBAY2 211 C 180 l
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
l ROW COL VOLTS DEG IND PER CRLEN CHN LOCN INCH1 INCH2 BEGT ENDT PDIA PTYPE CAL L IDX UTIL1 UTIL2l
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
42 ST Max
SG - 32 Calls of Interest Palo Verde 3 U3R20 PVNGS3 20180401 04/20/2018 13:40:22
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
l ROW COL VOLTS DEG IND PER CRLEN CHN LOCN INCH1 INCH2 BEGT ENDT PDIA PTYPE CAL L IDX UTIL1 UTIL2l
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
l l l 49 130.36 130 PCT 11 P2 BW1 -.40 TEC TEH.610 SBAY2 6 H 93 l l l l 89 130.51 147 PCT 14 P2 VS2.67 TEC TEH.610 SBAY2 14 H 27 l l l l 91 130.31 135 PCT 10 P2 BW2.39 TEC TEH.610 SBAY2 14 H 28 l l l l 101 130.37 141 PCT 11 P2 VS2.69 TEC TEH.610 SBAY2 14 H 33 l l l l 113 130.35 142 PCT 11 P2 VS4.87 TEC TEH.610 SBAY2 14 H 199 l l l l 115 130.35 135 PCT 11 P2 VS2.79 TEC TEH.610 SBAY2 14 H 198 l l l l 129 130.33 138 PCT 10 P2 VS2.63 TEC TEH.610 SBAY2 14 H 191 l l l l 131 130.32 156 PCT 10 P2 VS4.69 TEC TEH.610 SBAY2 14 H 190 l l l l 161 130.71 132 PCT 18 P2 BW2 -.84 TEC TEH.610 SBAY2 14 H 159 l l l l 163 130.68 112 PCT 17 P2 BW2 -.89 TEC TEH.610 SBAY2 14 H 153 l l l l 165 130 1.24 123 PCT 24 P2 BW2.99 TEC TEH.610 SBAY2 14 H 152 l l 165 130 2.12 81 WAR.47 P4 BW2.99 VS3 TEC.610 ZYAX2 228 C 13 l l l l 66 131.40 134 PCT 15 P2 09H.76 TEH TEC.610 SBAY2 211 C 150 l l l l 150 131.51 141 PCT 14 P2 VS2 -.75 TEC TEH.610 SBAY2 14 H 144 l l l l 11 132.36 44 PCT 13 P2 BW2.76 TEH TEC.610 SBAY2 211 C 117 l l l l 13 132.36 81 PCT 13 P2 BW2 1.10 TEH TEC.610 SBAY2 211 C 118 l l l l 37 132.33 105 PCT 13 P2 08C.71 TEH TEC.610 SBAY2 211 C 129 l l l l 45 132.51 122 PCT 17 P2 08H.79 TEH TEC.610 SBAY2 211 C 133 l l l l 63 132.35 98 PCT 13 P2 VS3.00 TEH TEC.610 SBAY2 211 C 142 l l l l 65 132.52 116 PCT 17 P2 09H.75 TEH TEC.610 SBAY2 211 C 143 l l l l 67 132.27 138 PCT 11 P2 BW1 1.05 TEH TEC.610 SBAY2 211 C 144 l l l l 127 132.40 52 PCT 16 P2 VS1.97 TEH TEC.610 SBAY2 223 C 103 l l l
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
l ROW COL VOLTS DEG IND PER CRLEN CHN LOCN INCH1 INCH2 BEGT ENDT PDIA PTYPE CAL L IDX UTIL1 UTIL2l
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
43 ST Max
SG - 32 Calls of Interest Palo Verde 3 U3R20 PVNGS3 20180401 04/20/2018 13:40:22
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
l ROW COL VOLTS DEG IND PER CRLEN CHN LOCN INCH1 INCH2 BEGT ENDT PDIA PTYPE CAL L IDX UTIL1 UTIL2l
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
l 50 133 1.26 110 WAR.26 P2 09H 1.49 09H TEH.610 ZYAX2 26 H 47 l l 50 133.71 127 PCT 18 P2 09H 1.23 TEH TEC.610 SBAY2 212 C 162 l l l l 64 133.34 134 PCT 11 P2 VS3.55 TEH TEC.610 SBAY2 212 C 155 l l l l 76 133.59 143 PCT 16 P2 VS2.67 TEC TEH.610 SBAY2 14 H 55 l l l l 88 133.33 75 PCT 11 P2 VS2.64 TEC TEH.610 SBAY2 14 H 49 l l l l 98 133.43 112 PCT 13 P2 10H.72 TEC TEH.610 SBAY2 14 H 44 l l l l 116 133.26 33 PCT 12 P2 VS2.79 TEH TEC.610 SBAY2 223 C 92 l l l l 45 134.62 111 PCT 19 P2 BW1 -1.33 TEH TEC.610 SBAY2 211 C 7 l l l l 53 134.28 69 PCT 9 P2 VS3.70 TEH TEC.610 SBAY2 212 C 141 l l l l 69 134.45 81 PCT 13 P2 VS3 -.90 TEH TEC.610 SBAY2 212 C 149 l l l l 81 134.30 140 PCT 10 P2 VS3.75 TEC TEH.610 SBAY2 14 H 61 l l l l 99 134.36 135 PCT 11 P2 VS2.74 TEC TEH.610 SBAY2 14 H 70 l l l l 107 134.53 125 PCT 15 P2 09H.77 TEC TEH.610 SBAY2 14 H 74 l l l l 127 134.19 55 PCT 7 P2 06H.82 TEH TEC.610 SBAY2 224 C 57 l l l l 28 135.37 98 PCT 14 P2 05C.81 TEH TEC.610 SBAY2 211 C 108 l l l l 50 135.53 121 PCT 17 P2 09H 1.25 TEH TEC.610 SBAY2 211 C 98 l l l l 58 135.30 78 PCT 12 P2 VS3 -.92 TEH TEC.610 SBAY2 211 C 94 l l l l 92 135.31 109 PCT 10 P2 10H.77 TEC TEH.610 SBAY2 15 H 60 l l l l 100 135.32 70 PCT 10 P2 10H.80 TEC TEH.610 SBAY2 15 H 56 l l l l 51 136.29 94 PCT 12 P2 09H -.78 TEH TEC.610 SBAY2 211 C 76 l l l l 117 136.51 111 PCT 18 P2 VS2 -.71 TEH TEC.610 SBAY2 223 C 53 l l l l 62 137.30 103 PCT 10 P2 VS3 -.74 TEH TEC.610 SBAY2 212 C 94 l l l l 70 137.41 135 PCT 12 P2 09H.76 TEH TEC.610 SBAY2 212 C 90 l
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
l ROW COL VOLTS DEG IND PER CRLEN CHN LOCN INCH1 INCH2 BEGT ENDT PDIA PTYPE CAL L IDX UTIL1 UTIL2l
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
44 ST Max
SG - 32 Calls of Interest Palo Verde 3 U3R20 PVNGS3 20180401 04/20/2018 13:40:22
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
l ROW COL VOLTS DEG IND PER CRLEN CHN LOCN INCH1 INCH2 BEGT ENDT PDIA PTYPE CAL L IDX UTIL1 UTIL2l
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
