. ATTACHMENT 1 TECHNICAL SPECIFICATIONS CHANGE FOR A 0.95 K-EFFECTIVE AT REFUELING CONDITIONS 8604100304 860401 PDR ADOCK 05000280 P

PDR SURRY POWER STATION UNIT NOS. 1 AND 2

C, e

TS 1.0-1.

1.0 DEFINITIONS The following frequently used terms are defined for the uniform interpre-tation of the specifications.

A.

Rated Power A steady state reactor core heat output of 2441 MWt.

B.

Thermal Power The total core heat transferred from the fuel to the coolant.

c.

Reactor Operation

1.

Refueling Shutdown Condition When the reactor is subcritical by at least 5% 6k/k and T is avg

~140°F and fuel is scheduled to be moved to or from the reactor core.

2.

Cold Shutdown Condition When the reactor is subcritical by at least 1% 6k/k and T is avg

~200°F.

3.

Intermediate Shutdown Condition When the reactor is subcritical by an amount greater than or equal to i.77% 6k/k and 200°F < T

<547°F.