l l l 102 137.39 123 PCT 12 P2 09H.74 TEC TEH.610 SBAY2 14 H 81 l l 102 137.34 129 PCT 11 P2 VS3.84 TEC TEH.610 SBAY2 14 H 81 l l l l 104 137.43 139 PCT 13 P2 VS2.79 TEC TEH.610 SBAY2 14 H 80 l l l l 128 137.24 29 PCT 11 P2 VS2.75 TEH TEC.610 SBAY2 223 C 41 l l 128 137.24 31 PCT 11 P2 VS3 -.75 TEH TEC.610 SBAY2 223 C 41 l l l l 156 137.20 119 PCT 7 P2 08H.80 TEH TEC.610 SBAY2 222 C 7 l l l l 67 138.52 90 PCT 15 P2 09H.79 TEH TEC.610 SBAY2 212 C 86 l l l l 87 138.36 147 PCT 11 P2 VS4.78 TEC TEH.610 SBAY2 14 H 103 l l l l 89 138.77 86 PCT 19 P2 VS2 -.95 TEC TEH.610 SBAY2 14 H 104 l l 89 138.42 102 PCT 12 P2 BW2.49 TEC TEH.610 SBAY2 14 H 104 l l l l 97 138 28.11 176 DTI P5 TSC -1.56 TEC TEH.610 SBAY2 14 H 108 l l 97 138 NDF P19 TSC -1.56 01C TEC.610 ZYAX2 227 C 37 l l l l 111 138.52 120 PCT 14 P2 10H.82 TEC TEH.610 SBAY2 14 H 115 l l l l 48 139.31 66 PCT 12 P2 VS3 -.73 TEH TEC.610 SBAY2 211 C 34 l l l l 56 139.30 67 PCT 12 P2 BW2 -1.60 TEH TEC.610 SBAY2 211 C 38 l l l l 60 139.27 62 PCT 11 P2 VS3 -.86 TEH TEC.610 SBAY2 211 C 40 l l l l 102 139.31 55 PCT 12 P2 VS2 -.71 TEH TEC.610 SBAY2 215 C 131 l l l l 59 140.28 143 PCT 11 P2 BW1 -.90 TEH TEC.610 SBAY2 211 C 53 l l l l 71 140.26 57 PCT 11 P2 VS3 -.90 TEH TEC.610 SBAY2 211 C 47 l l l l 113 140.33 87 PCT 14 P2 BW1.83 TEH TEC.610 SBAY2 223 C 10 l l 113 140.22 34 PCT 10 P2 VS2 -.90 TEH TEC.610 SBAY2 223 C 10 l l l l 115 140.40 40 PCT 16 P2 BW1.83 TEH TEC.610 SBAY2 223 C 11 l l l l 116 141.27 98 PCT 11 P2 VS2.72 TEH TEC.610 SBAY2 221 C 198 l l l l 118 141.46 83 PCT 16 P2 VS3 -.76 TEH TEC.610 SBAY2 221 C 199 l l l
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
l ROW COL VOLTS DEG IND PER CRLEN CHN LOCN INCH1 INCH2 BEGT ENDT PDIA PTYPE CAL L IDX UTIL1 UTIL2l
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
45 ST Max
SG - 32 Calls of Interest Palo Verde 3 U3R20 PVNGS3 20180401 04/20/2018 13:40:22
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
l ROW COL VOLTS DEG IND PER CRLEN CHN LOCN INCH1 INCH2 BEGT ENDT PDIA PTYPE CAL L IDX UTIL1 UTIL2l
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
l 156 141.24 141 PCT 10 P2 BW1 -.90 TEH TEC.610 SBAY2 219 C 48 l l l l 45 142.29 105 PCT 10 P2 BW1 -.71 TEH TEC.610 SBAY2 212 C 11 l l l l 47 142.31 63 PCT 10 P2 BW1 -.68 TEH TEC.610 SBAY2 212 C 12 l l l l 55 142.32 126 PCT 10 P2 09H.75 TEH TEC.610 SBAY2 212 C 57 l l l l 77 142.29 89 PCT 11 P2 VS2 -.81 TEH TEC.610 SBAY2 215 C 112 l l l l 81 142.28 87 PCT 11 P2 VS2 -.88 TEH TEC.610 SBAY2 215 C 114 l l l l 89 142.37 71 PCT 13 P2 BW1 -.12 TEH TEC.610 SBAY2 215 C 118 l l l l 157 142.42 130 PCT 14 P2 VS1 -.74 TEH TEC.610 SBAY2 219 C 15 l l 157 142.28 114 PCT 11 P2 VS4 -.75 TEH TEC.610 SBAY2 219 C 15 l l 157 142.40 123 PCT 14 P2 VS5 -.93 TEH TEC.610 SBAY2 219 C 15 l l 157 142.29 151 PCT 11 P2 BW2.85 TEH TEC.610 SBAY2 219 C 15 l l 157 142.29 134 PCT 11 P2 04C.79 TEH TEC.610 SBAY2 219 C 15 l l l l 48 143.25 99 PCT 10 P2 BW2.90 TEH TEC.610 SBAY2 207 C 237 l l l l 80 143.29 83 PCT 11 P2 VS2 -.71 TEH TEC.610 SBAY2 215 C 102 l l l l 84 143.24 80 PCT 10 P2 VS2 -.78 TEH TEC.610 SBAY2 215 C 100 l l l l 94 143.32 126 PCT 12 P2 10H.76 TEH TEC.610 SBAY2 215 C 95 l l l l 98 143.24 100 PCT 10 P2 10H.86 TEH TEC.610 SBAY2 215 C 93 l l l l 102 143.28 82 PCT 11 P2 BW1 -1.23 TEH TEC.610 SBAY2 215 C 91 l l l l 156 143.20 122 PCT 8 P2 06H.84 TEH TEC.610 SBAY2 219 C 14 l l 156 143.24 75 PCT 10 P2 03C.02 TEH TEC.610 SBAY2 219 C 14 l l l l 89 144.41 75 PCT 13 P2 BW1.40 TEH TEC.610 SBAY2 214 C 57 l l l l 91 144.28 78 PCT 10 P2 VS2 -.80 TEH TEC.610 SBAY2 214 C 56 l l l l 113 144.25 111 PCT 10 P2 06H.86 TEH TEC.610 SBAY2 221 C 174 l l l l 68 145.52 133 PCT 15 P2 09H.53 TEH TEC.610 SBAY2 214 C 26 l l l l 118 145.26 89 PCT 11 P2 VS3 -.81 TEH TEC.610 SBAY2 221 C 158 l
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
l ROW COL VOLTS DEG IND PER CRLEN CHN LOCN INCH1 INCH2 BEGT ENDT PDIA PTYPE CAL L IDX UTIL1 UTIL2l
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
46 ST Max
SG - 32 Calls of Interest Palo Verde 3 U3R20 PVNGS3 20180401 04/20/2018 13:40:22
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
l ROW COL VOLTS DEG IND PER CRLEN CHN LOCN INCH1 INCH2 BEGT ENDT PDIA PTYPE CAL L IDX UTIL1 UTIL2l
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
l l l 132 145.45 90 PCT 16 P2 VS2.77 TEH TEC.610 SBAY2 221 C 165 l l l l 134 145.29 126 PCT 12 P2 BW1 -.78 TEH TEC.610 SBAY2 221 C 166 l l l l 154 145.31 154 PCT 12 P2 11H.66 TEH TEC.610 SBAY2 219 C 12 l l l l 71 146.29 108 PCT 11 P2 VS3 -.99 TEH TEC.610 SBAY2 213 C 66 l l l l 79 146.28 115 PCT 11 P2 VS4 -.73 TEH TEC.610 SBAY2 213 C 62 l l l l 87 146.26 127 PCT 11 P2 VS2 -.61 TEH TEC.610 SBAY2 213 C 58 l l l l 95 146.26 139 PCT 11 P2 10H.47 TEH TEC.610 SBAY2 213 C 54 l l l l 103 146.27 140 PCT 11 P2 10H.77 TEH TEC.610 SBAY2 213 C 50 l l l l 107 146.34 85 PCT 13 P2 VS2 -.80 TEH TEC.610 SBAY2 213 C 48 l l l l 145 146.31 101 PCT 10 P2 VS3.36 TEH TEC.610 SBAY2 222 C 160 l l l l 84 147.34 129 PCT 13 P2 BW1 -.76 TEH TEC.610 SBAY2 213 C 35 l l l l 88 147.34 128 PCT 13 P2 06H.76 TEH TEC.610 SBAY2 213 C 37 l l l l 106 147.32 77 PCT 12 P2 VS4 -.63 TEH TEC.610 SBAY2 213 C 45 l l l l 144 147.15 149 PCT 6 P2 VS3.70 TEH TEC.610 SBAY2 222 C 159 l l l l 152 147.23 144 PCT 9 P2 04H.81 TEH TEC.610 SBAY2 219 C 10 l l 152 147.31 92 PCT 12 P2 03C.07 TEH TEC.610 SBAY2 219 C 10 l l l l 93 148.31 28 PCT 10 P2 10H.75 TEH TEC.610 SBAY2 214 C 11 l l l l 115 148.25 48 PCT 10 P2 BW1.54 TEH TEC.610 SBAY2 221 C 151 l l l l 125 148.34 50 PCT 13 P2 BW1.85 TEH TEC.610 SBAY2 221 C 146 l l l l 48 149.34 156 PCT 13 P2 BW1.97 TEH TEC.610 SBAY2 207 C 179 l l l l 72 149.51 134 PCT 15 P2 09H.78 TEH TEC.610 SBAY2 212 C 187 l l l l 86 149.30 62 PCT 10 P2 VS2 -.74 TEH TEC.610 SBAY2 212 C 194 l l l
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
l ROW COL VOLTS DEG IND PER CRLEN CHN LOCN INCH1 INCH2 BEGT ENDT PDIA PTYPE CAL L IDX UTIL1 UTIL2l
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
47 ST Max
SG - 32 Calls of Interest Palo Verde 3 U3R20 PVNGS3 20180401 04/20/2018 13:40:22
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
l ROW COL VOLTS DEG IND PER CRLEN CHN LOCN INCH1 INCH2 BEGT ENDT PDIA PTYPE CAL L IDX UTIL1 UTIL2l
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
l 126 149.29 64 PCT 12 P2 BW1.51 TEH TEC.610 SBAY2 221 C 128 l l l l 128 149.32 71 PCT 13 P2 BW1.50 TEH TEC.610 SBAY2 221 C 129 l l l l 134 149.25 49 PCT 10 P2 BW1 -.88 TEH TEC.610 SBAY2 221 C 132 l l l l 47 150.27 91 PCT 11 P2 BW1.88 TEH TEC.610 SBAY2 207 C 161 l l l l 57 150.28 122 PCT 11 P2 VS3.83 TEH TEC.610 SBAY2 207 C 166 l l l l 59 150.30 77 PCT 11 P2 VS3.97 TEH TEC.610 SBAY2 207 C 167 l l l l 71 150.25 106 PCT 10 P2 VS2 -.73 TEH TEC.610 SBAY2 213 C 23 l l l l 83 150.35 119 PCT 13 P2 VS2 -.81 TEH TEC.610 SBAY2 213 C 17 l l l l 95 150.29 135 PCT 12 P2 09H.83 TEH TEC.610 SBAY2 213 C 11 l l 95 150.29 72 PCT 12 P2 VS3 -.99 TEH TEC.610 SBAY2 213 C 11 l l l l 101 150.30 121 PCT 12 P2 VS3 -.98 TEH TEC.610 SBAY2 213 C 8 l l l l 133 150.25 36 PCT 8 P2 BW1.91 TEH TEC.610 SBAY2 222 C 131 l l l l 80 151.33 82 PCT 13 P2 VS2 -.72 TEH TEC.610 SBAY2 211 C 200 l l l l 90 151.28 150 PCT 11 P2 BW1 -.84 TEH TEC.610 SBAY2 211 C 205 l l l l 102 151.28 85 PCT 11 P2 VS3 1.01 TEH TEC.610 SBAY2 211 C 211 l l l l 116 151.31 83 PCT 10 P2 VS3 -.71 TEH TEC.610 SBAY2 222 C 114 l l l l 128 151.34 113 PCT 11 P2 VS3 -1.07 TEH TEC.610 SBAY2 222 C 120 l l l l 23 152.31 53 PCT 10 P2 BW1 -.91 TEH TEC.610 SBAY2 208 C 93 l l l l 45 152.19 100 PCT 7 P2 BW1 -.78 TEH TEC.610 SBAY2 208 C 104 l l l l 51 152.51 75 PCT 14 P2 09H.83 TEH TEC.610 SBAY2 208 C 107 l l l l 85 152.32 76 PCT 11 P2 VS2 -.89 TEH TEC.610 SBAY2 214 C 79 l l l l 89 152.28 64 PCT 10 P2 VS3 -1.09 TEH TEC.610 SBAY2 214 C 81 l l l l 95 152.34 47 PCT 11 P2 10H.68 TEH TEC.610 SBAY2 214 C 84 l
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
l ROW COL VOLTS DEG IND PER CRLEN CHN LOCN INCH1 INCH2 BEGT ENDT PDIA PTYPE CAL L IDX UTIL1 UTIL2l
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
48 ST Max
SG - 32 Calls of Interest Palo Verde 3 U3R20 PVNGS3 20180401 04/20/2018 13:40:22
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
l ROW COL VOLTS DEG IND PER CRLEN CHN LOCN INCH1 INCH2 BEGT ENDT PDIA PTYPE CAL L IDX UTIL1 UTIL2l
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
l l l 133 152.24 101 PCT 10 P2 BW1 -1.36 TEH TEC.610 SBAY2 221 C 108 l l l l 80 153.47 76 PCT 14 P2 VS2 -.60 TEH TEC.610 SBAY2 214 C 106 l l l l 102 153.35 85 PCT 11 P2 VS3.77 TEH TEC.610 SBAY2 214 C 95 l l l l 110 153.28 118 PCT 11 P2 06H.76 TEH TEC.610 SBAY2 221 C 90 l l l l 136 153.33 132 PCT 13 P2 BW1.39 TEH TEC.610 SBAY2 221 C 103 l l l l 67 154.26 90 PCT 11 P2 BW1.51 TEH TEC.610 SBAY2 213 C 70 l l l l 89 154.33 99 PCT 13 P2 VS3 -.91 TEH TEC.610 SBAY2 213 C 81 l l l l 91 154.30 30 PCT 12 P2 BW1.90 TEH TEC.610 SBAY2 213 C 82 l l l l 78 155.25 50 PCT 10 P2 VS2.87 TEH TEC.610 SBAY2 213 C 107 l l l l 96 155.36 93 PCT 13 P2 10H.64 TEH TEC.610 SBAY2 213 C 98 l l 96 155.24 94 PCT 10 P2 VS2.80 TEH TEC.610 SBAY2 213 C 98 l l l l 106 155.30 90 PCT 12 P2 BW1 -1.32 TEH TEC.610 SBAY2 213 C 93 l l l l 138 155.28 120 PCT 10 P2 BW1 -.59 TEH TEC.610 SBAY2 220 C 38 l l l l 71 156.28 76 PCT 10 P2 VS2.72 TEH TEC.610 SBAY2 214 C 116 l l l l 87 156.31 76 PCT 10 P2 VS3 -.84 TEH TEC.610 SBAY2 214 C 124 l l l l 91 156.40 135 PCT 12 P2 10H -1.00 TEH TEC.610 SBAY2 214 C 126 l l l l 101 156.28 33 PCT 10 P2 10H -.77 TEH TEC.610 SBAY2 214 C 131 l l l l 113 156.36 75 PCT 14 P2 BW1 1.18 TEH TEC.610 SBAY2 221 C 88 l l l l 115 156.26 45 PCT 11 P2 BW1.94 TEH TEC.610 SBAY2 221 C 87 l l l l 119 156.23 72 PCT 10 P2 06H -.83 TEH TEC.610 SBAY2 221 C 85 l l l l 131 156.24 132 PCT 10 P2 BW1 -.88 TEH TEC.610 SBAY2 221 C 79 l l l l 6 157.34 150 PCT 13 P2 08H.58 TEH TEC.610 SBAY2 225 C 121 l l l
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
l ROW COL VOLTS DEG IND PER CRLEN CHN LOCN INCH1 INCH2 BEGT ENDT PDIA PTYPE CAL L IDX UTIL1 UTIL2l
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
49 ST Max
SG - 32 Calls of Interest Palo Verde 3 U3R20 PVNGS3 20180401 04/20/2018 13:40:22
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
l ROW COL VOLTS DEG IND PER CRLEN CHN LOCN INCH1 INCH2 BEGT ENDT PDIA PTYPE CAL L IDX UTIL1 UTIL2l
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
l 88 157.32 63 PCT 11 P2 BW1 -.64 TEH TEC.610 SBAY2 214 C 146 l l l l 96 157.33 130 PCT 11 P2 09H.69 TEH TEC.610 SBAY2 214 C 142 l l l l 134 157.24 96 PCT 10 P2 BW1 -1.12 TEH TEC.610 SBAY2 221 C 76 l l l l 142 157.40 141 PCT 14 P2 11H.70 TEH TEC.610 SBAY2 217 C 204 l l l l 77 158.37 102 PCT 14 P2 VS2.76 TEH TEC.610 SBAY2 213 C 119 l l l l 86 159.31 99 PCT 12 P2 VS3 1.01 TEH TEC.610 SBAY2 213 C 147 l l l l 102 159.31 111 PCT 12 P2 VS2 -.71 TEH TEC.610 SBAY2 213 C 139 l l l l 43 160.31 57 PCT 10 P2 BW2.85 TEH TEC.610 SBAY2 206 C 243 l l l l 85 160.35 89 PCT 11 P2 VS2 -.79 TEH TEC.610 SBAY2 214 C 167 l l l l 87 160.55 86 PCT 16 P2 VS3 -.88 TEH TEC.610 SBAY2 214 C 168 l l l l 89 160.30 90 PCT 10 P2 BW1 -.02 TEH TEC.610 SBAY2 214 C 169 l l l l 117 160.60 110 PCT 19 P2 VS3 -.81 TEH TEC.610 SBAY2 221 C 60 l l l l 125 160.23 100 PCT 10 P2 06H.80 TEH TEC.610 SBAY2 221 C 56 l l l l 66 161.32 44 PCT 10 P2 VS3 -.86 TEH TEC.610 SBAY2 216 C 18 l l l l 98 161.28 94 PCT 10 P2 10H.73 TEH TEC.610 SBAY2 214 C 186 l l l l 104 161.33 69 PCT 11 P2 VS3.90 TEH TEC.610 SBAY2 214 C 183 l l l l 130 161.23 112 PCT 10 P2 BW1 -.78 TEH TEC.610 SBAY2 221 C 52 l l l l 75 162.31 105 PCT 12 P2 VS3 1.04 TEH TEC.610 SBAY2 213 C 162 l l l l 85 162.36 107 PCT 13 P2 VS2 -.71 TEH TEC.610 SBAY2 213 C 166 l l l l 93 162.28 85 PCT 11 P2 10H -.73 TEH TEC.610 SBAY2 213 C 170 l l l l 52 163.33 122 PCT 11 P2 09H.85 TEH TEC.610 SBAY2 206 C 206 l l l l 76 163.48 132 PCT 16 P2 09C -1.04 TEH TEC.610 SBAY2 215 C 14 l l l
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
l ROW COL VOLTS DEG IND PER CRLEN CHN LOCN INCH1 INCH2 BEGT ENDT PDIA PTYPE CAL L IDX UTIL1 UTIL2l
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
50 ST Max
SG - 32 Calls of Interest Palo Verde 3 U3R20 PVNGS3 20180401 04/20/2018 13:40:22
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
l ROW COL VOLTS DEG IND PER CRLEN CHN LOCN INCH1 INCH2 BEGT ENDT PDIA PTYPE CAL L IDX UTIL1 UTIL2l
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
l 84 163.30 106 PCT 11 P2 VS2 -.83 TEH TEC.610 SBAY2 215 C 10 l l l l 77 164.39 154 PCT 11 P2 BW2.41 TEH TEC.610 SBAY2 216 C 35 l l l l 93 164.58 96 PCT 15 P2 VS2.71 TEH TEC.610 SBAY2 216 C 27 l l l l 113 164.27 131 PCT 11 P2 VS3 -1.15 TEH TEC.610 SBAY2 221 C 40 l l l l 133 164.32 94 PCT 12 P2 VS5 -.58 TEH TEC.610 SBAY2 219 C 35 l l l l 72 165.43 122 PCT 12 P2 BW2 -.79 TEH TEC.610 SBAY2 216 C 44 l l l l 116 165.32 78 PCT 12 P2 VS4 -.67 TEH TEC.610 SBAY2 221 C 33 l l l l 120 165.26 127 PCT 10 P2 10H.79 TEH TEC.610 SBAY2 218 C 158 l l l l 67 166.27 94 PCT 11 P2 BW1.35 TEH TEC.610 SBAY2 215 C 41 l l l l 75 166.27 132 PCT 11 P2 VS2.74 TEH TEC.610 SBAY2 215 C 37 l l l l 77 166.36 120 PCT 13 P2 BW2.80 TEH TEC.610 SBAY2 215 C 36 l l l l 85 166.30 97 PCT 11 P2 VS2.80 TEH TEC.610 SBAY2 215 C 32 l l l l 87 166.26 129 PCT 10 P2 VS3 -.81 TEH TEC.610 SBAY2 215 C 31 l l l l 89 166 1.67 98 WAR.39 P7 VS3 -.98 VS3 TEH.610 ZYAX2 26 H 48 l l 89 166.29 118 PCT 11 P2 09H.81 TEH TEC.610 SBAY2 215 C 30 l l 89 166.25 72 PCT 10 P2 BW1 1.06 TEH TEC.610 SBAY2 215 C 30 l l 89 166.58 107 PCT 18 P2 VS3 -1.04 TEH TEC.610 SBAY2 215 C 30 l l 89 166.38 109 PCT 13 P2 VS3.80 TEH TEC.610 SBAY2 215 C 30 l l 89 166.29 116 PCT 11 P2 VS4 -.62 TEH TEC.610 SBAY2 215 C 30 l l l l 93 166.30 123 PCT 11 P2 VS2.57 TEH TEC.610 SBAY2 215 C 28 l l l l 109 166.25 99 PCT 10 P2 VS2 -.82 TEH TEC.610 SBAY2 215 C 20 l l 109 166.46 105 PCT 15 P2 VS3 -1.33 TEH TEC.610 SBAY2 215 C 20 l l l l 113 166.31 131 PCT 10 P2 BW1.82 TEH TEC.610 SBAY2 222 C 37 l l l l 72 167.28 101 PCT 11 P2 VS2 -.78 TEH TEC.610 SBAY2 215 C 45 l l l l 80 167.27 106 PCT 10 P2 VS2 -.75 TEH TEC.610 SBAY2 215 C 49 l l 80 167.35 118 PCT 13 P2 BW2.77 TEH TEC.610 SBAY2 215 C 49 l
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
l ROW COL VOLTS DEG IND PER CRLEN CHN LOCN INCH1 INCH2 BEGT ENDT PDIA PTYPE CAL L IDX UTIL1 UTIL2l
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
51 ST Max
SG - 32 Calls of Interest Palo Verde 3 U3R20 PVNGS3 20180401 04/20/2018 13:40:22
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
l ROW COL VOLTS DEG IND PER CRLEN CHN LOCN INCH1 INCH2 BEGT ENDT PDIA PTYPE CAL L IDX UTIL1 UTIL2l
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
l l l 96 167.25 96 PCT 10 P2 VS3 -.96 TEH TEC.610 SBAY2 215 C 57 l l l l 128 167.36 139 PCT 13 P2 10H.73 TEH TEC.610 SBAY2 219 C 28 l l 128 167 NDF P6 TSC.71 01C TEC.610 ZYAX2 227 C 62 l l l l 73 168.32 85 PCT 10 P2 BW2 -1.05 TEH TEC.610 SBAY2 216 C 81 l l l l 79 168.65 79 PCT 16 P2 BW2.70 TEH TEC.610 SBAY2 216 C 78 l l l l 101 168.41 91 PCT 12 P2 VS2 -.95 TEH TEC.610 SBAY2 216 C 67 l l l l 103 168.34 130 PCT 10 P2 BW1 -1.31 TEH TEC.610 SBAY2 216 C 66 l l 103 168.35 48 PCT 10 P2 VS3 -.91 TEH TEC.610 SBAY2 216 C 66 l l l l 105 168.35 83 PCT 10 P2 BW1 -.56 TEH TEC.610 SBAY2 216 C 65 l l l l 24 169.30 95 PCT 11 P2 BW2 1.15 TEH TEC.610 SBAY2 205 C 162 l l l l 57 170.31 99 PCT 12 P2 09H.67 TEH TEC.610 SBAY2 205 C 137 l l l l 77 170.26 74 PCT 10 P2 BW2 -.81 TEH TEC.610 SBAY2 215 C 80 l l l l 85 170.31 31 PCT 12 P2 BW1.48 TEH TEC.610 SBAY2 215 C 76 l l l l 87 170.49 95 PCT 16 P2 VS3 -1.20 TEH TEC.610 SBAY2 215 C 75 l l l l 101 170.31 114 PCT 12 P2 BW1 -.77 TEH TEC.610 SBAY2 215 C 68 l l l l 105 170.30 140 PCT 11 P2 BW1 -.59 TEH TEC.610 SBAY2 215 C 66 l l l l 119 170.37 140 PCT 13 P2 10H.71 TEH TEC.610 SBAY2 217 C 174 l l l l 16 171.40 99 PCT 12 P2 04C.83 TEH TEC.610 SBAY2 206 C 111 l l l l 46 171.22 25 PCT 8 P2 BW1 -.74 TEH TEC.610 SBAY2 206 C 96 l l l l 96 171.25 95 PCT 10 P2 10H.74 TEH TEC.610 SBAY2 215 C 200 l l l l 102 171.52 101 PCT 17 P2 VS3.89 TEH TEC.610 SBAY2 215 C 203 l l l l 104 171.30 108 PCT 11 P2 VS2 -.72 TEH TEC.610 SBAY2 215 C 204 l l l l 118 171.29 134 PCT 11 P2 10H -.79 TEH TEC.610 SBAY2 217 C 173 l
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
l ROW COL VOLTS DEG IND PER CRLEN CHN LOCN INCH1 INCH2 BEGT ENDT PDIA PTYPE CAL L IDX UTIL1 UTIL2l
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
52 ST Max
SG - 32 Calls of Interest Palo Verde 3 U3R20 PVNGS3 20180401 04/20/2018 13:40:22
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
l ROW COL VOLTS DEG IND PER CRLEN CHN LOCN INCH1 INCH2 BEGT ENDT PDIA PTYPE CAL L IDX UTIL1 UTIL2l
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
l l l 59 172.30 81 PCT 10 P2 BW2.47 TEH TEC.610 SBAY2 206 C 82 l l l l 75 172.74 113 PCT 18 P2 VS4 -.58 TEH TEC.610 SBAY2 216 C 200 l l l l 109 172.67 123 PCT 17 P2 VS3 -.61 TEH TEC.610 SBAY2 216 C 183 l l l l 104 173.14 139 PCT 8 P2 09H -.33 TEH TEC.610 SBAY2 218 C 26 l l l l 122 173.28 103 PCT 11 P2 VS3 -.76 TEH TEC.610 SBAY2 217 C 166 l l l l 15 174.40 109 PCT 14 P2 06C.76 TEH TEC.610 SBAY2 205 C 58 l l l l 43 174.49 131 PCT 16 P2 08C.76 TEH TEC.610 SBAY2 205 C 72 l l l l 87 174.30 89 PCT 11 P2 VS2 -.87 TEH TEC.610 SBAY2 215 C 218 l l l l 111 174.32 99 PCT 11 P2 10H.67 TEH TEC.610 SBAY2 218 C 149 l l l l 119 174.31 111 PCT 12 P2 VS3 -1.24 TEH TEC.610 SBAY2 219 C 19 l l l l 42 175.39 134 PCT 12 P2 08C.88 TEH TEC.610 SBAY2 206 C 40 l l l l 56 175.65 104 PCT 17 P2 BW1 -1.75 TEH TEC.610 SBAY2 206 C 33 l l l l 72 175.30 120 PCT 12 P2 VS2.84 TEH TEC.610 SBAY2 217 C 13 l l l l 86 175.09 112 NQI 3 VS3 4.88 TEH TEC.610 SBAY2 217 C 20 l l 86 175 NDF P28 VS3 4.88 VS3 TEC.610 ZYAX2 227 C 55 l l l l 88 175.46 130 PCT 16 P2 VS3.62 TEH TEC.610 SBAY2 217 C 21 l l l l 104 175.28 108 PCT 11 P2 VS4 -.72 TEH TEC.610 SBAY2 217 C 29 l l l l 114 175 1.35 115 PCT 29 P2 VS4 -.85 TEH TEC.610 SBAY2 217 C 169 l l 114 175 1.62 77 WAR.48 P20 VS4 -.73 VS3 TEC.610 ZYAX2 227 C 61 l l l l 65 176.32 139 PCT 10 P2 BW1 1.04 TEH TEC.610 SBAY2 206 C 28 l l l l 67 176.37 74 PCT 12 P2 VS3 -.82 TEH TEC.610 SBAY2 218 C 50 l l l l 89 176.27 72 PCT 10 P2 VS2 -.86 TEH TEC.610 SBAY2 218 C 39 l l l l 109 176.28 121 PCT 10 P2 BW1 -.15 TEH TEC.610 SBAY2 218 C 29 l
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
l ROW COL VOLTS DEG IND PER CRLEN CHN LOCN INCH1 INCH2 BEGT ENDT PDIA PTYPE CAL L IDX UTIL1 UTIL2l
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
53 ST Max
SG - 32 Calls of Interest Palo Verde 3 U3R20 PVNGS3 20180401 04/20/2018 13:40:22
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
l ROW COL VOLTS DEG IND PER CRLEN CHN LOCN INCH1 INCH2 BEGT ENDT PDIA PTYPE CAL L IDX UTIL1 UTIL2l
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
l 109 176.44 106 PCT 14 P2 BW1 1.02 TEH TEC.610 SBAY2 218 C 29 l l l l 98 177.14 125 PCT 9 P2 10H.86 TEH TEC.610 SBAY2 218 C 66 l l l l 106 177.12 118 PCT 9 P2 09H.69 TEH TEC.610 SBAY2 218 C 70 l l l l 83 178.45 95 PCT 15 P2 VS2 -.78 TEH TEC.610 SBAY2 217 C 45 l l l l 87 178.33 100 PCT 12 P2 VS3 -.99 TEH TEC.610 SBAY2 217 C 43 l l l l 95 178.36 77 PCT 13 P2 VS2 -.91 TEH TEC.610 SBAY2 217 C 39 l l l l 99 178.36 107 PCT 13 P2 VS3 -1.07 TEH TEC.610 SBAY2 217 C 37 l l l l 101 178.24 101 PCT 10 P2 VS2 -.64 TEH TEC.610 SBAY2 217 C 36 l l 101 178.24 110 PCT 10 P2 VS3.85 TEH TEC.610 SBAY2 217 C 36 l l l l 103 178.28 110 PCT 11 P2 VS3.75 TEH TEC.610 SBAY2 217 C 35 l l l l 113 178 1.55 97 WAR.22 P8 VS3 -1.02 VS3 TEH.610 ZYAX2 26 H 54 l l 113 178.67 120 PCT 20 P2 VS3 -1.29 TEH TEC.610 SBAY2 217 C 158 l l 113 178.14 144 NQI 3 09C 14.32 TEH TEC.610 SBAY2 217 C 158 l l 113 178 NDF P32 09C 14.32 10C TEC.610 ZYAX2 227 C 60 l l l l 76 179.32 122 PCT 12 P2 VS2.67 TEH TEC.610 SBAY2 217 C 59 l l l l 80 179.32 92 PCT 12 P2 VS2 -.74 TEH TEC.610 SBAY2 217 C 61 l l l l 90 179.24 74 PCT 10 P2 VS2 -.72 TEH TEC.610 SBAY2 217 C 66 l l l l 96 179.34 112 PCT 13 P2 VS2.68 TEH TEC.610 SBAY2 217 C 69 l l l l 69 180 TBP P2 VS3 -.86 TEC TEH.610 SBAY2 24 H 46 l l 69 180 2.99 100 WAR.45 P7 VS3 -.91 VS3 TEH.610 ZYAX2 26 H 51 l l 69 180 1.84 111 PCT 32 P2 VS3 -.86 TEH TEC.610 SBAY2 218 C 95 l l l l 75 180.38 131 PCT 13 P2 BW1.97 TEH TEC.610 SBAY2 218 C 92 l l l l 97 180.54 79 PCT 16 P2 VS3 -.92 TEH TEC.610 SBAY2 218 C 81 l l l l 99 180.27 122 PCT 10 P2 VS3 -1.28 TEH TEC.610 SBAY2 218 C 75 l l l l 56 181.32 148 PCT 12 P2 BW1 -1.52 TEH TEC.610 SBAY2 203 C 241 l l l
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
l ROW COL VOLTS DEG IND PER CRLEN CHN LOCN INCH1 INCH2 BEGT ENDT PDIA PTYPE CAL L IDX UTIL1 UTIL2l
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
54 ST Max
SG - 32 Calls of Interest Palo Verde 3 U3R20 PVNGS3 20180401 04/20/2018 13:40:22
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
l ROW COL VOLTS DEG IND PER CRLEN CHN LOCN INCH1 INCH2 BEGT ENDT PDIA PTYPE CAL L IDX UTIL1 UTIL2l
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
l 72 181.23 131 PCT 9 P2 VS3 1.11 TEH TEC.610 SBAY2 218 C 100 l l l l 74 181.45 32 PCT 14 P2 VS4.78 TEH TEC.610 SBAY2 218 C 101 l l l l 76 181.26 61 PCT 10 P2 VS2.97 TEH TEC.610 SBAY2 218 C 102 l l l l 84 181.32 129 PCT 12 P2 VS2 -.61 TEH TEC.610 SBAY2 215 C 162 l l l l 86 181.29 62 PCT 10 P2 VS2 -.65 TEH TEC.610 SBAY2 218 C 105 l l l l 49 182.29 97 PCT 11 P2 09H -1.72 TEH TEC.610 SBAY2 203 C 228 l l l l 73 182.32 109 PCT 12 P2 VS3.41 TEH TEC.610 SBAY2 217 C 102 l l l l 75 182.36 139 PCT 13 P2 BW1.90 TEH TEC.610 SBAY2 217 C 101 l l 75 182.25 106 PCT 10 P2 VS3.88 TEH TEC.610 SBAY2 217 C 101 l l l l 79 182.68 71 PCT 17 P2 VS4 -.58 TEH TEC.610 SBAY2 216 C 147 l l l l 83 182.27 98 PCT 11 P2 VS2 -.80 TEH TEC.610 SBAY2 215 C 161 l l l l 85 182.27 48 PCT 11 P2 VS3 -.94 TEH TEC.610 SBAY2 217 C 98 l l l l 87 182.26 75 PCT 10 P2 VS2 -.84 TEH TEC.610 SBAY2 217 C 97 l l 87 182.25 87 PCT 10 P2 VS3 -.97 TEH TEC.610 SBAY2 217 C 97 l l l l 97 182.40 110 PCT 13 P2 VS2 -.88 TEH TEC.610 SBAY2 218 C 77 l l l l 99 182.28 123 PCT 11 P2 VS3 -1.35 TEH TEC.610 SBAY2 217 C 91 l l l l 101 182.38 120 PCT 14 P2 VS3 -1.21 TEH TEC.610 SBAY2 217 C 87 l l l l 84 183.25 71 PCT 10 P2 VS2 -.65 TEH TEC.610 SBAY2 217 C 113 l l 84 183.36 128 PCT 13 P2 VS3.74 TEH TEC.610 SBAY2 217 C 113 l l l l 86 183.23 101 PCT 10 P2 VS2 -.77 TEH TEC.610 SBAY2 217 C 114 l l l l 92 183.27 137 PCT 11 P2 BW2 -.85 TEH TEC.610 SBAY2 217 C 117 l l l l 102 183 1.85 102 WAR.42 P32 VS3 -1.24 VS3 TEH.610 ZYAX2 26 H 53 l l 102 183.87 116 PCT 23 P2 VS3 -1.26 TEH TEC.610 SBAY2 217 C 85 l l l l 65 184.31 77 PCT 12 P2 09H -.79 TEH TEC.610 SBAY2 203 C 188 l l l
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
l ROW COL VOLTS DEG IND PER CRLEN CHN LOCN INCH1 INCH2 BEGT ENDT PDIA PTYPE CAL L IDX UTIL1 UTIL2l
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
55 ST Max
SG - 32 Calls of Interest Palo Verde 3 U3R20 PVNGS3 20180401 04/20/2018 13:40:22
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
l ROW COL VOLTS DEG IND PER CRLEN CHN LOCN INCH1 INCH2 BEGT ENDT PDIA PTYPE CAL L IDX UTIL1 UTIL2l
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
l 85 184.28 135 PCT 10 P2 09H.58 TEH TEC.610 SBAY2 218 C 112 l l l l 87 184.32 88 PCT 11 P2 VS2 -.65 TEH TEC.610 SBAY2 218 C 111 l l l l 89 184.29 67 PCT 10 P2 VS2 -.74 TEH TEC.610 SBAY2 218 C 110 l l l l 70 185.31 94 PCT 11 P2 VS2 -.47 TEH TEC.610 SBAY2 218 C 122 l l l l 80 185.56 111 PCT 17 P2 VS4.75 TEH TEC.610 SBAY2 215 C 158 l l l l 71 186.27 94 PCT 11 P2 VS2.52 TEH TEC.610 SBAY2 217 C 126 l l 71 186.23 99 PCT 10 P2 VS4 -.71 TEH TEC.610 SBAY2 217 C 126 l l l l 73 186.26 112 PCT 10 P2 VS3 -.84 TEH TEC.610 SBAY2 217 C 125 l l l l 77 186 1.59 115 WAR.59 P24 VS3 1.07 VS3 TEH.610 ZYAX2 26 H 52 l l 77 186.67 124 PCT 20 P2 VS3.64 TEH TEC.610 SBAY2 217 C 124 l l l l 66 187.39 126 PCT 14 P2 VS3 -.74 TEH TEC.610 SBAY2 217 C 129 l l l l 76 187.26 115 PCT 10 P2 VS2 -.84 TEH TEC.610 SBAY2 217 C 133 l l l l 80 187.35 103 PCT 13 P2 VS2 -.58 TEH TEC.610 SBAY2 217 C 134 l l 80 187.40 119 PCT 14 P2 VS3 -.72 TEH TEC.610 SBAY2 217 C 134 l l 80 187.63 112 PCT 19 P2 VS4.87 TEH TEC.610 SBAY2 217 C 134 l l l l 86 187 1.00 106 PCT 25 P2 VS4.94 TEH TEC.610 SBAY2 217 C 136 l l 86 187 2.72 288 WAR.40 P28 VS4.54 VS3 TEC.610 ZYAX2 227 C 58 l l l l 75 188.29 73 PCT 10 P2 VS2 -.79 TEH TEC.610 SBAY2 218 C 130 l l l l 77 188.27 98 PCT 11 P2 VS3 -1.01 TEH TEC.610 SBAY2 215 C 155 l l l l 81 188.65 135 PCT 16 P2 09H.74 TEH TEC.610 SBAY2 216 C 152 l l l l 89 188.28 124 PCT 11 P2 VS3 -1.02 TEH TEC.610 SBAY2 215 C 174 l l l l 78 189.38 78 PCT 11 P2 VS3 -.73 TEH TEC.610 SBAY2 216 C 151 l l l l 73 190.44 127 PCT 15 P2 BW1.92 TEH TEC.610 SBAY2 217 C 148 l l 73 190.34 95 PCT 13 P2 VS3 -.88 TEH TEC.610 SBAY2 217 C 148 l l l l 81 190.28 70 PCT 11 P2 VS4 -.88 TEH TEC.610 SBAY2 217 C 145 l l l
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
l ROW COL VOLTS DEG IND PER CRLEN CHN LOCN INCH1 INCH2 BEGT ENDT PDIA PTYPE CAL L IDX UTIL1 UTIL2l
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
56 ST Max
SG - 32 Calls of Interest Palo Verde 3 U3R20 PVNGS3 20180401 04/20/2018 13:40:22
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
l ROW COL VOLTS DEG IND PER CRLEN CHN LOCN INCH1 INCH2 BEGT ENDT PDIA PTYPE CAL L IDX UTIL1 UTIL2l
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
l 56 191.35 141 PCT 13 P2 BW1 -1.64 TEH TEC.610 SBAY2 203 C 169 l l l l 62 191.26 57 PCT 10 P2 VS3 -.81 TEH TEC.610 SBAY2 203 C 166 l l l l 47 194.24 59 PCT 10 P2 VS3 -.88 TEH TEC.610 SBAY2 203 C 36 l l l l 53 194.33 130 PCT 12 P2 09H.75 TEH TEC.610 SBAY2 203 C 39 l l l l 71 194.25 70 PCT 10 P2 VS3 -.78 TEH TEC.610 SBAY2 215 C 149 l l l l 50 197.25 88 PCT 10 P2 BW1 -.39 TEH TEC.610 SBAY2 201 C 41 l l l l 13 198.26 67 PCT 10 P2 BW1.68 TEH TEC.610 SBAY2 203 C 103 l l l l 31 198.24 86 PCT 10 P2 VS3 -.80 TEH TEC.610 SBAY2 201 C 28 l l l l 35 198.25 120 PCT 10 P2 VS3 -.75 TEH TEC.610 SBAY2 201 C 30 l l l l 41 198.27 63 PCT 11 P2 VS3 -.89 TEH TEC.610 SBAY2 201 C 33 l l l l 55 198.27 51 PCT 11 P2 01C -.92 TEH TEC.610 SBAY2 203 C 147 l l l l 6 203 NDF P21 TSH -.05 01H TEH.610 ZYAX2 27 H 85 l l 6 203 2.58 50 LNI P5 TSH -.05 TEH TEC.610 SBAY2 225 C 10 l
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
l ROW COL VOLTS DEG IND PER CRLEN CHN LOCN INCH1 INCH2 BEGT ENDT PDIA PTYPE CAL L IDX UTIL1 UTIL2l
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
Tubes: 1085 Records: 1404 57 ST Max
APPENDIX D PLI & PLP DATA SHEETS
SG - 31 SI PLP Calls Palo Verde 3 U3R20 PVNGS3 20180401 04/20/2018 07:49:59
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
l ROW COL VOLTS DEG IND PER CRLEN CHN LOCN INCH1 INCH2 BEGT ENDT PDIA PTYPE CAL L IDX UTIL1 UTIL2l
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
l 100 27.66 122 PLP 11 TSC 2.38 01C TEC.610 ZYAX2 32 C 6 SR l l l l 102 27 17.76 102 PLP 188 TSC 3.44 01C TEC.610 ZYAX2 32 C 5 SR l l l l 101 28 12.58 96 PLP 144 TSC 2.90 01C TEC.610 ZYAX2 34 C 19 SR l l l l 103 28 14.13 97 PLP 148 TSC 4.66 01C TEC.610 ZYAX2 34 C 18 HR l l l l 127 38 1.82 100 PLP 124 TSH 1.16 01H TEH.610 ZYAX2 32 H 15 HR l
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
l ROW COL VOLTS DEG IND PER CRLEN CHN LOCN INCH1 INCH2 BEGT ENDT PDIA PTYPE CAL L IDX UTIL1 UTIL2l
+----+----+---------+----+----+----+-------+-----+----+---------+---------+----+----+------+------+------+--+-----+---------+---------+
Tubes: 5 Records: 5 1 ST Max
APPENDIX E PLUG MAPS
S 3 Stake HL w/ 445" Stake and A Roll Plug HL & CL A
28 Roll Plug HL & CL A
- 53 Stay Rod A
- 77 Plugged Tube SG - 31 Tubes Plugged in U3R20 Palo Verde U3R20 PVNGS3 3RSG Westinghouse Electric Company LLC - ST Max 04/20/2018 07:15:41
S
S
S
5 5
10 10 15 15 20 20 25 25 30 30 35 35 40 40 45 45 50 50 55 55 60 60 65 65 70 70 75 75 80 80 85 85 90 90 95 95 100 100 105 105 110 110 115 115 120 120 125 125 130 130 135 135 140 140 145 145 150 150 155 155 160 160 165 165 170 170 175 175 180 180 185 185 190 190 195 195 200 200 5
5 10 10 15 15 20 20 25 25 30 30 35 35 40 40 45 45 50 50 55 55 60 60 65 65 70 70 75 75 80 80 85 85 90 90 95 95 100 100 105 105 110 110 115 115 120 120 125 125 130 130 135 135 140 140 145 145 150 150 155 155 160 160 165 165 170 170
S 2 Stake HL w/ 445" Stake and A Roll Plug HL & CL A
17 Roll Plug HL & CL A
- 53 Stay Rod A
- 101 Plugged Tube SG - 32 Tubes Plugged in U3R20 Palo Verde U3R20 PVNGS3 3RSG Westinghouse Electric Company LLC - ST Max 04/20/2018 07:16:53
S
S
5 5
10 10 15 15 20 20 25 25 30 30 35 35 40 40 45 45 50 50 55 55 60 60 65 65 70 70 75 75 80 80 85 85 90 90 95 95 100 100 105 105 110 110 115 115 120 120 125 125 130 130 135 135 140 140 145 145 150 150 155 155 160 160 165 165 170 170 175 175 180 180 185 185 190 190 195 195 200 200 5
5 10 10 15 15 20 20 25 25 30 30 35 35 40 40 45 45 50 50 55 55 60 60 65 65 70 70 75 75 80 80 85 85 90 90 95 95 100 100 105 105 110 110 115 115 120 120 125 125 130 130 135 135 140 140 145 145 150 150 155 155 160 160 165 165 170 170
APPENDIX F FORM NIS-1
APS NIS - 1 FORM OWNERS DATA REPORT FOR INSERVICE INSPECTIONS
- 2. PLANT PALO VERDE NUCLEAR GENERATING STATION 2a. ADDRESS 5801 SOUTH WINTERSBURG ROAD, TONOPAH, ARIZONA 85354
- 3. UNIT NUMBER 3
- 4. OWNERS CERTIFICATE OF AUTHORIZATION NONE
- 5. COMMERCIAL SERVICE DATE 1-8-88
- 6. COMPONENTS INSPECTED:
COMPONENT OR APPURTENANCE MANUFACTURER OR INSTALLER SERIAL NUMBER STATE OR PROVINCE NATIONAL BOARD NO 3MRCEE01A STEAM GENERATOR 31 Ansaldo 242 NA 191 3MRCEE01B STEAM GENERATOR 32 Ansaldo 243 NA 192
APS NIS - 1 BACK OWNERS DATA REPORT FOR INSERVICE INSPECTIONS
- 7. EXAM DATES April 2018
- 8. INSPECTION INTERVAL 1-11-08 to 1-10-18 (in 1 year extension)
- 9. ABSTRACT OF EXAMINATIONS. INCLUDE A LIST OF EXAMINATIONS AND A STATEMENT CONCERNING STATUS OF WORK REQUIRED FOR CURRENT INTERVAL.
Table 1 in the report summary section documents the number and type of each examination performed.
A summary of the tubes with indications of degradation is listed in Appendix B and C of this report for SG 31 and 32 respectively. The tubes identified on the attached page were plugged as a result of this examination.
The number of tubes plugged are as follows: SG 31 = 31 tubes SG 32 = 19 tubes WE CERTIFY THAT THE STATEMENTS MADE IN THIS REPORT ARE CORRECT AND THE EXAMINATIONS AND CORRECTIVE MEASURES TAKEN CONFORM TO THE RULES OF THE ASME CODE, SECTION XI.
SIGNED: ARIZONA PUBLIC SERVICE COMPANY BY ______________________________________________
CERTIFICATE OF INSERVICE INSPECTION I, THE UNDERSIGNED, HOLDING A VALID COMMISSION ISSUED BY THE NATIONAL BOARD OF BOILER AND PRESSURE VESSEL INSPECTORS AND THE STATE OF PROVINCE OF ARIZONA EMPLOYED BY THE HARTFORD STEAM BOILER INSPECTION AND INSURANCE COMPANY OF HARTFORD, CONNECTICUT HAVE INSPECTED THE COMPONENTS DESCRIBED IN THIS OWNERS REPORT DURING THE PERIOD 04-07-18 TO 10-18-18, AND STATE THAT TO THE BEST OF MY KNOWLEDGE AND BELIEF, THE OWNER HAS PERFORMED EXAMINATIONS AND TAKEN CORRECTIVE MEASURES DESCRIBED IN THIS OWNERS REPORT IN ACCORDANCE WITH THE REQUIREMENTS OF THE ASME CODE, SECTION XI. BY SIGNING THIS CERTIFICATE NEITHER THE INSPECTOR NOR HIS EMPLOYER MAKES ANY WARRANTY, EXPRESSED OR IMPLIED, CONCERNING THE EXAMINATIONS AND CORRECTIVE MEASURES DESCRIBED IN THIS OWNERS REPORT. FURTHERMORE, NEITHER THE INSPECTOR NOR HIS EMPLOYER SHALL BE LIABLE IN ANY MANNER FOR ANY PERSONAL INJURY OR PROPERTY DAMAGE OR A LOSS OF ANY KIND ARISING FROM OR CONNECTED WITH THIS INSPECTION.
INSPECTOR_______________________________________ COMMISSIONS: N.B. 9685 C, I, N, R Az 264 NATL BOARD, STATE, PROVINCE Hansen, Douglas B(Z41530)
Digitally signed by Hansen, Douglas B(Z41530)
DN: cn=Hansen, Douglas B(Z41530)
Date: 2018.10.19 07:59:13 -07'00'
- Hogstrom, Robert (YH2450)
Digitally signed by Hogstrom, Robert (YH2450)
DN: cn=Hogstrom, Robert (YH2450)
Date: 2018.10.19 08:07:12 -07'00'
APS NIS - 1 page 3 OWNERS DATA REPORT FOR INSERVICE INSPECTIONS U3R20 SG - 31 U3R20 SG - 32 TUBE ID Row - Col TUBE ID Row - Col 118 41 47 94 116 45 47 96 33 80 49 96 32 81 48 99 39 86 47 100 43 90 51 102 44 91 53 102 47 92 47 104 49 92 49 110 46 93 47 112 48 93 40 117 48 95 39 118 47 98 37 120 47 100 35 122 53 102 37 122 47 106 168 123 46 109 164 127 47 110 165 128 48 111 69 180 47 112 46 113 45 114 41 116 167 118 46 119 41 120 43 120 36 121 31 124 162 131 100 159